SE Digest 178
Sepam™ Characteristics
Sepam™ Protection Relays
www.se.com/us
Sepam™ 20/40/80 Characteristics
Table 5.3: Protection Configurations Characteristics
Series20
Series40
Series80
Logic inputs Logic outputs
0-10
0-10
0-42 5-23 0-16
4-8 0-8
4-8
Temperature sensors
0-16
Current 3I + I0 Voltage 3V + V0
Current 3I + I0 Voltage 3V + V0
Current 2 x 3I + 2 x I0 Voltage 2 x 3V + V0
Channels
LPCT [1]
LPCT [1]
LPCT [1]
1-2
1-2
2-4
ModBus, IEC 103, DNP3, IEC 61850
ModBus, IEC 103, DNP3, IEC 61850
ModBus, IEC 103, DNP3, IEC 61850
Communication Ports
Redundancy
Redundancy
— —
Goose Messaging
—
Matrix [2]
Matrix [2]
Matrix [2]
Logic equation editor
Logic equation editor
Control
Logipam [3]
— — —
— —
Front memory cartridge with settings
Other
Backup 48 hours (capacitor)
Backup lithium battery [4]
Table 5.4: Metering Measurements (Basic — Sepam Series 20) Metering
Measurement Range
Accuracy
Phase Current / Residual Current (Calculated)
0.1 to40 In 0.1 to 20 In0 0.1 to40 In 0.05 to 1.2 Vnp 0.015 to 3 Vnp 0.05 to 1.2 Vnp
±1% ±1% ±1% ±1% ±1% ±5%
Residual Current (Measured)
Demand Current / Peak Demand Current Phase-to-Phase Voltage / Phase-to-Neutral Voltage
Residual Voltage
Positive Sequence Voltage
Frequency Temperature
50±5Hzor60±5Hz
±0.05Hz
-22 to +392 °F (-30 to +200 °C)
±1 °C from -20 to +140 °C
Table 5.5: Metering Measurements (Standard — Sepam Series 40) Metering
Measurement Range
Accuracy
Phase Current / Residual Current (Calculated)
0.1 to40 In 0.1 to 20 In0 0.1 to40 In 0.06 to 1.2 Vnp 0.04 to 3 Vnp 0.05 to 1.2 Vnp
±0.5%
Residual Current (Measured)
±1%
Demand Current / Peak Demand Current Phase-to-Phase Voltage / Phase-to-Neutral Voltage
±0.5% ±0.5%
Residual Voltage
±1% ±2% ±1% ±1% ±1% ±1% ±1% ±1%
Positive Sequence Voltage / Negative Sequence Voltage
Frequency
25 to65Hz
±0.02Hz
Active Power Reactive Power Apparent Power
0.015 Sn to 999 MW 0.015 Sn to 999 MVar 0.015 Sn to 999 MVA 0.015 Sn to 999 MW 0.015 Sn to 999 MVar -1 to +1 (CAP/IND) 0 to 2.1x108 MWH 0 to 2.1x108 MVARH
Peak Demand Active Power Peak Demand Reactive Power
Power Factor
Calculated Active Energy Calculated Reactive Energy
±1% ±1 digit ±1% ±1 digit
Temperature
-22 to +392 °F (-30 to +200 °C
±1 °C from -20 to +140 °C
Table 5.6: Metering Measurements (Advanced — Sepam Series 80) Metering
Measurement Range
Accuracy
Phase Current
0.02 to 40 In 0.005 to 40 In 0.005 to 20 In0 0.02 to 40 In 0.05 to 1.2 Vnp 0.015 to 3 Vnp 0.05 to 1.2 Vnp
±0.5%
Residual Current (Calculated) Residual Current (Measured)
±1% ±1%
5 PROTECTION, CONTROL, AND ENERGYAUTOMATION
Demand Current / Peak Demand Current Phase-to-Phase Voltage / Phase-to-Neutral Voltage
±0.5% ±0.5%
Residual Voltage / Neutral Point Voltage
±1% ±2% ±1% ±1% ±1% ±1% ±1% ±1%
Positive Sequence Voltage / Negative Sequence Voltage
Frequency
50±5Hzor60±5Hz 0.008 Sn to 999 MW 0.008 Sn to 999 MVar 0.008 Sn to 999 MVA 0.008 Sn to 999 MW 0.008 Sn to 999 MVar -1 to +1 (CAP/IND) 0 to 2.1x108 MWH 0 to 2.1x108 MVARH
±0.01Hz
Active Power Reactive Power Apparent Power
Peak Demand Active Power Peak Demand Reactive Power
Power Factor
Calculated Active Energy Calculated Reactive Energy
±1% ±1 digit ±1% ±1 digit
Temperature
-22 to +392 °F (-30 to +200 °C)
±1 °C from -20 to +140 °C
Rotation Speed
0 to 7200 RPM
±1RPM
[1] LPCT: low-power current transducer complying with standard IEC 60044-8. [2] Control matrix for simple assignment of information from the protection, control and monitoring functions. [3] Logipam ladder language (PC programming environment) to make full use of Sepam series 80 functions. [4] Standard lithium battery 1/2 AA format 3.6 V front face exchangeable.