SE Modicon M580 Brochure

Description The BMENOP0300 IEC 61850 module is installed on the local Ethernet rack of a Modicon M580 system. The 6 LEDs on the front panel 1 are used to diagnose operating conditions: b RUN LED (green): Operating status b ERR LED (red): Error detected b MS LED (green/red): Module status Modicon M580 automation platform Modicon M580 Communication modules IEC 61850 module

Description, references

1

1

b NS LED (green/red): Network connection status b NS1 LED (green/red): Ethernet network status b NS2 LED (green/red): Ethernet network status

2

2

With three Ethernet ports 2 to link external intelligent electrical devices (IEDs), the module provides interfaces for IEC 61850 communication as well as device management software that utilizes the IEC 61850 standard (1) . The maximum number of BMENOP0300 modules that can be mounted on a local rack is determined by the M580 processor model:

BMENOP0300

3

BMEP581020 BMEP582020 BMEP582040(S)

BMEP583020 BMEP583040

BMEP584020 BMEP584040(S) BMEP585040 BMEP586040(S) BMEH584040(S) BMEH586040(S)

Standalone processor model

BMEH582040(S)

Redundant processor model Maximum number

4

2

3

4

Main features The main features of the BMENOP0300 module are as follows: b Compatible with the entire range of M580 CPUs, in both standalone and redundant configuration: v Ring topologies on 2 Ethernet ports using RSTP (Rapid Spanning Tree Protocol) b Cybersecurity features:

5

v ISA99 Achilles Level 2 certification v IPSec for IP-based communication b IEC 61850 services: v MMS messaging server and client v GOOSE publisher and subscriber

b Network management using SNMP (Simple Network Management Protocol) b Time synchronization: to be able to synchronize with external time servers and update the internal clock b Modbus TCP support (limited, no I/O scanning)

6

Capabilities The capabilities (2) per module are: b 16 logical devices

7

b MMS server: 16 concurrent connections, 64 report control block instances, 8 instances for one report control block, 68 data sets, 256 data attributes/data set, URCB and BRCB reports b Control model: DOes, SBOes, DOns, SBOns b MMS client: 32 concurrent connections b GOOSE: 4 control blocks for GOOSE publish and 32 control blocks for GOOSE subscribe, up to 256 inputs/data set References Description Usage Reference Weight kg/ lb

8

Modicon M580 IEC 61850 communication module

BMENOP0300 (3)

IEC 61850 communication module used in M580 local rack Ethernet backplanes

0.345/ 0.761

9

(1) Requires EcoStruxure Control Expert or Unity Pro software V12.0 or later (see our website). (2) Depends on the data model complexity. Maximum value has to be balanced with module performance behavior (loop latency, response time, etc.) (3) For the BMENOP0300C version with conformal coating, see page 6/5.

10

4/23