SE Digest 178
I-Line™ Panelboards—600 Vac, 250 Vdc
Molded Case Circuit Breakes for I-Line™ Panelboards
www.se.com/us
Refer to Catalog 0612CT0101 Table 9.146 PowerPacT P-frame 1200 A (600 Vac, 50/60 Hz) 3P Circuit Breaker with Electronic Trip Unit(PowerPacT P-frame circuit breakers utilize 9" of the available I-Line bussing.) (cont'd.) Electronic Trip Unit
Sensor Rating
Terminal WireRange
Cat. No. [82][83][84][85]
Type
Function
Code
P( )A36025(C)U74AE1 P( )A36040(C)U74AE1 P( )A36060(C)U74AE1 P( )A36080(C)U74AE1 P( )A36100U74AE1 P( )A36120U74AE1
250A 400A 600A 800A
(3) 3/0 AWG–500 kcmil Al or Cu AL800M23K
LSIG
6.0H
1000A 1200A
9 PANELBOARDS
(4) 3/0 AWG–500 kcmil Al or Cu AL1200P24K
Table 9.147: PowerPacT R-frame 1200 A (600 Vac, 50/60 Hz) 3P Circuit Breaker with Electronic Trip Unit Electronic Trip Unit
Terminal Wire Range
Sensor Rating 1200A 1000A 1200A 1000A 1200A 1000A 1200A 1000A 1200A 1000A 1200A 1000A 1200A 1000A 1200A 1000A 1200A 1000A 1200A
Cat. No. [82][83][84][85]
Type
Function
Code
Basic Electronic Trip Unit (Not Interchangeable)
Fixed Long-Time, Adjustable Instantaneous
R( )A36120
ET1.01
R( )A36100CU31A R( )A36120CU31A R( )A36100CU33A R( )A36120CU33A R( )A36100CU41A R( )A36120CU41A R( )A36100CU43A R( )A36120CU43A R( )A36100CU44A R( )A36120CU44A R( )A36100CU63AE1 R( )A36120CU63AE1 R( )A36100CU64AE1 R( )A36120CU64AE1 R( )A36100CU73AE1 R( )A36120CU73AE1 R( )A36100CU74AE1
LI
3.0
MicroLogic Interchangeable Standard TripUnit
LSI
5.0
LI
3.0A
MicroLogic Interchangeable Ammeter TripUnit
LSI
5.0A
AL1200R53K (4) 3/0-600 kcmil Al orCu
LSI
6.0A
LSI
5.0P
MicroLogic Interchangeable Power TripUnit
LSIG
6.0P
LSI
5.0H
MicroLogic Interchangeable Harmonic TripUnit
LSIG
6.0H
R( )A36120CU74AE1 P- and R-frame accessories, Mechanical Lugs, page .
P- and R-frame dimensions, Molded Case Circuit Breaker Dimensions, page . P- and R-frame trip unit options, MicroLogic™ Electronic Trip Units, page . P- and R-frame optional lugs, Mechanical Lugs, page . P- and R-frame alternate rating plugs, MicroLogic™ Electronic Trip Units, page .
[82] To complete the catalog number, replace the blank ( ) with the appropriate interrupt rating (G, J, K, or L). [83] For 100% rated circuit breakers add a “C” in the 9th character place. For example, the catalog number for a 100% standard-type trip unit with LI trip functions at 250 A would be PGA36025 C U31A. [84] The L interrupt rating is supplied in 480 V only. Change the 5 th character (voltage rating) from a 6 (600 V) to a 4 (480 V); for example, PLA3 4 025U31A. [85] See Table 9.145 PowerPacT P- and R-frame Interrupt Ratings, page 9-61 for interrupt ratings.