SE Digest 178
SE Legacy 6000 Relays Refer to Catalog 8501CT1002
Solid State Relays
www.se.com/us
70S2 Solid-State Relays 70S2 — SPST-NO, 3–25 A Part Number 70S201A
70S202A
70S203B
70S203C
Input Characteristics Control Voltage Range
3–15Vdc
9–30Vdc
3–30Vdc
Must Release Voltage 1Vdc Typical Input Current 5–40 mA
5–17mA
7–16mA
6–10mA
Maximum Reverse Control Voltage
3Vdc
Output Characteristics Switching Device
MOSFET
TRIAC
70S2 (V) Relay
70S2 (F) Relay
70S2 (S) Relay
Switching Type Contact Configuration Output Voltage Range Peak Blocking Voltage Maximum Rate of Rise Off-State Voltage (dv/dt) Output Current Range (rms) Non-Repetitive Surge Current (8.3 ms) Maximum Off-State Leakage Current (rms) Typical On-State Voltage Drop (rms) Maximum Turn-On Time Maximum Turn-Off Time
DC Switching
AC Zero Cross
SPST-NO
3–60Vdc
24–140Vac
24–280Vac
105Vdc
400Vac
600Vac
70S2 (M) Relay
70S2 (N) Relay
N/A
300V/us
3–5A
5A
25A
25A
23 RELAYS AND TIMERS
Minimum Load Current–Maintain On N/A
100mA
3A:5A(1s);5A:7A(1s)
300A
10mA
6mA
3 A: 1.2 Vdc; 5 A: 1.85 Vdc
1.7Vac
75ms
8.3ms
3 A: 500 ms; 5 A: 75 ms
8.3ms
70S2 Specifications (UL 508)
Part Number
70S201A
70S202A
70S203B
70S203C
Input Characteristics Control Voltage Range Must Release Voltage Typical Input Current
3–15Vdc
9–30Vdc
3–30Vdc
1Vdc
5–40mA
5–17mA
7–16mA
6–10mA
Maximum Reverse Control Voltage 3 Vdc Output Characteristics Switching Device MOSFET
TRIAC
Switching Type
DC Switching
AC Zero Cross
Contact Configuration Output Voltage Range Peak Blocking Voltage
SPST-NO 3–60Vdc
24–140Vac
24–280Vac
105Vdc
400Vac 300V/us
600Vac
Maximum Rate of Rise Off-State Voltage (dv/dt) Output Current Range (rms)
N/A
3–5A
5A
25A
25A
Minimum Load Current–Maintain On N/A Non-Repetitive Surge Current (8.3 ms)
100mA
3A:5A(1s);5A:7A(1s)
300A
Maximum Off-State Leakage Current (rms)
10mA
6mA
Typical On-State Voltage Drop (rms) 3 A: 1.2 Vdc; 5 A: 1.85 Vdc
1.7Vac 8.3ms 8.3ms
Maximum Turn-On Time Maximum Turn-Off Time
75ms
3 A: 500 ms; 5 A: 75 ms
70S2 Specifications (UL 508) Continued
Part Number
70S204B
70S204C
70S204D
70S205C
70S206C
Input Characteristics Control Voltage Range Must Release Voltage Typical Input Current
3 A: 3–32 Vdc; 4/6/10/12 A: 3–30 Vdc
6–30Vdc
3–30Vdc
1Vdc
3 A: 1–19 mA; 4/6/10/12 A: 7–16 mA
6–10mA
1–17mA
Maximum Reverse Control Voltage
3Vdc
Output Characteristics Switching Device
TRIAC
Switching Type
AC Zero Cross
Contact Configuration Output Voltage Range Peak Blocking Voltage
SPST-NO 24–140Vac
24–280Vac
8–50Vac 200Vac
24–280Vac
400Vac 300V/us
600Vac
600Vac
Maximum Rate of Rise Off-State Voltage (dv/dt)
Output Current Range (rms)
3–12A
3–12A
3A
12A
3/4/6 A: 75 mA; 10/12 A: 100 mA 3/4/6 A: 60 A; 10/12 A: 150 A
Minimum Load Current–Maintain On Non-Repetitive Surge Current (8.3 ms) Maximum Off-State Leakage Current (rms) Typical On-State Voltage Drop (rms)
6mA
10mA
6mA
1.6Vac 8.3ms 8.3ms
© 2020 Schneider Electric All Rights Reserved 10/25/2020 Maximum Turn-On Time Maximum Turn-Off Time
23-85
Made with FlippingBook flipbook maker