SE Digest 178

I-Line™ Panelboards—600 Vac, 250 Vdc

I-Line Merchandised Panelboard Accessories Refer to Catalog 2110CT9701

www.se.com/us

Table 9.120: Box Extensions

Catalog Number

Interior Type

Extension

HC2609DEX (F or S) HC3209EX (F or S) HC4212DEX (F or S) HC4406DEX (F or S)

HCP-SU

9 in. 9 in.

HCM HCP

12 in.

HCR-U

6 in.

HC4412DEX (F or S)

HCR-U

12 in.

9 PANELBOARDS

Sub-feed Lug Kits

Table 9.121: Sub-feed Lug Kits [39][40][41] Ampere Rating Height Catalog Number

Max. Short Circuit System Ratings RMS Symmetrical Amperes

For Use in I-Line Panelboard Types

Protected by Circuit Breaker

(mm)

In.

240Vac

480Vac

600Vac

FA, FD, FG, FH, FJ, HD, HG, HJ, HL, HR, JD, JG, JJ, JL, JR, KI HD, HG, HJ, HL, HR, JD, JG, JJ, JL, JR, LA, LH,, DG, DJ, DL, LD, LG, LJ, LL, LR (“L” & “D” FRAME 400AMAX.) HD, HG, HJ, HL, HR, JD, JG, JJ, JL, JR, LA, LH, LC, LI, MA, MH, MX, DG, DJ, DL, LD, LG, LJ, LL, LR FA, FD, FG, FH, FJ, KA, KH, KC, KI, HD, HG, HJ, HL, HR, JD, JG, JJ, JL, JR, MA, MH, MX, MG, PG, MJ, PJ, PK, PL, DG, DJ, DL, LD, LG, LJ, LL, LR FA, FD, FG, FH, FJ, KA, KH, KC, KI, HD, HG, HJ, HL, HR, JD, JG, JJ, JL, JR, LA, LH, LC, LI, MA, MH, MX, MG, PG, MJ, PJ, PK, PL, DG, DJ, DL, LD, LG, LJ, LL, LR FA, FD, FG, FH, FJ, KA, KH, KC, KI, HD, HG, HJ, HL, HR, JD, JG, JJ, JL, JR, LA, LH, LC, LI, MA, MH, MX, NA, NC, NX, MG, PG, MJ, PJ, PK, PL, RG, RJ, RL, RK, DG, DJ, DL, LD, LG, LJ, LL, LR FA, FD, FG, FH, FJ, KA, KH, KC, KI, HD, HG, HJ, HL, HR, JD, JG, JJ, JL, JR, MG, PG, MJ, PJ, PK, PL, RG, RJ, RL, RK, DG, DJ, DL, LD, LG, LJ, LL, LR

200,000

200,000

100,000

HCM, HCP, HCP-SU, HCR-U

250A

4.5

114

SL250

HCP, HCP-SU, HCR-U (wide side only)

152 SL400 [41]

200,000

200,000

100,000

400A

6

200,000

100,000

50,000

HCM, HCP, HCP-SU, HCR-U

800A

9

229

SL800

125,000

100,000

25,000

HCM, HCP, HCP-SU, HCR-U

800A

9

229

SL800M5

HCP, HCP-SU, HCR-U

125,000

100,000

50,000

1200A

9

229

S33931

125,000

100,000

50,000

HCR-U

1200A

15

381

S33930

SL1200P5, SL1200P6, SL1200P7

125,000

100,000

50,000

HCP, HCP-SU, HCR-U

1200A

9

229

NOTE: S33930, S33931, SL1200P5, SL1200P6, SL1200P7, SL Kits are rated 1200 A and may be applied to 1200 ampere loads when installed into HCRU panelboards. However, when installed into HCP and HCPSU panelboards they are only rated 800 amperes maximum due to restricted wire bending space. For Surgelogic™ I-Line plug-on SPD information, starting on Digest page 6-2.For field-installable I-Line door kits, see the Supplemental and Obsolescence Digest, Section 4. Table 9.122: Sub-feed Lug kit terminal data Catalog No. (Prefix) No. Poles Ampere Rating Standard Lug Wire Size [42] SL100 3 100 #14–1/0 AWG Cu or #12–1/0 AWG Al SL250 3 250 1– #4 AWG–300 kcmil SL400 3 400 1– #1 AWG–600 kcmil or 2– #1 AWG–250 kcmil SL800 3 800 3– #3/0 AWG–500 kcmil SL800M5 3 800 3– #3/0 AWG–500 kcmil S33931 3 1200 4– #3/0 AWG–500 kcmil S33930 3 1200 4– #3/0 AWG–600 kcmil SL1200P5 3 1200 4– #3/0 AWG–500 kcmil SL1200P6 3 1200 3– 350–600 kcmil SL1200P7 3 1200 3– #3/0 AWG–750 kcmil

[39] Plug-on in same manner as a branch circuit breaker [40] For other ratings, see the latest edition of I-Line Information Manual, #80043-309-xx. [41] SL400 cannot be used in HCM panelboards due to inadequate wire bending space. [42] Unless otherwise specified, wire sizes apply to both aluminum and copper conductors.

9-52

© 2021 Schneider Electric All Rights Reserved 6/20/2021

Made with FlippingBook flipbook maker