SE Digest 178
Power Factor Correction
Power Quality Improvement Solutions
Class 3030
www.se.com/us
VarSet Detuned Capacitor Banks
The VarSet Detuned automatic capacitor banks provide power factor correction in electrical distribution networks with moderate levels of harmonic content. The series capacitor and reactor combination is tuned below the first dominant harmonic order (usually the 5th). This prevents resonance and harmonic amplification.
Rebranded
Table 4.43: General Characteristics VarSet Detuned Capacitor Banks Electrical Characteristics Rated voltage ( Un ) / Frequency
480V / 60Hz
Capacitance Tolerance
-5%+10%
Connection type
Three-phase < 6 W per kvar
Power losses
Maximum permissible over current Maximum permissible over voltage
1.3x In
1.1 x Un, 8h per 24h
Enclosure Degree of protection
NEMA1
Color
RAL 7035 (VLV model ) or ASA 49 ( AV/BV Model )
Controller VarPlus Logic
VarPlus Logic controller with embedded Modbus communication
VLVAF4P
Head Protection Without incoming circuit breaker
Lug connection LV PFC Bank must be protected by a circuit breaker or by a fused disconnector on upstream switchboard
AV6000
With incoming circuit breaker
PowerPact with rotary handle
Step
Environment • Installation: Indoor • Ambient temperature: 15 °F to 104 °F (-10 °C to 40 °C) • Humidity: Up to 95% • Maximum altitude: 6500 feet (2000 m) Standards • CSA 22.2 No. 190 • UL810, UL508a Environmental Certifications • Produced in 14001 certified plants, product environmental profile available
Varplus Can 575 V for network voltage 480 V Maximum overcurrent 1.8 xIn 3 ph overpressure disconnection system Discharge resistor 50 V - 1 mn
Capacitors
Dedicated to capacitor switching VarplusDR Overheating protection by thermostat
Contactors
Detuned reactor
Circuit breaker protection Temperature Control Double control Communication ModBus Installation Customer connection Auxiliary transformer
PowerPact
By thermostat and by controller
RS485
TopEntry
120 V included, no need of additional supply
5 VA - secondary 1 or 5 A To be installed upstream of the load and capacitor bank
CT not included (see Current Transformer Selection, page4-40)
CONTROL
GenSet contact Alarm contact
Available for disconnection with generator Available for remote warning signal
4 POWER MONITORING AND
Options available by request: • Fixed stages (by controller programming) • Custom staging ratios • Other voltages and frequencies • Outdoor arrangement - Built to NEMA 3R (AV/BV models only) • Bottom cable entry to main lugs (AV models only) • Bottom cable entry to main breaker (BV models only)
4-37
© 2021 Schneider Electric All Rights Reserved 6/20/2021
Made with FlippingBook flipbook maker