Contactors, Type S
Type S Full Voltage Contactors and Starters
Class 8502 / Refer to Catalog 8502CT9701
www.se.com/us
General Information
Class 8502 Type S magnetic contactors are used to switch heating loads, capacitors, transformers, and electric motors where overload protection is provided separately. Class 8502 contactors are available in NEMA Sizes 00–7. Type S contactors are designed for operation up to 600 Vac, 50–60 Hz. NOTE: In Table 16.82, replace ●●● with the voltage code shown in Table 16.83. Table 16.82: 3-Pole Polyphase—600 Vac Maximum—50–60 Hz
NEMA4&4X Watertight, Dusttight Brushed Stainless Steel Enclosure (Size0-5) [1]
NEMA1 General Purpose Enclosure
Continuous Current Ratings
OpenType
Motor Voltage
Max. Hp
NEMA Size
Type
Type
Type
200 230 460 575 200 230 460 575 200 230 460 575 200 230 460 575 200 230 460 575 200 230 460 575 200 230 460 575 200 230 460 575 200 230 460 575
1.5 1.5
00
9
SAO12●●● SAG12●●●
UseSize0
TypeSCO2 Size 1, 3-Pole Contactor
2 2 3 3 5 5
0
18
SBO2●●● SBG2●●●
SBW12●●●
7.5 7.5 10 10
SCO2●●● SCG2●●●
SCW12●●●
1
27
10 15 25 25 25 30 50 50 40 50
16 NEMA AND DEFINITE PURPOSE CONTACTORS AND STARTERS
SDO2●●● SDG2●●●
SDW12●●●
2
45
3
90
SEO2●●● SEG2●●●
SEW12●●●
4
135
SFO2●●● SFG2●●●
SFW12●●●
100 100 75 100 200 200 150 200 400 400 — 300 600 600
5
270
SGO2●●● SGG2●●●
SGW12●●●
6
540
SHO2●●● SHG2●●●
SHW2●●●
SJO2●●● SJG2●●●
SJW2●●●
7
810
Table 16.83: Coil Voltage Codes Voltage
Code
60Hz 24 [2] 120 [3] 208 240 277 480 600 Specify
50Hz
— 110 — 220 —
V01 V02 V08 V03 V04 V06 V07 V99
440 550 Specify
NOTE: For voltage codes used with control transformers, see . Form S (separate control) is used when a separate source of power is available for the control (coil) voltage. Available at no charge. Dimensions: page 16-39 Factory Modifications (Forms) page 16-117
Separate Enclosures (Class 9991): page 16-110 Replacement Parts (Class 9998): page 16-122 Type S Accessories (Class 9999): page 16-125 For How to Order Information, see page 16-28.
Size 6 and 7 are NEMA 4 only, painted sheet steel enclosures.
[1]
[2] 24 V coils are not available on Sizes 4–7. On Sizes 00–3, where 24 V coils are available, FormS (separate control) must be specified (for example, order as 8502SBO2V01S). [3] 120 V polyphase contactors are wired for separate control. FormS must be specified (i.e., order as 8502SCO2V02S).
16-29