Square D Digest 179
Multi9™ Miniature Circuit Breakers
Multi9 Circuit Breakers Busbar Offer Class 860 / Refer to Catalog LVCATM9OEM_EN
www.se.com/us
C60 SP (UL1077) Comb Busbars
The comb busbars are used only for C60 SP circuit breakers UL 1077 supplementary protection in conformity with standards: • UL 1077 / CSA C22.2 No. 235 / IEC 60947-2 / GB 14048-2. They perform distribution and subdistribution of the electric power supply and allow rapid assembly and disassembly of equipment.
IEC
Table 7.41: C60 SP Comb Busbars Connection Accessories
Comb Busbars
Tooth Cover End-Piece
Function
• The comb busbars make it easier to install Schneider Electric circuit breakers UL1077 supplementary protection. • Power supply directly in the cage of the circuit breaker.
• The Tooth Caps are insulated protectors which may be slipped onto the unused teeth of the comb busbar. • They come in strips with 1-pole spacing, but can be snapped apart to be used individually.
Number of poles Voltage rating (Ue) Catalogue numbers
2P
3P
1P
All —
480Y/277 Vac
480Y/277 Vac
480Y/277 Vac
10285
10287
10286
60488
12 (8.5 in./216 mm)
12 (8.5 in./216 mm)
12 (8.5 i./216 mm)
Number of 18 mm modules
— 20
Set of
1
1
1
Technical Specifications Insulation voltage (Ui) Impulse withstand voltage (Uimp) Acceptable current at 40°C (Ie)
690Vac
— — — —
12 kV under 240 V 5 kV under 480Y/277 V or 277 V 63 A with 1 central power supply point
100 A with 2 power supply points
—
Power supply via cable directly in the cage of the device: • cross section max: 3 AWG (25 mm 2 ) • cross section min: 10 AWG (5.27 mm 2 )
7 MINIATURE AND MOLDED CASE
CIRCUIT BREAKERS
7-28
© 2024 Schneider Electric All Rights Reserved