Table 7.122: PowerPact P- and R-Frame MicroLogic Trip Unit and Options Model Protection Additional Features
Field-Installable Cat. No. [2]
2.0 (IEC only)
LSO
S132R S131A S133A
3.0 (UL/ANSI only)
None
LI
5.0
LSI
2.0A (IEC only)
S142R [3] S141A [3] S143A [3] S144A [3]
LSO
3.0A (UL/ANSI only)
LI
Ammeter
5.0A 6.0A 5.0P 6.0P 5.0H 6.0H
LSI
LSIG
S163A [3][4] S164A [3][4] S173A [3][4] S174A [3][4]
LSI
Metering, Adv. Protection
LSIG
LSI
Metering, Adv. Protection & Harmonic Analysis
LSIG
Table 7.123: PowerPact P- and R-Frame MicroLogic Trip Units x– Standard Feature o – Available Option Features Standard Ammeter
Power Harmonic 3.0 5.0 3.0A 5.0A 6.0A 5.0P 6.0P 5.0H 6.0H X — X — — — — — — — X — X X X X X X — — — — X — X — X — — — — — X — X — — — — — — — X — X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X — — X X X X X X X X X X X X X X X X — — X X X X X X X — — X X X X X X X — — X X X X X X X — — X X X X X X X — — — — — X X X X — — — — — X X X X — — — — — X X X X — — — — — X X X X — — — — — X X X X — — — — — X X X X — — — — — X X X X — — — — — X X X X — — — — — — — X X — — — — — — — X X
LI
LSI (Instantaneous can be turned off)
LSIG / Ground-Fault Trip [5]
Ground-Fault Alarm (No Trip) [5][6] Ground-Fault Alarm and Trip [5][6]
Adjustable Rating Plugs
True RMS Sensing
ULListed
Thermal Imaging
Phase Loading Bar Graph LED for Long-time Pickup LED for Trip Indication
Digital Ammeter
Zone-selective Interlocking
Communications
LCD Dot Matrix Display Advanced User Interface Protective Relay Functions Neutral Protection Contact Wear Indication
Incremental Fine Tuning of Settings Selectable Long-time Delay Bands
Power Measurement
Power Quality Measurements
Waveform Capture
Table 7.124: PowerPact P- and R-Frame Long-Time Pickup Settings Rating Plug Long-time Pickup Settings A .40 .45 .50 .60 .63 .70 .80 .90
1.0 1.0 1.0 1.0 1.0 1.0 .82 .64
B C D E F G H
.40 .42 .40 .60 .84 .66 .48
.44 .50 .48 .70 .86 .68 .50
.50 .53 .64 .75 .88 .70 .52
.56 .58 .70 .80 .90 .72 .54
.63 .67 .80 .85 .92 .74 .56
.75 .75 .90 .90 .94 .76 .58
.88 .83 .93 .93 .96 .78 .60
.95 .95 .95 .95 .98 .80 .62
Table 7.125: Special Options Description Ship circuit breaker in closed position CT Characterization (Calibrated trip system) Alternate Maintenenace Setting (AMS) kit (use with 5.0/6.0 A, P or H and 5.3/6.3 A or E MicroLogic trip units) Energy Reduction Maintenenace Setting (ERMS) kit (use with 5.0/6.0 P or H MicroLogic trip units)
Field-Installable Cat. No.
Factory-Installed Suffix
YK
N/A N/A
Q
—
84957
—
84956
120Vac 24Vdc
LV429659 LV429658
Maintenance Mode Setting Switch kit
[2] The standard rating plug supplied with a trip unit will be the “A” rating plug. To specify an alternative adjustable rating plug, please add the letter designation to the end of the catalog number. Please refer to page 7-64 for a complete listing of adjustable settings available with each plug. (Example: S143B would specify a “B” rating plug instead of the standard "A" plug.) Use suffix “N” if no rating plug is required, deduct. [3] When replacing a standard trip unit with Type A (Ammeter), P (Power metering) or H (Harmonic analysis) trip unit, order the 12-pin connector kit S33101 for the MasterPact NW and NT and the PowerPacT P-frame drawout circuit breakers or kit S33100 for PowerPacT P-frame and R-frame unit-mount and I-Line circuit breakers. See page 7-64. [4] Requires Circuit Breaker Communications Module. [5] Requires neutral current transformer in 3Ø4W systems. [6] Alarm history is available through the trip unit display and communications. Local indication of an alarm requires an M2C Programmable Contact Module.
CIRCUIT BREAKERS
7 MINIATURE AND MOLDED CASE