SE Modicon M580 Brochure
Modicon M580 automation platform Architectures Standard I/O architectures
Overview
Modicon M580 architecture type Note: These architectures can be combined with each other
Architectures with local racks (main rack and expansion racks)
Architecture with local racks (main rack and expansion racks)
Architecture with racks in remote drops
1
1
Hardwired
Distributed peripherals over fieldbuses
Distributed peripherals and I/O over Ethernet
Remote over Ethernet
Compact topology with devices hardwired on local I/O
Compact topology with devices distributed over fieldbuses Distributed devices and I/O topology over Ethernet
Remote I/O + remote functions (including fieldbus master)
Local I/O architecture
Integrated fieldbus architecture
Distributed I/O architecture
Remote I/O architecture
2
2
Ethernet
X-bus
3
3
HART
AS
Interface
X-bus
Ethernet
Product name
Label MAC-Address
4
4
Modbus
Expansion rack (with X-bus rack expansion module)
Main local rack with up to 7 local expansion racks on X-bus (Modicon Premium or Modicon X80 racks)
Main local rack with up to 7 local expansion racks on X-bus (Modicon Premium or Modicon X80 racks), RIO drop with up to 1 remote expansion rack on X-bus (only Modicon X80 racks)
5
5
Backplane compatibility BMEXBP pp 00 Ethernet + X-bus backplanes
Compatible for main racks (local or remote)
BMXXBP pp 00 X-bus backplanes PV02 (or later)
Mandatory for expansion racks (main or remote) Compatible with any rack provided that no Modicon X80 I/O Ethernet modules (such as weighing, HART, and BMECRA31210 modules) are used in the racks
BMEP58 pp 40 CPUs are required to manage RIO
Compatible CPU types CPU Ethernet ports
All standalone processors are compatible (1)
SERVICE port
One SERVICE port for HMI, EcoStruxure Control Expert (2) , control network, variable speed drive, etc.
6
6
Dual port
Dual ports are not used
Dual ports are used for distributed equipment (DIO scanner)
Dual ports are used for remote equipment (RIO scanner), BMECRA31210 Ethernet drop adapter is mandatory in RIO drop (3) A maximum of 32 RIO drops can be supported in an M580 network
RIO drops
–
Communication
AS-Interface module
BMXEIA0100
Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
Yes, in a local rack or RIO drop Yes, in a local rack or RIO drop
7
7
Serial link module
BMXNOM0200
RTU modules
BMXNOR0200H BMENOR2200H BMENOP0300 BMENUA0100
Yes, only in a local rack Yes, only in a local rack Yes, only in a local rack
IEC 61850 module
OPC UA module
No
8
8
Ethernet communication modules BMENOC03 p 1
Yes, only in a local rack
CANopen module
BMECXM0100 PMEPXM0100
Yes, in a local rack or RIO drop
PROFIBUS DP Master module
Expert functions
PTO (pulse train output) module BMXMSP0200
Yes, only in a local rack
Other expert modules: counter, SSI encoder, etc.
Yes, in a local rack or RIO drop Yes, in a local rack or RIO drop
9
9
Time stamping
1 ms max. between modules in the same rack as ERT time stamping module 10 ms with CRA I/O drop adapter combined with discrete I/O modules in the RIO drop
BMXERT1604T
BMECRA31210
–
Yes, only in the RIO drop, system mode with OFS (3)
Pages
5/9
5/10
5/11
5/12
10
10
(1) BMEP58 pp 40 CPUs are not mandatory. (2) Unity Pro software in earlier versions. (3) BMXCRA31210 modules are also compatible