SE Modicon M580 Brochure

Modicon M580 automation platform Modicon M580 redundant processors

Selection guide

Modicon M580 automation platform

BMEH5820 model

BMEH5840 model

BMEH5860 model

1

1

2

2

Racks

Local racks (main + extension)

1 8

31

Remote I/O drops (1) Discrete I/O channels

16

Local X80 I/O (2) (3)

Safe discrete I/O channels Analog I/O channels Safe analog I/O channels Application-specific channels (4)

3

3

Not supported

Combined Local and Remote X80 I/O (3)

31744

Discrete I/O channels

8192

16384

Safe discrete I/O channels

Not supported

7936

Analog I/O channels

2048

4096

4

4

Safe analog I/O channels

Not supported

1116

Application-specific channels (4)

288

576

Distributed equipment (DIO, CSIO)

EtherNet/IP or Modbus TCP devices (scanned by CPU)

61

573

EtherNet/IP or Modbus TCP devices (scanned by CPU and Ethernet modules)

BMENOC301/ BMENOC311

317

573

CIP safety devices (scanned by CPU)

Not supported

Integrated communication ports

Ethernet service port (RJ45)

Engineering and Maintenance console (EcoStruxure Control Expert, Web browser, external tools), HMI, SCADA, Distributed equipment (DIO)

5

5

Ethernet device network dual ports (RJ45) - RSTP

RIO network (RIO/DIO scanner)

USB type mini B port

Programming port for Engineering Console (EcoStruxure Control Expert)

Communication

Cumulative max number of : Ethernet networks modules

Ethernet networks

BMENOC/BMENOP/ BMENOR

2

4

EtherNet/IP and Modbus TCP

EtherNet/IP and Modbus TCP module BMENOC0301

2 2 2 2 2 2

4 4

FactoryCast IP Forwarding

FactoryCast module Ethernet control router

BMENOC0311 BMENOC0321 BMENOP0300 BMENUA0100 BMENOR2200H BMXNOR0200H (5)

6

6

IEC 61850

IEC 61850 module OPC UA module

4

OPC UA

DNP3 Serial/NET, IEC60870-5-101/104 Advanced RTU module

4

DNP3 Serial / IEC 60870-5-101

RTU module

– (6) – (6) 4 (7)

Global Data AS-Interface

Global Data module AS-Interface module Serial link module CANopen module PROFIBUS DP module Program process (MB)

BMXNGD0100 BMXEIA0100 BMXNOM0200 BMECXM0100 PMEPXM0100

7

7

8 (7)

Serial Link (Modbus and Character)

(8)

CANopen

– (6)

2 8

6

10 64

PROFIBUS DP

Internal memory capacity

16

Data process (KB) Data storage (GB)

768

2048

Up to 64MB

4

8

8

No. of K instructions executed per ms

100% Boolean (Kinstr/ms)

10

40 30

50 40

65% Boolean + 35% fixed arithmetic (Kinstr/ms) Support of Quantum Ethernet I/O and LL984 Editor

7.5 No

Product compatibility with Quantum

Yes

References

BMEH582040

BMEH584040

BMEH586040

Pages 2/8 (1) A Remote I/O drop can be either a X80 RIO Drop (RIO) or a Quantum Ethernet I/O drop (QEIO). One X80 RIO drop can support up to 2 racks (via X-bus extension). (2) Local X80 I/O are localized in local racks (main or extension). Redundant controllers do not not support Local X80 I/O. (3) Maximum number of I/O channels (Discrete, Safe Discrete, Analog and Safe Analog) as well as application-specific channels is not cumulative. (4) Application-specific channels include counters, time-stamping, SSI encoder, Motion control, Serial and Frequency input modules. (5) Maximum number of BMXNOR modules is not cumulative with other Ethernet network modules. (6) Not supported with redundant controllers. (7) Only supported in Remote I/O drops and with a maximum of 16 BMXEIA0100 modules. (8) Only supported in Remote I/O drops.

9

9

10

10

More technical Information on www.se.com

More technical Information on www.se.com

2/3 2/4

2/3 2/5

Made with FlippingBook flipbook maker