Modicon M580 automation platform Standards, certifications, and environment conditions

Environment tests (continued)

Environment tests (continued) Name of test

Standards

Levels

1

Immunity to mechanical constraints (1) (power on) Sinusoidal vibrations

IEC/EN 61131-2; IEC 60068-2-6 (Fc)

Basic IEC/EN 61131-2: 5 Hz ... 150 Hz, ± 3.5 mm/ 0.14 in. amplitude (5 Hz …. 8.4 Hz), 1 g (8.4 Hz …. 150 Hz) Specific profile: 5 Hz ... 150 Hz, ± 10.4 mm/ 0.41 in. amplitude (5 Hz …. 8.4 Hz), 3 g (8.4 Hz …. 150 Hz) For basic and specific: endurance: 10 sweep cycles for each axis 2 Hz ... 500 Hz, 7 mm/ 0.28 in. amplitude (2 Hz … 9 Hz), 2 g (9 Hz … 200 Hz), 1.5 g (200 Hz … 500 Hz) endurance: 10 sweep cycles for each axis Seismic analysis: 3 Hz ... 35 Hz, 22.5 mm/ 0.89 in. amplitude (3 Hz …. 8.1 Hz), 6 g (8.1 Hz …. 35 Hz) 30 g, 11 ms; 3 shocks/direction/axis (2) For Modicon M580 Safety: 15 g, 11 ms; 3 shocks/ direction/axis 25 g, 6 ms; 100 bumps/direction/axis (bumps) (3)

2

IEC 60870-2-2; IEC 60068-2-6 (Class Cm)

IEC 60068-2-6

Shock

IEC/EN 61131-2; IEC 60068-2-27 (Ea)

3

Free fall during operation

IEC/EN 61131-2; IEC 60068-2-32 (Ed Method 1)

1 m/ 3.28 ft , 2 falls

Name of test

Standards

Levels

Withstand to mechanical constraints (power off) Random free fall with packaging

IEC/EN 61131-2; IEC 60068-2-32 (Method 1) IEC/EN 61131-2; IEC 60068-2-32 (Ed Method 1)

1 m/ 3.28 ft , 5 falls

4

Flat free fall

10 cm/ 0.33 ft , 2 falls

Controlled free fall

IEC/EN 61131-2; IEC 60068-2-31 (Ec)

30° or 10 cm/ 0.33 ft , 2 falls

Plugging/Unplugging For modules and connectors: Operations: 50 for permanent connections, 500 for non-permanent connections (1) Devices must be installed, wired, and maintained in accordance with the instructions provided in the manual “Grounding and Electromagnetic Compatibility of PLC Systems” (see page 7/4). IEC/EN 61131-2

5

(2) When using fast actuators (response time y 5 ms) driven by relay outputs: 15 g, 11 ms; 3 shocks/direction/axis. (3) When using fast actuators (response time y 15 ms) driven by relay outputs: 15 g, 6 ms; 100 bumps/direction/axis. (4) Refer also to the section “Treatment for severe environments”. ( e ) : Tests required by European e directives and based on IEC/EN 61131-2 standards.

6

7

8

9