SE Digest 178

Starters, Type S

Type S Full Voltage Contactors and Starters

Class 8536 / Refer to Catalog 8502CT9701

www.se.com/us

2-Pole Single Phase—Open or NEMA 1, 4, and 4X NOTE: In Table 16.91, replace ●●● with the voltage code shown in . For melting alloy thermal units, see page 16-132.

Table 16.91: 2-Pole Single Phase—600 Vac Maximum—50–60 Hz (require 1 melting alloy thermal unit)

NEMA4&4X Watertight, Dusttight Brushed Stainless Steel Enclosure

NEMA4X Watertight, Dusttight, Corrosion-Resistant Glass-Polyester Enclosure

NEMA1 General Purpose Enclosure

Continuous Current Ratings

OpenType

Motor Voltage

Max. Hp

NEMA Size

Type

Type

Type

Type

115 230 115 230 115 230 115 230 115 230

1/3 1

00

9

SAO11●●●

SAG11●●●

UseSize0

UseSize0

1 2 2 3 3 5

SBO1●●●

SBG1●●●

SBW11●●●

SBW21●●●

0

18

SCO1●●●

SCG1●●●

SCW11●●●

SCW21●●●

1

27

SCO2●●●

SCG2●●●

SCW12●●●

SCW22●●●

1P

36

3 7-1/2

SDO6●●●

SDG6●●●

SDW16●●●

SDW26●●●

2

45

4-Pole, 2-Phase—Open and NEMA 1, 4, and 4X NOTE: In Table 16.92, replace ●●● with the voltage code shown in . For melting alloy thermal units, see page 16-132.

Table 16.92: 4-Pole, 2-Phase—600 Vac Maximum—50–60 Hz (require 2 melting alloy thermal units)

16 NEMA AND DEFINITE PURPOSE CONTACTORS AND STARTERS

NEMA4&4X Watertight, Dusttight Brushed Stainless Steel Enclosure

NEMA4X Watertight, Dusttight, Corrosion-Resistant Glass-Polyester Enclosure

NEMA1 General Purpose Enclosure

Continuous Current Ratings

OpenType

Motor Voltage

Max. Hp

NEMA Size

Type

Type

Type

Type

200 230 460 575 200 230 460 575 200 230 460 575 200 230 460 575 200 230 460 575

3 3 5 5

0

18

SBO3●●●

SBG3●●●

SBW13●●●

SBW23●●●

7-1/2 7-1/2

SCO4●●●

SCG4●●●

SCW14●●●

SCW24●●●

1

27

10 10 10 15 25 25 25 30 50 50 40 50

2

45

SDO2●●●

SDG2●●●

SDW12●●●

SDW22●●●

3

90

SEO2●●●

SEG2●●●

SEW12●●●

Consult the Customer Care Center at (1-888-778-2733)

4

135

SFO2●●●

SFG2●●●

SFW12●●●

100 100

NOTE: For voltage codes used with control transformers, see page 16-118. Form S (separate control) is used when a separate source of power is available for the control (coil) voltage. Form S is provided at no charge. Dimensions: page 16-39 Factory Modifications (Forms): page 16-117

Table 16.93: Coil Voltage Codes Voltage

Code

60Hz

50Hz

24 [22] 120 [23] 208 240 277 480 600 Specify

— 110 — 220 —

V01 V02 V08 V03 V04 V06 V07 V99

Separate Enclosures (Class 9991): page 16-110 Replacement Parts (Class 9998): page 16-122 Type S Accessories (Class 9999) page 16-125 For How to Order Information, see page 16-28.

440 550 Specify

[22] 24 V coils are not available on Sizes 4–7. On sizes 00–3, where 24 V coils are available, FormS (separate control) must be specified (i.e., order as 8536SBO2V01S). [23] 120 V polyphase starters are wired for separate control. FormS (separate control) must be specified (for example, order as 8536SCO2V02S).

16-35

© 2019 Schneider Electric All Rights Reserved

11/20/2019

Made with FlippingBook flipbook maker