Square D Digest 179

Contactors, Type S

Type S Reversing Full Voltage Contactors and Starters

www.se.com/us

Class 8702 / Refer to Catalog 8502CT9701

General Information

Class 8702 Type S reversing magnetic contactors are used for starting, stopping, and reversing AC motors where overload protection is separately provided. Class 8702 reversing contactors consist of two Class 8502 contactors mechanically and electrically interlocked. Open type devices, Sizes 0–5, are available in either horizontal or vertical arrangements. Sizes 00 and 6 are available as horizontal only. Enclosed devices, Size 00–6, use horizontally arranged components. Type S reversing contactors are designed for operation at up to 600 Vac, 50/60 Hz. NOTE: In Table 16.159, replace the three bullets (●●●) in the catalog number with the coil voltage code. Refer to the standard coil voltage codes listed in Table 16.160. For information on field modification of NEMA 12 enclosures, see page 16-113 .

NEMA 00, 0, and 1 Reversing Contactor

Table 16.159: 600 Vac Maximum—50–60 Hz

NEMA 12/3R [3] Dusttight & Driptight Industrial Use Enclosure

NEMA 4X Watertight, Dusttight Brushed Stainless Steel Enclosure (Sizes 0–5) [1] [2]

NEMA1 General Purpose Enclosure

OpenType

Continuous Current Ratings

Motor Voltage

Max. Hp

NEMASize

Vertical Type

Horizontal Type

Type

Type

Type

200 230 460 575 200 230 460 575 200 230 460 575 200 230 460 575 200 230 460 575 200 230 460 575 200 230 460 575 200 230 460 575

1.5 1.5

16 NEMA AND DEFINITE PURPOSE CONTACTORS AND STARTERS

00

9

SAO4●●●

SAG4●●●

UseSize0

UseSize0

2 2 3 3 5 5

0

18

SBO12●●●

SBO4●●●

SBG4●●●

SBW14●●●

SBA4●●●

7.5 7.5 10 10 10 15 25 25 25 30 50 50 40 50 100 100 100 200 200 150 200 400 400 75

SCO7●●●

SCO8●●●

SCG8●●●

SCW14●●●

SCA4●●●

1

27

2

45

SDO1●●●

SDO2●●●

SDG2●●●

SDW11●●●

SDA1●●●

3

90

SEO1●●●

SEO2●●●

SEG2●●●

SEW11●●●

SEA1●●●

SFO1●●●

SFO3●●●

SFG3●●●

SFW11●●●

SFA1●●●

4

135

5

270

SGO1●●●

SGO3●●●

SGG3●●●

SGW11●●●

SGA1●●●

6

540

SHO1●●●

SHG1●●●

SHA1●●●

NOTE: For voltage codes used with control transformers, see page page 16-118. Form S (separate control) is used when a separate source of power is available for the control (coil) voltage. Form S is available at no charge. Dimensions: page 16-65 Factory Modifications (Forms) page 16-117

Table 16.160: Coil Voltage Codes Voltage

Code

60Hz 24 [4] 120 [5] 208 240 277 480 600 Specify

50Hz

— 110 — 220 —

V01 V02 V08 V03 V04 V06 V07 V99

Separate Enclosures (Class 9991): page 16-111 Replacement Parts (Class 9998): page 16-123 Type S Accessories (Class 9999): page 16-127 For How to Order Information, see page 16-28.

440 550 Specify

[1] NEMA 4X stainless steel enclosures (sizes 0–5) have a brushed finish. [2] NEMA 4X stainless steel enclosures are shipped with hubs installed in the top and bottom of the enclosure. [3] NEMA 12 enclosures can be field modified for outdoor non-corrosive and non-service entrance rated applications. See Enclosures—Reversing, page for more information. [4] 24 V coils are not available on Sizes 4-6. On Sizes 00-3, where 24 V coils are available, FormS (separate control) can be specified (i.e., order as 8702SAO4V01S). [5] This voltage code can include FormS for separate control (provided at no charge) (for example, order as 8702SAO4V02S).

16-61

© 2024 Schneider Electric All Rights Reserved

Made with FlippingBook Ebook Creator