SE Modicon M580 Brochure

Modicon M580 automation platform Architectures High-availability I/O architectures

Overview (continued)

Modicon M580 architecture type

High-availability architectures for remote I/O (primary and redundant CPU)

High-availability architectures for distributed I/O (primary and redundant CPU) High-availability architectures for hybrid I/O (primary and redundant CPU)

1

1

Remote over Ethernet

Distributed over Ethernet

Distributed and remote over Ethernet

Hot Standby topology with devices hardwired on remote I/O over Ethernet

Hot Standby topology with devices linked to distributed I/O over Ethernet

Hot Standby topology with devices available on distributed and remote I/O over Ethernet

Remote I/O architecture

Distributed I/O architecture

Mixed RIO/DIO architecture

2

2

Ethernet

Ethernet

Ethernet

Fiber optic

Fiber optic

Ethernet fiber optic network

Fiber optic

3

3

4

4

Expanded rack (with X-bus rack expansion module)

No local I/O on high-availability architecture

5

5

Backplane compatibility BMEXBP pp 00 Ethernet + X-bus backplanes

Compatible for main racks (remote only)

BMXXBP pp 00 X-bus backplanes PV02 (or later)

Mandatory for expansion racks (main or remote) Compatible with any rack provided that no Modicon X80 I/O Ethernet modules (such as weighing, HART, and BMECRA31210 modules) are used in the racks

Compatible CPU types CPU Ethernet ports

All redundant processors are compatible

SERVICE port

One SERVICE port for HMI, EcoStruxure Control Expert (1) , control network, variable speed drive, etc.

Dual ports are used for remote equipment (RIO scanner) (3) , BMECRA31210 Ethernet drop adapter is mandatory in RIO drop (4) A maximum of 31 RIO drops can be supported in an M580 network

Dual port

Dual ports are used for remote equipment

Dual ports are used for distributed equipment (DIO scanner) (2)

6

6

RIO drops

A maximum of 31 RIO drops can be supported in an M580 network

Communication

AS-Interface module

BMXEIA0100

Yes Yes

Yes, in a local rack or RIO drop Yes, in a local rack or RIO drop

Serial link module

BMXNOM0200

RTU module

BMENOR2200H BMENOP0300 BMENUA0100

Yes, only in local rack

7

7

IEC 61850 module

Yes

Yes, only in a local rack

OPC UA module

Yes, only in local rack Yes, only in local rack

Ethernet communication modules BMENOC03 p 1

CANopen module

BMECXM0100 PMEPXM0100

No

PROFIBUS DP Master module

Yes, only in local rack

8

8

Expert functions

PTO (pulse train output) module BMXMSP0200

No

Other expert modules: counter, SSI encoder, etc.

Yes, in an RIO drop Yes, in an RIO drop

No

Yes, in an RIO drop Yes, in an RIO drop

Time stamping

1 ms max. between modules in the same rack as ERT time stamping module 10 ms with CRA I/O drop adapter combined with discrete I/O modules in the RIO drop

BMXERT1604T

Yes

BMECRA31210

Yes, only in the RIO drop, system mode with OFS (2)

Yes, only in the RIO drop, system mode with OFS (2)

9

9

Pages

5/17

5/17

5/17

(1) Unity Pro software in earlier versions. (2) Distributed I/O can also be connected through the dual port of a BMENOC03 p 1 module (3) NRP Fiber converter can be used in case of long distance network (4) BMXCRA31210 modules are also compatible.

10

10

More technical Information on www.se.com

More technical Information on www.se.com

5/4

5/5

Made with FlippingBook flipbook maker