SE Digest 178
I-Line™ Panelboards—600 Vac, 250 Vdc
I-Line Merchandised Panelboard Accessories Refer to Catalog 2110CT9701
www.se.com/us
Table 9.120: Box Extensions
Catalog Number
Interior Type
Extension
HC2609DEX (F or S) HC3209EX (F or S) HC4212DEX (F or S) HC4406DEX (F or S)
HCP-SU
9 in. 9 in.
HCM HCP
12 in.
HCR-U
6 in.
HC4412DEX (F or S)
HCR-U
12 in.
9 PANELBOARDS
Sub-feed Lug Kits
Table 9.121: Sub-feed Lug Kits [39][40][41] Ampere Rating Height Catalog Number
Max. Short Circuit System Ratings RMS Symmetrical Amperes
For Use in I-Line Panelboard Types
Protected by Circuit Breaker
(mm)
In.
240Vac
480Vac
600Vac
FA, FD, FG, FH, FJ, HD, HG, HJ, HL, HR, JD, JG, JJ, JL, JR, KI HD, HG, HJ, HL, HR, JD, JG, JJ, JL, JR, LA, LH,, DG, DJ, DL, LD, LG, LJ, LL, LR (“L” & “D” FRAME 400AMAX.) HD, HG, HJ, HL, HR, JD, JG, JJ, JL, JR, LA, LH, LC, LI, MA, MH, MX, DG, DJ, DL, LD, LG, LJ, LL, LR FA, FD, FG, FH, FJ, KA, KH, KC, KI, HD, HG, HJ, HL, HR, JD, JG, JJ, JL, JR, MA, MH, MX, MG, PG, MJ, PJ, PK, PL, DG, DJ, DL, LD, LG, LJ, LL, LR FA, FD, FG, FH, FJ, KA, KH, KC, KI, HD, HG, HJ, HL, HR, JD, JG, JJ, JL, JR, LA, LH, LC, LI, MA, MH, MX, MG, PG, MJ, PJ, PK, PL, DG, DJ, DL, LD, LG, LJ, LL, LR FA, FD, FG, FH, FJ, KA, KH, KC, KI, HD, HG, HJ, HL, HR, JD, JG, JJ, JL, JR, LA, LH, LC, LI, MA, MH, MX, NA, NC, NX, MG, PG, MJ, PJ, PK, PL, RG, RJ, RL, RK, DG, DJ, DL, LD, LG, LJ, LL, LR FA, FD, FG, FH, FJ, KA, KH, KC, KI, HD, HG, HJ, HL, HR, JD, JG, JJ, JL, JR, MG, PG, MJ, PJ, PK, PL, RG, RJ, RL, RK, DG, DJ, DL, LD, LG, LJ, LL, LR
200,000
200,000
100,000
HCM, HCP, HCP-SU, HCR-U
250A
4.5
114
SL250
HCP, HCP-SU, HCR-U (wide side only)
152 SL400 [41]
200,000
200,000
100,000
400A
6
200,000
100,000
50,000
HCM, HCP, HCP-SU, HCR-U
800A
9
229
SL800
125,000
100,000
25,000
HCM, HCP, HCP-SU, HCR-U
800A
9
229
SL800M5
HCP, HCP-SU, HCR-U
125,000
100,000
50,000
1200A
9
229
S33931
125,000
100,000
50,000
HCR-U
1200A
15
381
S33930
SL1200P5, SL1200P6, SL1200P7
125,000
100,000
50,000
HCP, HCP-SU, HCR-U
1200A
9
229
NOTE: S33930, S33931, SL1200P5, SL1200P6, SL1200P7, SL Kits are rated 1200 A and may be applied to 1200 ampere loads when installed into HCRU panelboards. However, when installed into HCP and HCPSU panelboards they are only rated 800 amperes maximum due to restricted wire bending space. For Surgelogic™ I-Line plug-on SPD information, starting on Digest page 6-2.For field-installable I-Line door kits, see the Supplemental and Obsolescence Digest, Section 4. Table 9.122: Sub-feed Lug kit terminal data Catalog No. (Prefix) No. Poles Ampere Rating Standard Lug Wire Size [42] SL100 3 100 #14–1/0 AWG Cu or #12–1/0 AWG Al SL250 3 250 1– #4 AWG–300 kcmil SL400 3 400 1– #1 AWG–600 kcmil or 2– #1 AWG–250 kcmil SL800 3 800 3– #3/0 AWG–500 kcmil SL800M5 3 800 3– #3/0 AWG–500 kcmil S33931 3 1200 4– #3/0 AWG–500 kcmil S33930 3 1200 4– #3/0 AWG–600 kcmil SL1200P5 3 1200 4– #3/0 AWG–500 kcmil SL1200P6 3 1200 3– 350–600 kcmil SL1200P7 3 1200 3– #3/0 AWG–750 kcmil
[39] Plug-on in same manner as a branch circuit breaker [40] For other ratings, see the latest edition of I-Line Information Manual, #80043-309-xx. [41] SL400 cannot be used in HCM panelboards due to inadequate wire bending space. [42] Unless otherwise specified, wire sizes apply to both aluminum and copper conductors.
9-52
© 2021 Schneider Electric All Rights Reserved 6/20/2021
Made with FlippingBook flipbook maker