Panelboards

Panelboard Series Ratings

Refer to NQ Panelboards

www.se.com/us

Table 9.1 NQ Series Connected Circuit Breaker Ratings (RMS Symmetrical) (cont'd.) Maximum System VoltageAC [9] Maximum Short Circuit Current Rating [10] Square D™ Brand Integral or Remote Main Circuit Breakers and Remote Main Fuses [11][12][13]

Square D™ Brand Branch Circuit Breaker Catalog Designation and Allowable Ampere Ranges Type [14][15][16] 1Pole 2Pole 3Pole

QO(B) VH QO(B) VH QO(B) VH

50,000

600 A Max. Class T3 Fuses 400 A Max. Class J Fuses

— — — — — — — — — — — — —

— — — — — — — — — — — — —

15–30A 15–100A 15–100A 110–150A 15–100A 15–50A 15–50A 15–100A 15–50A 15–50A 15–100A 15–50A 15–50A

65,000

400 A Max. Class T6 Fuses

QOB-VH QO(B)

QO(B) EPD QO(B) EPE

100,000

200 A Max. Class T3 Fuses

240/120 3P/4W 2403P/3W

QO(B)

QO(B) EPD QO(B) EPE

200 A Max. Class T6 or J Fuses

200,000

QO(B)

QO(B) EPD QO(B) EPE

400 A Max. Class T3 Fuses

NF Panelboards This page contains UL Tested and Certified series combination ratings for panelboards. These ratings apply to either an integral main located in the same enclosure or a remote main located in a separate enclosure.

9 PANELBOARDS

Table 9.2: NF Series Connected Circuit Breaker Ratings (RMS Symmetrical) Maximum System Voltage, AC [17] Max. Short Circuit Current Rating Square D™ Brand Integral or Remote Main Circuit Breakers and Remote MainFuses [18]

Square D™ Brand Branch Circuit Breaker Catalog Designation and Allowable Ampere Ranges

Circuit Breaker Abbreviation [19]

1Pole 15–70 15–30 15–70 15–30 15–70 15–30 15–70 15–30 15–30 15–70 15–50 15–30 15–70 15–50 15–30 15–70 15–50 15–70 15–50 15–70 15–50 15–30 15–70 15–50 15–30 15–70 15–70 15–70 15–70 15–70 15–70

2Pole 15–125 15–30 15–125 15–30 15–125 15–30 15–125 15–30 15–30 15–125

3Pole 15–125 15–30 15–125 15–30 15–125 15–30 15–125 15–30 15–30 15–125

EG, BG, HG, JG, LG, LH

EDB

65,000

EG

ECB-G3 EDB, EGB

EJ, BJ, HJ, JJ, LJ

100,000

EJ, BJ, HJ, JJ

ECB-G3

120 120/240 240

HL, JL HL, JL

EDB, EGB, EJB

125,000

ECB-G3

HR, JR, LR

EDB, EGB, EJB

HR, JR

200,000

ECB-G3 ECB-G3

Class J or T (600 V) 200 A Max Fuses

EG, BG, HG, JG, LG, LH EG, BG, HG, JG, LG, LH

EDB

35,000

EDB-EPD ECB-G3 EDB, EPD

EG, BG, HG, JG EJ, BJ, HJ, JJ, LJ

15–30 15–125

15–20 15–125

EJ, BJ, HJ, JJ, LJ, LL

EDB-EPD, EGB-EPD

65,000

EJ, BJ, HJ, JJ

ECB-G3

15–30 15–125

15–20 15–125

HL, JL, LL HL, JL, LL

EDB, EGB, EJB

EDB-EPD, EGB-EPD, EJB-EPD

277 480Y/277

100,000

Class J or T (600 V) 400 A Max Fuses Class J or T (600 V) 400 A Max Fuses

EDB, EGB, EJB

15–125

15–125

EDB-EPD, EGB-EPD, EJB-EPD

HR, JR, LR HR, JR, LR

EDB, EGB, EJB

15–125

15–125

EDB-EPD, EGB-EPD, EJB-EPD

HR, JR

ECB-G3

15–30 15–125

15–20 15–125

200,000

Class J or T (600 V) 200 A Max Fuses Class J or T (600 V) 200 A Max Fuses Class J or T (600 V) 200 A Max Fuses

EDB, EGB, EJB

EDB-EPD, EGB-EPD, EJB-EPD

ECB-G3

15–30 15–100 15–100 15–100 15–100 15–100 15–100

15–20 15–100 15–100 15–100 15–100 15–100 15–100

18,000 25,000 50,000 65,000 200,000

HG, BG, JG, LG

EDB

EJ, BJ, HJ, JJ, LJ, LH

EDB, EGB

HL, JL, LL

EDB, EGB, EJB EDB, EGB, EJB

347 600Y/347

HR, JR

LR

EJB

Class J or T (600 V) 200 A Max Fuses

EDB, EGB, EJB

[9] Series Ratings listed at higher system voltages apply to lower system voltages (Example: 240 3P/3W covers 208Y/120 3P/4W). [10] Short Circuit tests are conducted at 100–105% of the maximum rated voltage of the panelboard. [11] Please consult the NQ/NQM Panelboards Information Manual (80043-712-06) for additional information, including series ratings with obsolete circuit breakers. [12] Where LG is shown, LJ and LL can be used. [13] Unless otherwise noted, main breakers can be applied at the maximum available amperage rating. [14] Suffixes HID, SWD, and SWN may also be applied to the applicable branch circuit breakers shown above. [15] Where QO(B) circuit breakers are shown above, QO(B)H, QO(B)VH, and QH(B) circuit breakers may also be used. [16] Two-pole CAFI circuit breakers cannot be used on 208Y/120V systems. [17] Short circuit tests are conducted at 100–105% of the maximum rated voltage of the panelboard. [18] Please consult the NF/NFOM Panelboards Information Manual (80043-741-03) for additional information, including series ratings with obsolete circuit breakers. [19] EDB-EPD, EGB-EPD & EJB-EPD suitable for 480Y/277Vac or 277Vac ONLY.

9-5