SE Modicon M580 Brochure
Modicon M580 automation platform Modicon M580 Safety standalone processors
Selection guide
Modicon M580 automation platform
BMEP582040S + BMEP58CPROS3 mandatory coprocessor (1)
BMEP584040S + BMEP58CPROS3 mandatory coprocessor (1)
BMEP586040S + BMEP58CPROS3 mandatory coprocessor (1)
1
1
+
+
+
2
2
Racks
8
Local racks (main + extension)
4 8
16
31
Remote I/O drops (2) Discrete I/O channels
Local X80 I/O (3) (4)
2048
4096 1456 1024
6144 1456 1536
668 512 128
Safe discrete I/O channels
Analog I/O channels
3
3
272 144
272 216
Safe analog I/O channels
Application-specific channels (5)
72
Combined Local and Remote X80 I/O (4)
20480
37888 12864
Discrete I/O channels
10240
7344 5120 1360
Safe discrete I/O channels
3632 2560
9472 2380 1080
Analog I/O channels
Safe analog I/O channels
672 360
4
4
720
Application-specific channels (5)
Distributed equipment (DIO, CSIO)
EtherNet/IP or Modbus TCP devices (scanned by CPU)
61
445
445
EtherNet/IP or Modbus TCP devices (scanned by CPU and Ethernet modules)
BMENOC301/ BMENOC311
317
64
128
CIP safety devices (scanned by CPU)
16
Integrated communication ports
Ethernet service port (RJ45)
Engineering and Maintenance console (EcoStruxure Control Expert, Web browser, external tools), HMI, SCADA, Distributed equipment (DIO, CSIO)
Ethernet device network dual ports (RJ45) - RSTP
RIO network (RIO/DIO/CSIO scanner)
5
5
USB type mini B port
Programming port for Engineering Console (EcoStruxure Control Expert)
Communication
Ethernet networks
Cumulative max number of Ethernet networks modules
BMENOC/BMENOP/ BMENOR
2
4
EtherNet/IP and Modbus TCP
EtherNet/IP and Modbus TCP module BMENOC0301
2 2 2 2 2 2
3 3
FactoryCast IP Forwarding
FactoryCast module Ethernet control router
BMENOC0311 BMENOC0321 BMENOP0300 BMENUA0100
IEC 61850
IEC 61850 module OPC UA module
4
6
6
OPC UA
DNP3 NET / IEC 60870-5-104 DNP3 Serial / IEC 60870-5-101
Advanced RTU module
BMENOR2200H (6) BMXNOR0200H
4
RTU module
– (7)
4
Global Data AS-Interface
Global Data module AS-Interface module Serial link module CANopen module PROFIBUS DP module Program process (MB)
BMXNGD0100 BMXEIA0100 BMXNOM0200 BMECXM0100 PMEPXM0100
2
4 (8)
8 (8)
Each BMXNOM0200 channel counts as an application-specific channel (9)
Serial Link (Modbus and Character)
7
7
Each BMECXM0100 counts as a Distributed equipment (DIO)
CANopen
PROFIBUS DP
2 8 2
6
10 64 16
Internal memory capacity
16
Program safe (MB) Data process (KB)
4
768 512
2048 1024
up to 64MB (10)
Data safe (KB)
1024
Data storage (GB)
4
8
8
No. of K instructions executed per ms
100% Boolean (Kinstr/ms)
10
40 30
60 40
65% Boolean + 35% fixed arithmetic (Kinstr/ms)
7.5 No
Product compatibility with Quantum
Support of Quantum Ethernet I/O (QEIO) and LL984 Editor
Yes
References
BMEP582040S
BMEP586040S
Pages
3/11
(1) The mandatory coprocessor must be ordered separately. (2) A Remote I/O drop can be either a X80 RIO Drop (RIO) or Quantum Ethernet I/O drop (QEIO). One X80 RIO Drop can support up to 2 racks (via X-bus extension). (3) Local X80 I/O are localized in local racks (main or extension). Redundant controllers do not not support Local X80 I/O. (4) Maximum number of I/O channels (Discrete, Safe Discrete, Analog and Safe Analog) as well as application-specific channels is not cumulative. (5) Application-specific channels include counters, time-stamping, SSI encoder, Motion control, Serial and Frequency input modules. (6) Maximum number of BMENOR modules is not cumulative with other Ethernet network modules. (7) Not supported with safety controllers. (8) Additional BMXEIA0100 modules can be installed in remote drops : 2 per drop and with a maximum of 16 BMXEIA0100 modules. (9) Only supported in non-safety related Remote I/O drops. (10) BMEP586040S CPU features a global memory pool of 64 Mbytes for Program process (non-safe), Data process (non-safe non-retain data only), Program safe, and Data safe.
9
9
10
10
More technical Information on www.se.com
More technical Information on www.se.com
3/2
3/2 3/3
Made with FlippingBook flipbook maker