SE Digest 178

NF Merchandised Main Lug Three Phase Interiors

NF Panelboards—600Y/347 Vac Max.

Refer to Catalog 1670CT0701

www.se.com/us

NF Main Lug Interiors - 600Y/347 Vac Max Table 9.46: NF Main Lug Interiors - Use I-Line Panelboard for 3Ø3W Delta applications above 240 Vac

Interior Only Catalog Number (Order Branch Circuit Breakers Separately) [1][3]

Water, Dirt, and Dust Resistant Enclosure Catalog Numbers [4]

NEMA 1 Enclosure

Mains Rating (Amps)

Circuit Breaker Pole Spaces [1] [2]

Box 20 in.Wx 5.75 in.D [5]

Type 3R/5/12 20 in. W x 5.75 in. D [7]

Type3R 26 in. W x 8.75 in. D [8]

Mono-Flat Trim ™ Front [6]

Hinged Front [5]

Height (In.)

(Single Phase 3-Wire: Factory Assembled Only) Three Phase 4-Wire [9] 18 NF418L1 MH26

30 42 54 30 9 PANELBOARDS 42

NC26( )

NC26( )HR

MH26WP

26

NF418L1C NF430L1 NF430L1C NF442L1C NF454L1C NF430L2 NF430L2C NF442L2 NF442L2C NF454L2 NF454L2C NF466L2 NF466L2C NF430L4 NF430L4C NF442L4 NF442L4C NF454L4C NF454L4C NF466L4 NF466L4C NF484L4 NF484L4C NF430L6C NF442L6C NF454L6C NF466L6C NF484L6C

NC32( ) NC38( ) NC44( ) NC38( )

NC32( )HR NC38( )HR NC44( )HR NC38( )HR

MH32 MH38 MH44 MH38

MH32WP MH38WP MH44WP MH38WP

32 38 44 38

125

NC44( )

NC44( )HR

MH44

MH44WP

44

250

NC50( )

NC50( )HR

54

MH50

MH50WP

50

NC62( )

NC62( )HR

66

MH62

MH62WP

62

NC50( )

NC50( )HR

30

MH50

MH50WP

50

NC56( )

NC56( )HR

42

MH56

MH56WP

56

NC62( )

NC62( )HR

54

MH62

MH62WP

MH74D9VWP

62/74

400

NC74( )

NC74( )HR

66

MH74

MH74WP

MH86D9VWP

74/86

NC86( )

NC86( )HR NC50V( )HR NC56V( )HR NC62V( )HR NC74V( )HR NC86V( )HR

84 30 42 54 66 84

MH86 MH50 MH56 MH62 MH74 MH86

MH86WP

86

NC50V( ) NC56V( ) NC62V( ) NC74V( ) NC86V( )

MH62WP [10] MH68WP [10] MH74WP [10] MH86WP [10]

MH62D9VWP MH68D9VWP MH74D9VWP MH86D9VWP

50/62 56/68 62/74 74/86

600

86

800 Factory Assembled Only [11] Note: All NF Merchandised Panelboard interiors include the following: a NFFP15 bag of blank filler plates; a neutral bonding strap; an NF information manual; a NEMA instruction booklet; and a sheet of circuit numbers.

[1] Order EDB, EGB, or EJB branch circuit breakers separately. Maximum allowable branch circuit breaker pair combination is 170 A. [2] Please note that some local building codes limit panelboards to 42 circuits, including those that reference 2005 or earlier version of the US NEC. [3] “C” suffix indicates copper bussing. [4] Wall mounting brackets add 0.4 inches to back of MHxxWP enclosures. [5] Nominal interior dimensions, see PBA600 for details. [6] Add “F” for flush mount, “S” for surface mount. [7] Enclosure includes trim kit. NEMA 3R, 5, 12 enclosures must be bottom fed. Nominal enclosure dimensions, see PBA555 for details. [8] Vented Type 3R enclosure with three point latch door required for outdoor applications with two sub-feed breakers, or sub-feed breaker with trip current >150A. NEMA 3R enclosures must be bottom fed, when selected a NF12RDE kit should also be selected. Enclosure nominal dimensions, see PBA603WP for details. [9] NF panelboards without neutral connections may be applied to 3 phase, 4 wire grounded Wye systems, except at the Service Entrance. [10] NEMA 3R, 5, 12 enclosures must be bottom fed, when selected a NF12RDE kit should also be selected. [11] 800 A interiors with main circuit breaker require 8.75 inch deep, 26 inch wide enclosures.

9-28

© 2021 Schneider Electric All Rights Reserved 6/20/2021

Made with FlippingBook flipbook maker