NF Panelboards—600Y/347 Vac Max.
NF Factory Assembled Main Circuit Breakers
Refer to NF Panelboards
www.se.com/us
Factory Assembled Main Circuit Breakers (600Y/347 Vac maximum) Table 9.55: NF Panelboard Factory Assembled Interiors—600Y/347 Vac Max Single Phase 3-Wire (1P/3W), or Three Phase 4-Wire (3P/4W) [40] Mains Rating (Amps) Max. Number of One-Pole Circuit Breakers Bus Material Min. Box Depth (inches) MainLugs Only Circuit Breaker Frame Main Breaker [41] Main Switch [41] Main Lugs Only
Main Breaker / Switch
9 PANELBOARDS
ED, EG, EJ [42]
18, 30
Al, Cu 5.75 in.
125Max
15–125
–
5.75 in.
18, 30, 42 [43] , 54 [43] 30, 42, 54, 66 [44] 30, 42, 54, 66 [44] , 84
Al, Cu 5.75 in.
125 Max HD/HG/HJ/HL/ HR 250 Max JD/JG/JJ/JL/ JR
15–125
110–125
5.75 in.
Al, Cu 5.75 in.
150–250 150–250
5.75 in.
8.75 in. or 5.75 in. [45]
Al, Cu 5.75 in.
400 Max LG/LJ/LL/LR & LA/LH
125–400 300–400
8.75 in. [45] 8.75 in. [47]
600 Max LG/LJ/LL/LR 400–600 450–600 30, 42, 54, 66, 84
Cu
5.75 in. 8.75 in. [46]
MG
600–800
—
30, 42, 54
800Max
Cu
PG, PJ, PL 600–800 600–800 NOTE: Factory Assembled Main Circuit Breakers (600Y/347 Vac maximum). 600Y/ 347 Vac applications require use of ExBx6xxx branch circuit breakers, i.e. EDB16015 for a 1P, 15A circuit. [48] 400 A and 600 A panelboards, 1Ø or 3Ø PowerPacT L-frame - see Tables in Section 7. Table 9.56: Main Circuit Breaker No. of Poles Trip Unit Options Frame Sizes Ampacity 3 LI, LSI, Switch LG, LJ, LL, LR 125–600A LA/LH, PowerPacT H and J-frame circuit breakers are also available—see Tables in Section 7 and Supplemental Digest Section 3. Table 9.57: PowerPacT L Main Circuit Breaker Cabinet Height (inches)
NEMA 1 Enclosure (20 in. W x 8.75 in. D) [49]
Vented NEMA 3R Enclosure (26 in. W x 8.75 in. D) [50]
Max. No. of Branch Spaces (Does not include sub-feed circuit breaker spaces)
400 / 600 A Interior
400A
600A
30 42 54 66
68 74 80 92
68 74 80
74 80 86
– – Table 9.58: NF Sub-Feed Circuit Breakers (available on 1Ø or 3Ø, 250 A–800 A main lugs or 250 A–600 A main circuit breaker interiors)
Sub Feed Breaker
No.Of Sub Feed Breakers Available to Install
Interior Mains Rating
Space Factor [51] (in.)
No. of Poles
MainsType
Ampaci ty
Sub-Feed Circuit Breaker Frame
110 - 150 HD, HG, HJ, HL, HR
250 A Main Lugs or Main Breaker
18
1
150 - 250
JD, JG, JJ, JL, JR
Main Lugs or LA / LH Main Breaker
18
110 - 150 HD, HG, HJ, HL, HR
PowerPacT L Main Breaker
12
1or 2
Main Lugs or LA / LH Main Breaker
18
2or 3
150 - 250
JD, JG, JJ, JL, JR
PowerPacT L Main Breaker
12
400A / 600A / 800A
Main Lugs or LA / LH Main Breaker
18
300 - 400
LA, LH
1
PowerPacT L Main Breaker
12
LA or LH with PowerPacT H or J LG, LJ, LL, LR [52]
1LAor LH and1Hor J
Main Breaker or Main Lugs
36
125 - 600
Main Lugs or Main Breaker
18
3
1
[40] NF panelboards without neutral connections may be applied in 3-phase, 4-wire grounded Wye systems, except at the Service Entrance. [41] Factory Assembled Interiors are rated for trip current of Main Breaker / Switch. [42] Back-Fed Main Breaker applications only. [43] Three Phase Copper only. [44] Three Phase only. [45] 8.75" Deep Box required for PowerPacT L Main Breaker or Switch. [46] Enclosures limited to NEMA Type 1 only. [47] 8.75" Enclosures limited to 26" Wide NEMA Type 1. [48] Requires use of ExBx6xxx branch circuit breakers, i.e. EDB16015 for a 1P, 15A circuit. [49] D9 8.75" deep enclosure and three point latch door is required for PowerPacT L Main Circuit Breaker, Switch, or Sub-Feed Circuit Breaker. See Table 9.47 NF Main Circuit Breaker Interiors - Use I-Line Panelboard for 3 Ø 3W Delta applications above 240 Vac, page 9-29.
[50] PowerPacT L not available in non-vented (NEMA Type 3R/5/12, or 4/4X) enclosures. [51] Space Factor is added to Space Factors for Interior and Main Breaker (if present).
[52] D9 8.75" deep enclosure and three point latch door is required for PowerPacT L Main Circuit Breaker, Switch, or Sub-Feed Circuit Breaker. PowerPacT L Sub-Feed Circuit Breakers cannot be installed on 400A NF Panelboard interiors. Use NF interiors with a mains ratings of at least 600A for all NF Panelboards applications requiring a PowerPacT L circuit breaker. See Table 9.47
9-32