NF Factory Assembled Panelboard Common Features
NF Panelboards—600Y/347 Vac Max.
Refer to NF Panelboards
www.se.com/us
Table 9.66: NF Main Neutral Conductors—(Quantity) and Wire Size
Mechanical Neutral Line Lugs
Compression Neutral Line Lugs
Interior Rating
Standard
Oversized
Standard
Neutral Lug Wire Range
Actual Lug Wire Range (1) #6 AWG-350 kcmil (2) 1/0 AWG-300 kcmil or (1) 1/0 AWG-750 kcmil
Actual Lug Wire Range (1) #6-1/0 AWG Cu or (1) #4-300 kcmil Al (1) 2/0 AWG-300 kcmil Cu or (1) 250-350 kcmil Al (1) 400-750 kcmil Cu or (1) 2/0 AWG-500 kcmil Al (1) 2/0 AWG-500 kcmil Cu orAl
(1) 2/0 AWG Cu or Al (1) 250 kcmil Cu or (1) 350 kcmil Al
125A
250A
400A
—
9 PANELBOARDS
(2) 1/0 AWG 300 kcmil or (1) 700 kcmil Cu or Al
(2) 1/0 AWG-750 kcmil Cu or Al [58] (3) 4/0 AWG-500 kcmil Cu or Al [59]
600A
800A — NOTE: 200% applications require gutter mounted neutral in special (W x 26 in.) enclosure factory assembled only. One exception, without subfeed lugs, feed-thru lugs and subfeed breakers 400 A (30-84 circuit interiors) and 600 A (30-54 circuit interiors) does not require an special enclosure. Neutral conductors must be of size and quantity per table above.
Table 9.67: Metal Directory Frame
Metal Directory Frame Metal Directory Frames are available as a premium factory assembled alternative to standard plastic directory card holders on the back of panelboard trim fronts. Table 9.68: Hinged Door-in-Door Trim Hinged Door-in-Door Trim Hinged Door-in-Door Trim has piano hinge down one side. Inner door has a lock, outer door is retained with screws Hinged Door-in-Door with Outer Door Lock in place of screws Table 9.69: Weatherproof or Dusttight Cabinets NEMA Type 3R, 4, 4X, 5, 12) Weather resistant and Dust resistant Cabinets —Type 3R, 4, 4X, 5, 12 NEMA Type 4, 4X, 4, 12 enclosures not available with panelboards having PowerPacT L circuit breakers Table 9.70: Optional Factory Assembled Lugs for Main Lug Only and Main Circuit Breaker Interiors Incoming Lugs Type Aluminum Compression Lugs
Copper Mechanical Lugs Copper Compression Lugs Table 9.71: Surgelogic ™ Hard Bus SPD—Model [60] Surge Current RatingkA
100 120 160 200 240
Table 9.72: Surgelogic SPD Options
Surgelogic SPD Options
Surge Counter Dry Contacts Remote Monitor NOTE: For additional factory modifications, see Modifications For Factory Assembled Panelboards, page 9-66. Table 9.73: NQ and NF Lighting Contactors—Mechanically Held (Furnish a one-line power and control voltage connection diagram.) ASCO 920 Series Ampacity 2-Pole 3-Pole 30 Y Y 60 Y Y 75 Y Y 100 Y Y 150 Y Y 225 Y Y NOTE: Lighting Contactors increase box & trim length by 18 in. (457 mm)
[58] Factory Assembled only; increases enclosure length 6"-12". [59] Factory Assembled only; enclosure length increases 6-12"; requires 8.75" deep D9 enclosure. [60] Panelboard box height with SPD unit—Contact your local Schneider Electric representative or distributor.