SE Digest 178
QO™ Miniature Circuit Breakers
QO Plug-On Circuit Breakers
Class 685, 690, 730, 912, 950 / Refer to Catalog: 0730CT9801
www.se.com/us
1 LOAD CENTERS
QO-EPD/EPE Circuit Breakers
QO-EPD/EPE circuit breakers provide overload and short circuit protection combined with Class B ground fault protection. They are designed to provide ground fault protection of equipment at a 30 mA level (EPD) or 100 mA level (EPE). They are not designed to protect people from electrical shock. Table 1.9: QO-EPD Circuit Breakers Ampere Rating [19] 1P 120Vac 10kAIR 1 Space Required 2P Common Trip 120/240 Vac 10kAIR 2 Spaces Required 3P Common Trip 240Vac 10kAIR 3 Spaces Required
QO315EPE [20] QO320EPE [20] QO330EPE [20] QO340EPE [20] QO350EPE [20] —
QO115EPD QO120EPD
QO215EPD QO220EPD QO225EPD QO230EPD QO240EPD QO250EPD
QO315EPD OBS QO320EPD [20] QO330EPD [20] QO340EPD [20] QO350EPD [20] —
15 20 25 30 40 50 60
QO125EPD OBS
QO1P With Shunt Trip
QO130EPD
— — —
QO260EPD [21]
—
—
OBS This product is obsolete.
QO Switch Neutral Common Trip Circuit Breakers (QO-SWN)
Switch Neutral Common Trip 2008 NEC ® 514.11 Table 1.10: QO-SWN Circuit Breakers Ampere Rating [22] 2 Wire 120 Vac 10kAIR 2 Spaces Required
3 Wire 120/240 Vac 10kAIR 3 Spaces Required
QO310SWN
QO210SWN OBS
10 15 20 25 30 40 50
QO215SWN QO220SWN
QO315SWN OBS
QO320SWN QO325SWN
QO225SWN OBS QO230SWN OBS QO240SWN OBS QO250SWN OBS
QO330SWN OBS QO340SWN OBS QO350SWN OBS
Two-wire QO-SWN
Three-wire QO-SWN
OBS This product is obsolete.
QO High Intensity Discharge Circuit Breakers (QO-HID) HID circuit breakers are for use on circuits feeding fluorescent and high intensity discharge (HID) lighting systems such as mercury vapor, metal halide, or high pressure sodium. These circuit breakers are physically interchangeable with QO circuit breakers. Table 1.11: QO-HID Circuit Breakers Ampere Rating [22] 1P 120/240 Vac 10kAIR 1 Space Required 2P Common Trip 120/240 Vac 10kAIR 2 Spaces Required 3P Common Trip 240Vac 10kAIR 3 Spaces Required
QO215HID OBS
QO315HID OBS
QO115HID OBS
15 20 25 30 40 50
QO220HID
QO320HID
—
QO125HID OBS QO130HID OBS QO140HID OBS QO150HID OBS
QO225HID OBS QO230HID OBS QO240HID OBS QO250HID OBS
QO325HID OBS QO330HID OBS
— —
OBS This product is obsolete.
QO Key Operated Circuit Breakers (QO-K)
Key operated QO circuit breakers are available in single-pole construction and can be mounted in any single-pole space which will accept a standard QO circuit breaker. These circuit breakers can be turned ON or OFF or to RESET with a special key (catalog number QOK10) included with the circuit breaker. These circuit breakers are UL Listed
and available as shown in the table. Table 1.12: QO-K Circuit Breakers
120 Vac—10 k AIR (1 Space Required)
Ampere Rating [22]
Ampere Rating [22]
Cat. No.
Cat.No. QO125K
QO110K OBS QO115K OBS QO120K OBS
10 15 20
25 30 —
QO130K OBS
—
OBS This product is obsolete.
QO-K Key Operated
[19] 10–30 A circuit breakers are suitable for use with 60 o Cor 75 o C conductors. 35–60 A circuit breakers are suitable for use with 75 o C conductors. [20] See note in Instruction Bulletin when using in an enclosure with a QO403 or QON prefix. [21] Suitable only for feeding 240 Vac and 208 Vac two-wire loads. Does not contain load neutral connection. [22] 10–30 A circuit breakers are suitable for use with 60oC or 75oC conductors. 35–60 A circuit breakers are suitable for use with 75oC conductors.