SE Digest 178
Application Data
Double Throw Safety Switches
Class 3110 / Refer to Catalog 3100CT1602
www.se.com/us
Application Data for Double Throw Safety Switches Situations Requiring Fuses 30–100 A Type DT (Series F):
Select DT switches from 240 Volt Double-Throw Safety Switches, page 3-26 and 600 Volt Double Throw Safety Switches, page 3-27 which have provisions for accepting fuses. 30 A, 200–600 A Type 82,000 (Series E, T4, A), all DTU devices: Use the non-fusible double throw switches from 240 Volt Double-Throw Safety Switches, page 3-26 and 600 Volt Double Throw Safety Switches, page 3-27 in conjunction with standard fusible devices, and install them according to diagram 1 or 2, below.
Table 3.54: UL Listed Short Circuit Current Ratings Switch Type Amperes Voltage Rating ULListed FuseClass
Line
Short Circuit Current Rating [43] (A)
Line
Fusible Single Throw Switch or Circuit Breaker
10,000 [44] 10,000 200,000 10,000 [44] 200,000
Type92000 TypeDT (SeriesF)
H, K H, K R, J
30A
240V
Line 3 SAFETY SWITCHES
Non-Fusible Double Throw Switch
240Vor 600V 240Vor 600V
30–100A
HorK
TypeDTU [45] (SeriesF)
30–100A
R, Jor T
Non-Fusible Double
DTU224NRB and DTU324NRB (SeriesE)
10,000 [44]
H, K
200A
240V
Load
Throw Switch
10,000 [44]
H, K R, J H, J H, K
DTU324N (SeriesE)
200A
240V
100,000
240Vor 600V 240Vor 600V
Type 82,000
10,000 [44]
All
Fusible Single Throw Switch or Circuit Breaker
Fusible Single Throw Switch or Circuit Breaker
10,000 100,000
TypeDTU (SeriesA)
400–600A
R, J, T
Line
Load
Diagram 2
Diag ram 1
[43] Rating applies to AC only. The UL Listed short circuit current rating for non-fusible switches is based on the switch being used in conjunction with the corresponding fuse type. Evaluation of non-fusible switches in conjunction with molded case circuit breakers has not been performed. [44] Any brand of circuit breaker or fuse not exceeding the ampere rating of the switch may be used ahead of a non-fusible safety switch when there is up to 10 kA short circuit current available. [45]
The DTU361 and DTU361RB are also suitable for use on a circuit capable of delivering not more than (A) 18 kA, 600 Vac maximum when protected by Type FH circuit breaker rated 30 A maximum or (B) 14 kA, 600 Vac maximum when protected by Type FA circuit breaker rated 30 A maximum.
3-30
© 2019 Schneider Electric All Rights Reserved