Square D Digest 179
TeSys™ Deca GV Manual Starters and Protectors Refer to Catalog MKTED210011EN and 8536CT1901
Motor Starters and Protectors
www.se.com/us
Table 17.90: GV4, GV5, GV6 UL 489 Motor Protective Circuit Breakers
Interrupting Rating: 240 V ... 35 kA 480Y/277 V ... 18 kA 600Y/347 V ... 14 kA
Interrupting Rating: 240 V ... 65 kA 480Y/277 V ... 35 kA 600Y/347 V ... 18 kA
Interrupting Rating: 240 V ... 100 kA 480Y/277 V ... 65 kA 600Y/347 V ... 25 kA
Motor FLA Dial Range
0.8 ... 2 1.4 ... 3.5 2.9 ... 7 5 ... 12.5 10 ... 25 20 ... 50 40 ... 80 65 ... 115 58 ... 130 114 ... 217 190 ... 348 312 ... 520
— — — —
GV4PB02N GV4PB03N GV4PB07N GV4PB12N GV4PB25N GV4PB50N GV4PB80N GV4PB115N GV5PB150N GV5PB250N GV6PB400N GV6PB600N
GV4PB02S GV4PB03S GV4PB07S GV4PB12S GV4PB25S GV4PB50S GV4PB80S GV4PB115S GV5PB150S GV5PB250S GV6PB400S GV6PB600S
GV4PB25B GV4PB50B GV4PB80B GV4PB115B
— — — —
GV4PB
GV5PB
GV2P + LC1D Pre-Assembled Kits
Simplify your life! These new pre-assembled kits come with a GV2P manual motor protector already connected to an LC1D contactor. Panel builders and end users can now save wiring time by purchasing the pre-assembled kits.
Table 17.91: Pre-Assembled Kits
Group Motor Rating UL File E89451
UL File E134347 SCCR Type F 480Y/277V
17 CONTACTORS AND STARTERS-IEC
Components (includes GV2AF3)
Kit Part No. [20]
With GV1G09 LineSide Adapter and GV2G Busbar
With GV2GH7 or GV1G09 Line Side Adapter
SCCR480V
GV2P02 + LC1D09G7 GV2P03 + LC1D09G7 GV2P04 + LC1D09G7 GV2P05 + LC1D09G7 GV2P06 + LC1D09G7 GV2P07 + LC1D09G7 GV2P08 + LC1D09G7 GV2P10 + LC1D09G7 GV2P14 + LC1D09G7 GV2P16 + LC1D25G7 GV2P20 + LC1D25G7 GV2P21 + LC1D25G7 GV2P22 + LC1D25G7
100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 50kA 50kA 50kA 50kA
100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 42kA 42kA 42kA 42kA
22kA 22kA 22kA 22kA 22kA 22kA 22kA 22kA 22kA 22kA 22kA 22kA 22kA
GV2P02KD09 GV2P03KD09 GV2P04KD09 GV2P05KD09 GV2P06KD09 GV2P07KD09 GV2P08KD09 GV2P10KD09 GV2P14KD09 GV2P16KD25 GV2P20KD25 GV2P21KD25 GV2P22KD25
GV2P10 with LC1D09
Coil Voltage Suffix 120Vac
G7 B7 BL
24Vac
24 Vdc Low Consumption
[20] Complete the catalog number with the coil voltage suffix (for example GV2P16KD25G7 ).
17-31
© 2024 Schneider Electric All Rights Reserved
Made with FlippingBook Ebook Creator