SE Digest 178

NQ Panelboards—240 Vac, 48 Vdc

NQ Feed-through Lugs, Neutral Assemblies, & Factory Assembled Options

Online Refer to NQ Panelboards

www.se.com/us

Feed-through Lugs

Table 9.26: Feed-through Lugs Cabinet Data

Table 9.25: Feed-through Lugs Mains Rating

Box Height (20 in. W x 5.75 in. D)

Feed-Through Wire Range Per Phase (AWG or kcmil)

225A 250A

400A

600A

100A 225A 400A 600A

one #6-2/0 Al or Cu one #6–350 Al or Cu

Max. No. ofBranch Spaces

Main Circuit Break er [82]

Main Circuit Breaker

Main Circuit Breaker

Main Lugs

Main Lugs

Main Lugs

one 1/0–750 or two 1/0–350 Al or Cu

two 1/0–750 Al or Cu

9 PANELBOARDS

30 42 72 84

38 38 50 56

50 50 62 68

50 56 68 68

62 68 80 80

62 62 74 80

68 80 — —

Table 9.28: Copper Bus Bars Copper Bus Bars 100 A, 225 A, 250 A

Table 9.27: Name Plates Name Plates

Standard white face/black letter laminated bakelite, 1 in. x 3.5 in., adhesive backed or screw mountable with screws in a bag assembly

400A 600A

Table 9.29: NQ Panelboard Neutral Assembly Options

Without Sub-Feed or Thru-Feed Lugs

With Sub-Feed or Thru-Feed Lugs

Interior Rating

200% Neutrals [83]

200% Neutrals [83]

100% Neutrals

100% Neutrals

Copper

Copper

Copper

Copper

Aluminum

Aluminum

Aluminum

Aluminum

NQN1CU NQN2CU

NQNL1 NQNL2 NQNL4

NQN1CU NQN2CU

NQNL1

100A 225A 400A

Factory Assembled Only

Factory Assembled Only

NQNL2ACCY FAOnly [84]

Standard

Standard

Factory Assembled in 26" Wide Enclosure Only

Factory Assembled in 26" Wide Enclosure Only

NQN6CU

NQN6CU

600A [3]

Not Available

Not Available

Table 9.30: NQ Main 100% and 200% Rated Neutral Conductors—(Quantity) and Wire Size (Mechanical Lugs & Compression Lugs)

Mechanical Neutral Line Lugs

Compression Neutral Line Lugs

200%Rated [85][86]

100%Rated

200%Rated [85][86]

100%Rated

Standard Neutral Assemblies Neutral Lug Wire Range

Oversized Neutral Assemblies

Standard Neutral Assemblies Oversized Neutral Assemblies

Interior Rating Lug Material

Neutral Lug Wire Range select 225 A neutral assembly select 400 A neutral assembly

Neutral Lug Wire Range

Neutral Lug Wire Range select 225 A neutral assembly select 400 A neutral assembly

Neutral Lug Wire Range

Neutral Lug Wire Range

Space Factor

Space Factor

(1) #6-2/0 (1) #6-2/0

(2) #6-2/0 (2) #6-2/0

(1) #8-1/0 (1) #6-1/0

(2) #8-1/0 (2) #6-1/0 (2) #4-300

Al

100A

N/A

N/A

Cu

(1) #6-300 kcmil (1) #6-250 kcmil (2) 1/0-300 kcmil or (1) 1/0-750 [87] kcmil (4) 1/0-300 kcmil or (2) 1/0-750 [87] kcmil

(2) #6-300 kcmil (2) #6-250 kcmil (4) 1/0-300 kcmil or (2) 1/0-750 [87] kcmil

(1) #4-300 kcmil (1) #6 2/0-300 kcmil (2) 2/0-500 kcmil

Al

225A

N/A

N/A

(2) #6 2/0-300 kcmil (4) 2/0-500 kcmil

Cu

Al

(4) 1/0-750 kcmil or (8) 1/0-300 kcmil

(2) 1/0-750 kcmil or (4) 1/0-300 kcmil

6

6

400A

(2) 400-750 kcmil

(4) 400-750 kcmil

Cu

Al

(4) 1/0-750 kcmil or (8) 1/0-300 kcmil (2) 1/0-750 kcmil or (4) 1/0-300 kcmil

600A

6

N/A

N/A

N/A (2) 2/0-500 kcmil

N/A

Cu

600A(with NQALMN6or NQCUMN6)

Al

N/A

12

N/A

N/A

N/A

N/A

N/A

Cu NOTE: Implicit AWG (American Wire Gauge) abbreviation on conductors wire range (kcmil is shown). Neutral conductors must be of size and quantity per table above.

Table 9.31: Metal Directory Frames Metal Directory Frame Replaces standard plastic stick-on directory pouch, add "WMD" suffix to NC Trim catalog number. Table 9.32: NQ Equipment Ground Bar Kits [88] Interior Rating Aluminum Copper

Table 9.33: Hinged Door-in-Door Trims Hinged Door-in-Door Trim Hinged Door-in-Door Trim has piano hinge down one side. Inner door has a lock, outer door is retained with screws Hinged Door-in-Door with Outer Door Lock in place of screws

GroundBar Insulator Kit

PK12GTA, PK18GTA, PK23GTA, or PK27GTA

100A / 225A

PK27GTACU

PKGTAB

PK12GTA, PK27GTA PK27GTACU

400A / 600A

PKGTAB

[82] 8.75 in. deep box, ship fully assembled only. [83] 600 A main circuit breaker panelboards require an 8.75 in. deep, 26 in. wide box. [84] FA - Factory Assembled Panelboards [85] 200% Neutrals not available on Column Width interiors. [86] Panelboards with 200% rated neutrals are not available with 250 A J-frame main circuit breakers or integral lighting contactors. [87] Installation of 750 kcmil neutral conductors possible if enclosure length is extended. [88] One PK kit supplied when ground bar is specified. Two PK kits supplied when "extra" ground bar is ordered.

9-20

© 2021 Schneider Electric All Rights Reserved 6/20/2021

Made with FlippingBook flipbook maker