SE Digest 178

I-Line™ Panelboards—600 Vac, 250 Vdc

Molded Case Circuit Breakes for I-Line™ Panelboards

www.se.com/us

Refer to Catalog 0612CT0101

Table 9.145: PowerPacT P- and R-frame Interrupt Ratings Voltage P-frame Interrupt Rating

R-frame Interrupt Rating

G

J

K

L

G

J

K

L

240Vac 480Vac 600Vac

65 kA 100 kA 65 kA 125 kA 65 kA 100 kA 65 kA 125 kA

35kA 65kA 18kA 25kA

50 kA 100 kA 35 kA 65 kA 50 kA 25 kA 18 kA 25 kA

65kA 100kA 65kA 50kA

P- and R-frame accessories, page . P- and R-frame dimensions, page . P- and R-frame optional lugs, page .

PG/PJ/PK/PL 2– and 3–pole

RG/RJ/RK/RL 2– and 3–pole

PowerPacT P- and R-frame for I-Line™ Panelboards and Switchboards

Table 9.146: PowerPacT P-frame 1200 A (600 Vac, 50/60 Hz) 3P Circuit Breaker with Electronic Trip Unit (PowerPacT P-frame circuit breakers utilize 9" of the available I-Line bussing.) Electronic Trip Unit

9 PANELBOARDS

Sensor Rating

Terminal WireRange

Cat. No. [78][79][80][81]

Type

Function

Code

P( )A36060 P( )A36080 P( )A36100 P( )A36120

600A 800A

(3) 3/0 AWG–500 kcmil Al or Cu AL800M23K (4) 3/0 AWG–500 kcmil Al or Cu AL1200P24K

Basic Electronic TripUnit (Not Interchangeable)

Fixed long-time, Adjustable Instantaneous

ET1.0I

1000A 1200A

P( )A36025(C)U31A P( )A36040(C)U31A P( )A36060(C)U31A P( )A36080(C)U31A P( )A36100U31A P( )A36120U31A P( )A36025(C)U33A P( )A36040(C)U33A P( )A36060(C)U33A P( )A36080(C)U33A P( )A36100U33A P( )A36120U33A P( )A36025(C)U41A P( )A36040(C)U41A P( )A36060(C)U41A P( )A36080(C)U41A P( )A36100U41A P( )A36120U41A P( )A36025(C)U43A P( )A36040(C)U43A P( )A36060(C)U43A P( )A36080(C)U43A P( )A36100U43A P( )A36120U43A P( )A36025(C)U44A P( )A36040(C)U44A P( )A36060(C)U44A P( )A36080(C)U44A P( )A36100U44A P( )A36120U44A P( )A36025(C)U63AE1 P( )A36040(C)U63AE1 P( )A36060(C)U63AE1 P( )A36080(C)U63AE1 P( )A36100U63AE1 P( )A36120U63AE1 P( )A36025(C)U64AE1 P( )A36040(C)U64AE1 P( )A36060(C)U64AE1 P( )A36080(C)U64AE1 P( )A36100U64AE1 P( )A36120U64AE1 P( )A36025(C)U73AE1 P( )A36040(C)U73AE1 P( )A36060(C)U73AE1 P( )A36080(C)U73AE1 P( )A36100U73AE1 P( )A36120U73AE1

250A 400A 600A 800A

(3) 3/0 AWG–500 kcmil Al or Cu AL800M23K

LI

3.0

1000A 1200A

(4) 3/0 AWG–500 kcmil Al or Cu AL1200P24K

MicroLogic Interchangeable Standard TripUnit

250A 400A 600A 800A

(3) 3/0 AWG–500 kcmil Al or Cu AL800M23K

LSI

5.0

1000A 1200A

(4) 3/0 AWG–500 kcmil Al or Cu AL1200P24K

250A 400A 600A 800A

(3) 3/0 AWG–500 kcmil Al or Cu AL800M23K

LI

3.0A

1000A 1200A

(4) 3/0 AWG–500 kcmil Al or Cu AL1200P24K

250A 400A 600A 800A

(3) 3/0 AWG–500 kcmil Al or Cu AL800M23K

MicroLogic Interchangeable Ammeter TripUnit

LSI

5.0A

1000A 1200A

(4) 3/0 AWG–500 kcmil Al or Cu AL1200P24K

250A 400A 600A 800A

(3) 3/0 AWG–500 kcmil Al or Cu AL800M23K

LSIG

6.0A

1000A 1200A

(4) 3/0 AWG–500 kcmil Al or Cu AL1200P24K

250A 400A 600A 800A

(3) 3/0 AWG–500 kcmil Al or Cu AL800M23K

LSI

5.0P

1000A 1200A

(4) 3/0 AWG–500 kcmil Al or Cu AL1200P24K

MicroLogic Interchangeable Power TripUnit

250A 400A 600A 800A

(3) 3/0 AWG–500 kcmil Al or Cu AL800M23K

LSIG

6.0P

1000A 1200A

(4) 3/0 AWG–500 kcmil Al or Cu AL1200P24K

250A 400A 600A 800A

(3) 3/0 AWG–500 kcmil Al or Cu AL800M23K

MicroLogic Interchangeable Harmonic TripUnit

LSI

5.0H

1000A 1200A

(4) 3/0 AWG–500 kcmil Al or Cu AL1200P24K

[78] To complete the catalog number, replace the blank ( ) with the appropriate interrupt rating (G, J, K, or L). [79] For 100% rated circuit breakers add a “C” in the 9th character place. For example, the catalog number for a 100% standard-type trip unit with LI trip functions at 250 A would be PGA36025 C U31A. [80] The L interrupt rating is supplied in 480 V only. Change the 5 th character (voltage rating) from a 6 (600 V) to a 4 (480 V); for example, PLA3 4 025U31A. [81] See Table 9.145 PowerPacT P- and R-frame Interrupt Ratings, page 9-61 for interrupt ratings.

9-61

© 2021 Schneider Electric All Rights Reserved 6/20/2021

Made with FlippingBook flipbook maker