Table 7.104: Mechanical Lug Kits for B-Frame Circuit Breakers [17] Description Circuit Breaker Application

Field Installable Cat. No. LV426966 LV426967 LV426964 LV426965

Number of Wires Per Lug and Wire Range (1) 14-2/0 AWG Al or Cu (1) 14-2/0 AWG Al or Cu

Factory-Installed Cat. Suffix

QtyPer Kit

Ampere Rating

Ampere Rating

Optional BDBGBJ BDBGBJ BDBGBJ BDBGBJ

Standard

15-125A 15-125A 15-125A 15-125A

LH LH LC LC

2 3 2 3

Al Lugs for Use with Al orCuWire Cu Lugs for Use with Cu Wire Only

(1) 14-1/0 AWG Cu (1) 14-1/0 AWG Cu (1) 14-3/0 AWG Cu (1) 14-3/0 AWG Cu (1) 14-3/0 AWG Cu (1) 14-3/0 AWG Cu (1) 14-3/0 AWG Cu (1) 14-3/0 AWG Cu (1) 14-3/0 AWG Cu

BD BG BJ (1P) BD BG BJ (2P) BD BG BJ (3P) BD BG BJ (4P)

15 - 125A 15 - 125A 15 - 125A 15 - 125A 15 - 125A 15 - 125A 15 - 125A

— — — —

— — — —

— — — —

EverLink Lug

BD BG BJ (2P) BD BG BJ (3P) BD BG BJ (4P)

LU, LV, or LW [18] LU, LV, or LW [18] LU, LV, or LW [18]

LV426973 LV426974 LV426975

1 1 1

EverLink Lug with Control Wire Terminal

Table 7.105: Mechanical Lug Kits for H- and J-Frame Circuit Breakers [17] Description Circuit Breaker Application

Number of Wires Per Lug and Wire Range (1) 14–3/0 AWG Al or Cu (1) 4-4/0 AWG Al or Cu (1) 3/0–350 kcmil Al or Cu

QtyPer Kit

Ampere Rating

Kit Cat. No. AL150HD AL175JD AL250JD CU150HD CU250JD

Ampere Rating

Optional

Standard

HD, HG, HJ, HL JD, JG, JJ, JL JD, JG, JJ, JL

15–150A 150–175A 200–250A

3 3 3 3 3 2 2

Al Lugs for Use with Al or Cu Wire Cu Lugs for Use with Cu Wire Only

JD,JG,JJ,JL HD,HG,HJ,HL JD,JG,JJ,JL

150–175A 15–150A 150–250A

(1) 14–2/0 AWG Cu (1) 1/0–300 kcmil Cu

Control Wire Terminal for H-frame lug kit Control Wire Terminal for J-frame lug kit

S37423 S37424

Table 7.106: Mechanical Lug Kits for L-Frame Circuit Breakers [19] Descrip tion Circuit Breaker Application Number of Wires Per Lug and Wire Range

Qty Per Kit

Kit Cat. No.

Ampere Rating Poles

Unit Mount

I-Line

250

3 4

X X X X X X X X X X

X

(1) 2 AWG–500 kcmil Al (1) 2 AWG–600 kcmil Cu

AL400L61K3 3 AL400L61K4 4

Al Lugs for UsewithAl orCuWire

400/600 3

— (2) 2/0 AWG–500 kcmil Al or Cu AL600LS52K3 3

4

AL600LS52K4 4

400/600 3

X (2) 3/0 AWG–500 kcmil Al or Cu AL600LF52K3 3

250

3 4

X

CU400L61K3 3 CU400L61K4 4

(1) 2 AWG–600 kcmil Cu

CuLugs for Usewith CuWire Only

400/600 3

— (2) 2/0 AWG–500 kcmil Cu CU600LS52K3 3

AL250JD

AL400L6IK3

AL600LS52K3

4

CU600LS52K4 4

J-Frame Lug

L-Frame Lug

(2) 3/0 AWG–500 kcmil Cu CU600LF52K3 3

400/600 3

X

Table 7.107: Mechanical Lug Kits for M-, P- and R-Frame Circuit Breakers [20] Descrip tion Circuit Breaker Application Wires per Lug and Wire Range Cat.No. Lugs Per Kit Standard Rating Optional Rating

AL800M23K AL800M23K4

3 4 1 3 4 3 4 3 4 3 4 3 4 1 2 3 3 4 1 3 4 1

800A

— 800 A (3) 3/0 AWG-500 kcmil MG,MJ, PG, PJ, PK, PL 800 A (4) 3/0 AWG-500 kcmil MG,MJ, PG, PJ, PK, PL 800 A (2) 3/0 AWG-600 kcmil

AL1200P24K [21] AL800P6K [21] AL800P6K4 [21] AL800P7K [21] AL800P7K4 [21] AL1200P25K [22] AL1200P25K4 [22] AL1200P6KU [22] AL1200P6KU4 [22] AL1200P7KU [22] AL1200P7KU4 [22] AL1200R53K AL2500RK [23] CU250P1K [25] CU800M23K CU800M23K4 CU1200P24K [21] CU1200P25K [22]

1200A

M-Frame, P-Frame

AL800M23K

AL800P6K

(2) 3/0 AWG-750 kcmil 750 kcmil: compact AL only

M- and P-Frame Lugs (800 A and below)

MG,MJ, PG, PJ, PK, PL 800 A

Al Lugs forALor CuWire

1200 A PG, PJ, PK, PL

800 A (4) 3/0 AWG-500 kcmil

P-Frame

800– 1200A

(3) 350-600 kcmil

— PG, PJ, PK, PL

(3) 3/0 AWG-750 kcmil 750 kcmil: compact AL only

PG,PJ,PL — PG, PJ, PK, PL

1200A

1200 A I-Line 2500 A Unit Mount

— (4) 3/0 AWG-600 kcmil — (1) 3/0 AWG-750 kcmil

AL800P6K

AL1200P6KU

R-Frame

7 MINIATURE AND MOLDED CASE

100– 150A

(1) 1-1/0 AWG

— PJ

MG,MJ, PG, PJ, PK, PL MG,MJ, PG, PJ, PK, PL

M-Frame, P-Frame

800A

— (3) 3/0 AWG-500 kcmil

CuLugs forCu Wire Only [24]

800– 1200A 800– 1200A

(4) 3/0 AWG-500 kcmil

1200A

(4) 3/0 AWG-500 kcmil

P-Frame 1200 A PG, PJ, PK, PL R-Frame 1200 A I-Line

AL1200P25K P-Frame Lugs (Above 800 A)

CU1200P25K4 CU1200R53K

CIRCUIT BREAKERS

— (4) 3/0 AWG-500 kcmil

[17] For terminal nuts/bus bar connections see page 7-59. [18] LU = ON end only, LV = OFF end only, LW = BOTH ends

[19] Lug kits for Legacy L-frame circuit breakers can be found in Supplemental Digest Section 11 (i.e. LA, LH circuit breakers). [20] For lug with a tapped hole for control wire, add a “T” before the “K” in the catalog number (for example, AL800P6TK). [21] Does not fit onto ON end of unit-mount P-frame circuit breakers. [22] For unit-mount circuit breaker only. [23] All unit-mount R-frame circuit breakers require terminal pads for mounting lugs of any type. See page 7-59. [24] Not available with tapped hole for control wire. [25] This lug can only be used on low amp PJ frame breakers where the Instantaneous setting must not be turned OFF. The cables must be laced with rope per lug instructions.

7-56

© 2021 Schneider Electric All Rights Reserved July 30, 2021