Square D Digest 179
Multi9 Circuit Breakers Busbar Offer Class 860 / Refer to Catalog LVCATM9OEM_EN
Multi9™ Miniature Circuit Breakers
www.se.com/us
C60 BP (UL489) Comb Busbars
These comb busbars are aimed to be used only with C60 BP circuit-breakers. They perform distribution and subdistribution of the electric power supply and allow rapid assembly and disassembly of equipment.
IEC
Table 7.40: C60 BP Comb Busbars Connection Accessories
Insulated Connectors
Comb Busbars
Tooth Covers
End-Piece
Function
• The comb busbars make it easier to install C60 BP UL489 circuit breakers. • They must not be cut.
• Comb busbar power supply • Vertical incoming feeder Tightening torque: 3.5 N•m (31 lb.in.)
• Insulation of teeth remaining free
•
Ensures the correct comb busbar insulation
Use
Power supply by insulated connector • Use with rigid and flexible copper cable • 6 to35mm 2 (AWG #10 to #2):
Standard Comb Busbars
Number of poles Catalogue numbers
1P
2P
3P
All
All
— — — —
M9XUP106
M9XUP312
M9XUP312 M9XUP312 M9XUP312 M9R81425 M9XUPC04
M9XCTC18
Number of 18 mm modules 6
12
6 1
12
6 1
12
—
—
Set of
1
4
5x3
Cuttable Comb Busbars
Number of poles x Catalogue numbers
1P
2P
3P
1P+Aux
3P+Aux
All
All
—
M9XCP157 M9XCP256 M9XCP357 M9XCA137
M9XCA348
M9XCPC04
M9XUTC18
M9XCEC10
Number of 18 mm modules 57
56
57
37
37
—
—
— —
Set of
1
1
1
1
1
4
5x3
Technical Specifications Acceptable current at 40°C (Ie) Resistance to short-circuit currents Voltage rating (Ue) Insulation voltage (Ui)
Standard comb busbars: 115 A Cuttable comb busbars: 80 A
Compatible with the breaking capacity of Schneider Electric modular circuit breakers
480Y/277V 1000VAC
Pollution degree Fire resistance
3
Self-extinguishability 960°C 30 s/30 s
Colour
RAL7035
Standards
UL508
CIRCUIT BREAKERS
7 MINIATURE AND MOLDED CASE
7-27
© 2024 Schneider Electric All Rights Reserved
Made with FlippingBook Ebook Creator