SE Modicon M580 Brochure

Modicon M580 automation platform Architectures High-availability architectures

Architectures

Example of a complex high-availability architecture The complex architecture below illustrates the extensive possibilities of the Modicon M580 offer in terms of mixed RIO and DIO networks: b A choice between 3 BMEH58 p 040 Modicon M580 redundant CPUs 1 b Easy integration of the I/O network with supervisors in the control network, due to the BMENOC03 p 1 Ethernet module 2 b Optimized wiring with RIO and DIO control via a single medium: the DIO are controlled via the CPU b High availability of secondary rings with Modicon managed switches 3 b Long distance optimized by the fiber optic converter 4 installed directly in the Modicon X80 rack b Simplified integration of devices via a serial link 5 (for example, power meter, variable speed drive, motor starters, protection relays, etc.); FTD/DTM technology makes it possible to configure and debug devices transparently via the Ethernet network, from any supervisor b Great flexibility due to integration of DIO devices 6 or other diagnostic/configuration tools on any drop SERVICE port or on the DIO port of a managed switch b Easy integration of Modicon X80 I/O drops on Ethernet with BMECRA31210 drop adapters 7 b The redundant power supplies are compatible with both single power supply racks for standard applications, and the dual power supply racks are compatible with high-availability applications 8

1

2

3

MES (Manufacturing Execution System)

Redundant system servers

Ethernet

4

Modicon M580 (“Standby” PLC)

Modicon M580 (“Primary” PLC)

1

Ethernet

HMI

HSBY communication link

2

7

Modicon X80 drop

5

Modicon X80 drop

Modicon X80 drop

IRIG-B/DCF77

3

7

Fiber optic

Telefast ABE7

Modicon managed switch

7

4

EcoStruxure Control Expert

6

Modicon X80 drop

Modicon X80 drop

STB I/O island

CANopen

7

HART instrumentation

5

Energy supervision

Altivar Process

6

Motor starter

Supervision

PROFIBUS remote master

Modicon X80 drop

Modicon X80 drop

7

PROFIBUS DP

PROFIBUS PA

AS-Interface

Altivar Process

7

7

8

Instrumentation on AS-I bus

4

Motor starter

8

Motor protection

Example of a complex high available architecture

9

10

Processors: page 2/2

Modicon M580 modules for severe environments: page 6/2

5/20