SE Digest 178
Motor Circuit Protectors
Motor Protection Selection Tables
Class 601
www.se.com/us
Table 7.96: Selection Tables for Conductors, Safety Switches and Thermal-Magnetic Circuit Breakers Based on 2017 NEC ® Tables 430.247, 430.248 & 430.250 Horsepower Ratings
Amperage of Thermal-Magnetic [2] Inverse Time Circuit Breaker
Minimum Size metallic Conduit 75° C, C Wire Field-Installed Sized for 125% FLA [4]
QMB and Heavy Duty Switch with Time Delay Fuses [3]
Squirrel-Cage and Wound Rotor Motors with Norm. Torque Characteristics Operating at Usual Speeds
Average Direct Current Motors Operating at BaseSpeed
For Motor Code Letter B to E
1Ø 10Hzac
Full Load Amperage [1]
For Motor Code LetterF toV [5]
Conduit 3W
3Ø60Hz
AWG kcmil
Heavy Service andEnergy Efficient [7]
THHN THWN XHHW
Ordinary Service [6]
200 Vac [8]
200 Vac [8]
THW
230 Vac
460 Vac
575 Vac
115 Vac
230 Vac
120 Vdc
240 Vdc
3/4
6.9A 7.2A 7.6A 7.8A 7.9A 8.0A 8.5A 9.0A 9.2A 9.5A 9.6A 9.8A
15A
1/3
5
3.4
20A
2
3/4
1
15A
2
7-1/2
20A
1
1
25A
3
14
1/2 in.
N/A
1/2
1-1/2
10.0A 11.0A 11.5A 12.0A 12.2A 13.2A 13.8A 14.0A 15.2A 16.0A 17.0A 17.5A 19.6A 20.0A 21.0A 22.0A 24.0A 25.0A 25.3A 27.0A 28.0A 29.0A 32.0A 32.2A 34.0A 38.0A 40.0A 41.0A 42.0A 46.0A 48.3A 50.0A 52.0A 54.0A 55.0A 56.0A 57.5A 58.0A 62.0A 62.1A 65.0A 68.0A 72.0A 76.0A 77.0A 78.2A 80.0A 89.0A
3
7-1/2 10
20A
30A
1-1/2
30A
2
25A
3
1-1/2
25A
35A
3/4 2
10
5
40A
1
30A
35A
15
3
2
45A
5
35A
12
1/2 in.
N/A
3
40A
50A
1-1/2
5
15
40A
45A
7-1/2
60A
2
45A
50A
3
10
1/2 in.
N/A
7-1/2
50A
70A
20 25
60A
10
5
7-1/2
80A
30
60A
10
70A
1/2 in. [9]
90A
60A
8
N/A
25
3
10
80A
100A
7-1/2
5
80A
90A
110A
15
7–1/2
6
3/4 in.
1 in.
15
125A
10
110A
40 50
20
90A
15
150A
5
10
7-1/2
125A
4
1 in.
1 in.
60
100A
20
100A
175A
50
25
150A
20
110A 125A
10
60 75
200A
3
1 in.
1-1/4 in.
25
110A
175A
30
7-1/2
25
125A
225A 200A 2
1 in.
1-1/4 in.
7 MINIATURE AND MOLDED CASE
CIRCUIT BREAKERS Thermal-magnetic circuit breaker ampere ratings recommended are approximate for average conditions, based on trip characteristics of Square D circuit breakers and NEC Table 430.52. Under some conditions, the next size larger switch or circuit breaker rating may be necessary to accommodate the motor starting current and is permitted by NEC 430.52(C)(1) Exception 2. High starting currents are anticipated with Design E and other energy efficient motors. For explanation of Code letter markings, see NEC 430.7(B). For Busway Plug-in units, see page 9-7. [3] Switch size only is shown in table. Selected fuses should not exceed maximum percent of full-load current as given in NEC Table 430.52. Above 50 hp dc switches are not hp rated by UL as Motor Circuit Switches, but as General Use Switches only and are not necessarily capable of interrupting the max. operating overload current of a motor. See NEC 100 for definition of General Use Switch. When protecting a 3Ø, Design E energy efficient motor, the switch is required by NEC 430.109 to have a hp rating of not less than 1.4 times that of a motor rated 3–100 hp, or not less than 1.3 times that of a motor rated over 100 hp. Switches shown in this table do not necessarily comply with that requirement. [4] NEC 430.22 for Single Motor, Smaller conductors may be permitted for light duty-cycle service per 430.22 (B) Exception No. 1. DC motors operating from rectified 1Ø power supply will require larger conductors per 430.22 (A) Exception No. 1. For motor-generator arc welders, see 630.11 [5] Thermal-magnetic breaker ampere ratings recommended are approximate for average conditions and based on trip characteristics of Square D circuit breakers and NEC Tables 430.7(B) and 430.52. [6] Ordinary service for normal starting duty only, acceleration time of 10 sec. or less. [7] Heavy service is jogging or plugging duty or cycling load with over 25 starts per hour or over 5 starts per minute. Energy efficient motors are polyphase motors defined in NEMA Standard MG1 and exhibit high starting current. [8] 200 V motors are commonly used on 208 V services. [9] 8 XHHW requires 3/4 in. conduit for 3W. [1] Motor full load currents thru 200 hp are taken from NEC Tables 430.247, 248 and 250. Above 200 hp from UL 98. Select wire size, circuit breakers, or fuses on basis of hp rather than nameplate full load current per NEC 430.6. Do not use these values to select overload relay thermal units. See Digest pages 16-129—16152 for selection of thermal units when actual full load current is not known. Voltages listed are rated motor voltages. Corresponding nominal system voltages are 110–120 V, 200–208 V, 220–240 V, 440–480 V and 550–600 V [2]
7-48
© 2021 Schneider Electric All Rights Reserved July 30, 2021
Made with FlippingBook flipbook maker