SE Digest 178
PowerPact™ Circuit Breaker Accessories Compression Lugs and Power Distribution Connectors (PDC)
www.se.com/us
Class 612 / Refer to Catalog 0612CT0101
Power Distribution Connectors
Power distribution connectors (PDCs) can be used for multiple load wire connections on one circuit breaker in place of standard distribution block to save space and time. The connectors are attached to circuit breaker terminals equipped with separately provided terminal nut connectors. [29] Applications: • For use on load end of circuit breaker only • For use in UL 508 Industrial Control applications • For use in UL 1995/CSA C22.2 No. 236 heating and cooling equipment • For copper wire only Table 7.109: Power Distribution Connectors for B-Frame, H-Frame, J-Frame and L Frame Circuit Breakers [30] Usewith Circuit Breaker Type Ampere Rating (Wires Per Terminal) WireRange Dimension A (in.) Cat.No. Qty. Per Kit Kit Contents BD, BG, BJ 125A (3) 14 - 2 AWG 1.2 PDC3BD2 3 Mounting hardware, lugs 125A (6) 14 - 6 AWG 1 PDC6BD6 3 HD, HG, HJ,HL [31] 15–150 A (6) 14–6 AWG Cu 1.0 PDC6HD6 3 Mounting 15–150 A (3) 14–2 AWG Cu 1.2 PDC3HD2 3
PDC6HD6
PDC6JD4
PDC3HD2 PDC3JD20 Crimp lugs or PDC connectors extension “A” past end of circuit breaker
“A” See Table
Molded Case w/Mechanical Lugs
hardware, lugs, special purpose label and instructions Mounting hardware, lugs, special purpose label, Medium Terminal Shield and instructions Mounting hardware, lugs, special purpose label, Long Terminal Shield and instructions
150–250 A 150–250 A
(6) 14–4 AWG Cu (2) 14–1 AWG and (1) 3–2/0 AWG Cu
1.0
PDC6JD4
3
JD, JG, JJ, JL [31]
“A” See Table
1.5
PDC3JD20
3
(3) 14–1 AWG and (2) 3–2/0 AWG
150–600 A
1.28
PDC5DG20L3
3
LD, LG, LJ, LL [32]
150–600 A
(12) 14–4 AWG
1.31
PDC12DG4L3
3
Table 7.110: Power Distribution Connectors for M-Frame and P-Frame Circuit Breakers [30] Ampere Rating (WiresPer Terminal) WireRange Cat.No. Qty PerKit Kit Contents
Use for multiple load connections on one circuit breaker in place of standard distribution block to save space and time. • Use on load end of circuit breaker only • Use in UL508 Industrial Control applications only. • Use in UL1995/CSA C22.2 No. 236 heating and cooling equipment. • For Cu wire only.
Mounting hardware, lugs, special purpose label and instructions Mounting hardware, lugs, special purpose label and instructions Mounting hardware, lugs, special purpose label and instructions Mounting hardware, lugs, special purpose label and instructions
(6) 12–2/0 AWG Cu
PDC6P20
3
PDC12P4
PDC6P20
250– 1200A
(6) 12–2/0 AWG Cu PDC6P204
4
PDC12P4
3
250– 1200A
(12) 10–4 AWG Cu
PDC12P44
4
7 MINIATURE AND MOLDED CASE
CIRCUIT BREAKERS
[29] Refer to Table xxxxxx: Terminal Shields and Phase Barriers [30] Not for use with I-Line™ circuit breakers. [31] Special Purpose—Not for General Use. Use on ON end of the circuit breaker only when ON end is used as Load end. Use on OFF end of the circuit breaker only when OFF end is used as Loadend. [32] Kit includes long terminal shield and cover, which adds 1.65 inches to standard lug with short terminal shield.
7-58
© 2021 Schneider Electric All Rights Reserved July 30, 2021