SE Digest 178
Medium Voltage Metal-Enclosed Switchgear
HVL/cc™
Class 6045 / Refer to Catalog 6045CT9801
www.se.com/us
Factory Modifications Table 11.24: Factory Modifications Catalog No.
Description
Auxiliary switch 2 N.O.–2 N.C. contact
HVLCC-X3
Distribution Class Surge Arresters (One Set of Three) Switch Load Side Connected or Incoming Line Bay) Table 11.25: Surge Arresters Catalog No. kVRating
Section Width Minimum Required in
mm 375 375 375 375 375 508 508
3 kV, 2.55 kV MCOV 6 kV, 5.10 kV MCOV 9 kV, 7.65 kV MCOV 10 kV, 8.40 kV MCOV 12 kV, 10.20 kV MCOV 15 kV, 12.70 kV MVOV 18 kV, 15.3 kV MCOV
HVLCCDSA3 HVLCCDSA6 HVLCCDSA9 HVLCCDSA10 HVLCCDSA12 HVLCCDSA15 HVLCCDSA18
14.75 14.75 14.75 14.75 14.75 20.00 20.00
600 A “Single” HVL/cc Switch with PROVISIONS ONLY for Square D™ brand Current-Limiting, Non-Disconnect Type Fuses for Cable Connection to Power Dry™, Power-Cast™, and Uni-Cast™ Transformers (FLC = 300 A MAXIMUM) RH—Transformer on right, LH—Transformer on Left
600 A, tin-plated, copper bus
Application A = Top Entry (Incoming Cables) Application B = Bottom Entry (Incoming Cables) Table 11.26: 600 A “Single” HVL/cc Switch Selection Catalog No. kV Rating Fuse Range Ap plica tion
M
90.00 2286
200E
M
Width
RH/ LH
in
mm 375 508 375 508 375 508 375 508 375 508 375 508 375 508 375 508
HVLCCA14405DGR HVLCCA20405DGR HVLCCA14405DGL HVLCCA20405DGL HVLCCA14415DGR HVLCCA20415DGR HVLCCA14415DGL HVLCCA20415DGL HVLCCB14405DGR HVLCCB20405DGR HVLCCB14405DGL HVLCCB20405DGL HVLCCB14415DGR HVLCCB20415DGR HVLCCB14415DGL HVLCCB20415DGL
4.76 4.76 4.76 4.76
10–450E 10–450E 10–450E 10–450E 10–200E 10–200E 10–200E 10–200E 10–450E 10–450E 10–450E 10–450E 10–200E 10–200E 10–200E 10–200E
A 14.75 A 20.00 A 14.75 A 20.00 A 14.75 A 20.00 A 14.75 A 20.00 B 14.75 B 20.00 B 14.75 B 20.00 B 14.75 B 20.00 B 14.75 B 20.00
RH RH LH LH RH RH LH LH RH RH LH LH RH RH LH
37.25 946
14.75 375
14.75 375
15 15 15 15
Listed Metal-Enclosed Interrupter Switchgear
4.76 4.76 4.76 4.76
15 15 15 15
LH NOTE: Switches with transformer connections are painted ANSI 49. Standalone switches are painted ANSI 61. Transformer connections in HVL/cc switches are based on standard Square D™ brand transformer connections. If these switches are used to connect to other manufacturers' transformers, then connections must match standard Square D™ brand transformer connections. (Cable connections are furnished with the transformer.)
11 SWITCHBOARDS AND SWITCHGEAR
11-19
© 2019 Schneider Electric All Rights Reserved
11/20/2019