SE Digest 178
I-Line™ Panelboards—600 Vac, 250 Vdc
Molded Case Circuit Breakes for I-Line™ Panelboards
www.se.com/us
Refer to Catalog 0612CT0101
Table 9.145: PowerPacT P- and R-frame Interrupt Ratings Voltage P-frame Interrupt Rating
R-frame Interrupt Rating
G
J
K
L
G
J
K
L
240Vac 480Vac 600Vac
65 kA 100 kA 65 kA 125 kA 65 kA 100 kA 65 kA 125 kA
35kA 65kA 18kA 25kA
50 kA 100 kA 35 kA 65 kA 50 kA 25 kA 18 kA 25 kA
65kA 100kA 65kA 50kA
P- and R-frame accessories, page . P- and R-frame dimensions, page . P- and R-frame optional lugs, page .
PG/PJ/PK/PL 2– and 3–pole
RG/RJ/RK/RL 2– and 3–pole
PowerPacT P- and R-frame for I-Line™ Panelboards and Switchboards
Table 9.146: PowerPacT P-frame 1200 A (600 Vac, 50/60 Hz) 3P Circuit Breaker with Electronic Trip Unit (PowerPacT P-frame circuit breakers utilize 9" of the available I-Line bussing.) Electronic Trip Unit
9 PANELBOARDS
Sensor Rating
Terminal WireRange
Cat. No. [78][79][80][81]
Type
Function
Code
P( )A36060 P( )A36080 P( )A36100 P( )A36120
600A 800A
(3) 3/0 AWG–500 kcmil Al or Cu AL800M23K (4) 3/0 AWG–500 kcmil Al or Cu AL1200P24K
Basic Electronic TripUnit (Not Interchangeable)
Fixed long-time, Adjustable Instantaneous
ET1.0I
1000A 1200A
P( )A36025(C)U31A P( )A36040(C)U31A P( )A36060(C)U31A P( )A36080(C)U31A P( )A36100U31A P( )A36120U31A P( )A36025(C)U33A P( )A36040(C)U33A P( )A36060(C)U33A P( )A36080(C)U33A P( )A36100U33A P( )A36120U33A P( )A36025(C)U41A P( )A36040(C)U41A P( )A36060(C)U41A P( )A36080(C)U41A P( )A36100U41A P( )A36120U41A P( )A36025(C)U43A P( )A36040(C)U43A P( )A36060(C)U43A P( )A36080(C)U43A P( )A36100U43A P( )A36120U43A P( )A36025(C)U44A P( )A36040(C)U44A P( )A36060(C)U44A P( )A36080(C)U44A P( )A36100U44A P( )A36120U44A P( )A36025(C)U63AE1 P( )A36040(C)U63AE1 P( )A36060(C)U63AE1 P( )A36080(C)U63AE1 P( )A36100U63AE1 P( )A36120U63AE1 P( )A36025(C)U64AE1 P( )A36040(C)U64AE1 P( )A36060(C)U64AE1 P( )A36080(C)U64AE1 P( )A36100U64AE1 P( )A36120U64AE1 P( )A36025(C)U73AE1 P( )A36040(C)U73AE1 P( )A36060(C)U73AE1 P( )A36080(C)U73AE1 P( )A36100U73AE1 P( )A36120U73AE1
250A 400A 600A 800A
(3) 3/0 AWG–500 kcmil Al or Cu AL800M23K
LI
3.0
1000A 1200A
(4) 3/0 AWG–500 kcmil Al or Cu AL1200P24K
MicroLogic Interchangeable Standard TripUnit
250A 400A 600A 800A
(3) 3/0 AWG–500 kcmil Al or Cu AL800M23K
LSI
5.0
1000A 1200A
(4) 3/0 AWG–500 kcmil Al or Cu AL1200P24K
250A 400A 600A 800A
(3) 3/0 AWG–500 kcmil Al or Cu AL800M23K
LI
3.0A
1000A 1200A
(4) 3/0 AWG–500 kcmil Al or Cu AL1200P24K
250A 400A 600A 800A
(3) 3/0 AWG–500 kcmil Al or Cu AL800M23K
MicroLogic Interchangeable Ammeter TripUnit
LSI
5.0A
1000A 1200A
(4) 3/0 AWG–500 kcmil Al or Cu AL1200P24K
250A 400A 600A 800A
(3) 3/0 AWG–500 kcmil Al or Cu AL800M23K
LSIG
6.0A
1000A 1200A
(4) 3/0 AWG–500 kcmil Al or Cu AL1200P24K
250A 400A 600A 800A
(3) 3/0 AWG–500 kcmil Al or Cu AL800M23K
LSI
5.0P
1000A 1200A
(4) 3/0 AWG–500 kcmil Al or Cu AL1200P24K
MicroLogic Interchangeable Power TripUnit
250A 400A 600A 800A
(3) 3/0 AWG–500 kcmil Al or Cu AL800M23K
LSIG
6.0P
1000A 1200A
(4) 3/0 AWG–500 kcmil Al or Cu AL1200P24K
250A 400A 600A 800A
(3) 3/0 AWG–500 kcmil Al or Cu AL800M23K
MicroLogic Interchangeable Harmonic TripUnit
LSI
5.0H
1000A 1200A
(4) 3/0 AWG–500 kcmil Al or Cu AL1200P24K
[78] To complete the catalog number, replace the blank ( ) with the appropriate interrupt rating (G, J, K, or L). [79] For 100% rated circuit breakers add a “C” in the 9th character place. For example, the catalog number for a 100% standard-type trip unit with LI trip functions at 250 A would be PGA36025 C U31A. [80] The L interrupt rating is supplied in 480 V only. Change the 5 th character (voltage rating) from a 6 (600 V) to a 4 (480 V); for example, PLA3 4 025U31A. [81] See Table 9.145 PowerPacT P- and R-frame Interrupt Ratings, page 9-61 for interrupt ratings.
9-61
© 2021 Schneider Electric All Rights Reserved 6/20/2021
Made with FlippingBook flipbook maker