Modicon M580 automation platform Architectures High-availability I/O architectures
Overview (continued)
Modicon M580 architecture type
High-availability architectures for remote I/O (primary and redundant CPU)
High-availability architectures for distributed I/O (primary and redundant CPU) High-availability architectures for hybrid I/O (primary and redundant CPU)
1
1
Remote over Ethernet
Distributed over Ethernet
Distributed and remote over Ethernet
Hot Standby topology with devices hardwired on remote I/O over Ethernet
Hot Standby topology with devices linked to distributed I/O over Ethernet
Hot Standby topology with devices available on distributed and remote I/O over Ethernet
Remote I/O architecture
Distributed I/O architecture
Mixed RIO/DIO architecture
2
2
Ethernet
Ethernet
Ethernet
Fiber optic
Fiber optic
Ethernet fiber optic network
Fiber optic
3
3
4
4
Expanded rack (with X-bus rack expansion module)
No local I/O on high-availability architecture
5
5
Backplane compatibility BMEXBP pp 00 Ethernet + X-bus backplanes
Compatible for main racks (remote only)
BMXXBP pp 00 X-bus backplanes PV02 (or later)
Mandatory for expansion racks (main or remote) Compatible with any rack provided that no Modicon X80 I/O Ethernet modules (such as weighing, HART, and BMECRA31210 modules) are used in the racks
Compatible CPU types CPU Ethernet ports
All redundant processors are compatible
SERVICE port
One SERVICE port for HMI, EcoStruxure Control Expert (1) , control network, variable speed drive, etc.
Dual ports are used for remote equipment (RIO scanner) (3) , BMECRA31210 Ethernet drop adapter is mandatory in RIO drop (4) A maximum of 31 RIO drops can be supported in an M580 network
Dual port
Dual ports are used for remote equipment
Dual ports are used for distributed equipment (DIO scanner) (2)
6
6
RIO drops
A maximum of 31 RIO drops can be supported in an M580 network
–
Communication
AS-Interface module
BMXEIA0100
Yes Yes
Yes, in a local rack or RIO drop Yes, in a local rack or RIO drop
Serial link module
BMXNOM0200
RTU module
BMENOR2200H BMENOP0300 BMENUA0100
Yes, only in local rack
7
7
IEC 61850 module
Yes
Yes, only in a local rack
OPC UA module
Yes, only in local rack Yes, only in local rack
Ethernet communication modules BMENOC03 p 1
CANopen module
BMECXM0100 PMEPXM0100
No
PROFIBUS DP Master module
Yes, only in local rack
8
8
Expert functions
PTO (pulse train output) module BMXMSP0200
No
Other expert modules: counter, SSI encoder, etc.
Yes, in an RIO drop Yes, in an RIO drop
No
Yes, in an RIO drop Yes, in an RIO drop
Time stamping
1 ms max. between modules in the same rack as ERT time stamping module 10 ms with CRA I/O drop adapter combined with discrete I/O modules in the RIO drop
BMXERT1604T
Yes
BMECRA31210
Yes, only in the RIO drop, system mode with OFS (2)
–
Yes, only in the RIO drop, system mode with OFS (2)
9
9
Pages
5/17
5/17
5/17
(1) Unity Pro software in earlier versions. (2) Distributed I/O can also be connected through the dual port of a BMENOC03 p 1 module (3) NRP Fiber converter can be used in case of long distance network (4) BMXCRA31210 modules are also compatible.