SE Digest 178
I-Line™ Panelboards—600 Vac, 250 Vdc
Molded Case Circuit Breakes for I-Line™ Panelboards
www.se.com/us
Refer to I-Line Power Distribution Panelboards Table 9.143: PowerPacT M-frame: with ET1.0 Factory – sealed trip unit (not field adjustable)—800 A [73] (PowerPacT M-frame circuit breakers utilize 9" of the available I-Line bussing.) Ampere Rating Adjustable Instantaneous TripRange [74] G Interrupting J Interrupting
Terminal WireRange
High 3000 3500 4000 4500 5000 6000 7000 8000 3000 3500 4000 4500 5000 6000 7000 8000
Catalog Number [75]
Catalog Number [75]
Low
MGA26300( ) MGA26350( ) MGA26400( ) MGA26450( ) MGA26500( ) MGA26600( ) MGA26700( ) MGA26800( )
MJA26300( ) MJA26350( ) MJA26400( ) MJA26450( ) MJA26500( ) MJA26600( ) MJA26700( ) MJA26800( )
300A 350A 400A 450A 500A 600A 700A 800A 300A 350A 400A 450A 500A 600A 700A 800A
600 700 800 900
3–3/0 through 500 kcmil Al orCu
2-pole, 600 Vac, 50/60Hz 9 PANELBOARDS 3-pole, 600 Vac, 50/60Hz
1000 1200 1400 1600
600 700 800 900
MGA36300 MGA36350 MGA36400 MGA36450 MGA36500 MGA36600 MGA36700 MGA36800
MJA36300 MJA36350 MJA36400 MJA36450 MJA36500 MJA36600 MJA36700 MJA36800
3–3/0 through 500 kcmil Al orCu
1000 1200 1400 1600
L-frame accessories, see Supplemental Digest Section 3. L-frame dimensions, page . L-frame optional lugs, page .
M-frame accessories, page . M-frame dimensions, page . M-frame optional lugs, page .
Table 9.144: Automatic Molded Case Switches—600 Vac, 50/60 Hz Ampere Rating 2-pole 3-pole Catalog Number [77] Catalog Number 240Vac
Withstand Rating [76]
Trip Point Amperes
Terminal WireRange
480Vac
600Vac
AC
PJA26000S60( ) PJA26000S80( ) PJA26000S10( ) PJA26000S12( )
600A 800A
PJA36000S60 PJA36000S80 PJA36000S10 PJA36000S12
100 100 100 100
65 65 65 65
25 25 25 25
10000 10000 10000 10000
3–3/0 through 500 kcmil Al or Cu 4–3/0 through 500 kcmil Al or Cu
1000A 1200A
[73] The ET 1.0 trip unit cannot be field replaced, nor does it allow adjustment of the long-time trip point setting. It is considered an electronic equivalent of a thermal-magnet circuit breaker. [74] UL magnetic trip setting tolerances are ±10% from the nominal values shown. [75] Fill in parentheses with the following phase connection options: (2) for AC and (5) for CA. [76] The withstand rating is the fault current, at rated voltage, that the molded case switch will withstand without damage when protected by a circuit breaker with an equal ampere rating. [77] Fill in parentheses with the following phase connection options: (2) for AC or (5) for CA.
9-60
© 2021 Schneider Electric All Rights Reserved 6/20/2021
Made with FlippingBook flipbook maker