Square D Digest 179
30 mm Push Buttons
Type K, KX, and SK Selector Switch Guide
Class 9001 / Refer to Catalog 9001CT1103
www.se.com/us
Type K, KX, and SK Selector Switch Guide
Table 19.137: 2 Position Selector Switch If you require contact sequence—
Selection Shown below is a simplified method of selecting a selector switch to meet almost any combination of contact sequences. StepNo. 1 Determine the contact sequence(s) required. Set up a target table like the one shown for the example below. Contact Sequence 0—contact open 1— contact closed A 1 0 0 B 0 1 0 C 0 0 1 StepNo. 2 Look for a cam type common to all sequences in: Table 19.137 2 Position Selector Switch, page 19-53, Table 19.138 3 Position Selector Switch, page 19-53, or Table 19.139 4 Position Selector Switch, page 19-53. For the example above, Table 19.138 3 Position Selector Switch, page 19-53 would be used. ForthecontactsequencesA (1 0 0),B (0 1 0)andC (0 0 1)of the example above, cam types F and L are common to all three sequences. StepNo. 3 Next, use the cam type common to all the sequences (if several cam types are common, choose one) to find the operator type number. Go to the proper reference topic as indicated in the table below: Number of Positions Push Button Line Reference topics 4 Type K, page 19-52 Type SK, page 19-60 Type KX, page If for the example above a manual return operator with a standard black knob is required and: The F cam type is chosen, the operator type number is: • Type K—Class 9001 Type KS46B, page 19-51 • Type SK—Class 9001 Type SKS46B, page 19-59 • Type KX—Class 9001 Type KXSDFB, page The L cam type is chosen, the operator type number is: • Type K—Class 9001 Type KS401B, page 19-51 • Type SK—Class 9001 Type SKS401B, page 19-59 • Type KX—Class 9001 Type KXSDLB, page StepNo. 4: Determine the contact blocks required by using the same table in Step No. 2. If, for the example above, the F cam type is chosen: • Usea9001KA3mountedonsideno.2forsequenceA (1 0 0). • Usea9001KA3mountedonsideno.1forsequenceB (0 1 0). • Use a 9001KA2 mounted on side no. 1 or 2 for sequence C (0 0 1). If, for the example above, the L cam type is chosen: • Usea9001KA2mountedonsideno.2forsequenceA (1 0 0). • Use a 9001KA2 mounted on side no. 1 or a 9001KA3 mounted on sideno.2forsequenceB (0 1 0). • Usea9001KA3mountedonsideno.1forsequenceC (0 0 1). One Type KA1 double circuit block can be used in place of one Type KA2 single circuit block plus one Type KA3 single circuit block mounted on the same side. 2 TypeK, TypeSK, TypeKX Type K, page 19-50 Type SK, page 19-58 “H” Numbers, page 19-65 Type KX with Contacts, page Type KX without Contacts, page Type K, page 19-51 Type SK, page 19-59 “H” Numbers, page 19-65 Type KX with Contacts, page Type KX without Contacts, page 3 TypeK, TypeSK, TypeKX TypeK, TypeSK, TypeKX
Use Contact BlockType
Mount on sideno. [42]
Use Cam Type
E D E D
KA3 KA2 KA2 KA3
1or 2 1or 2 1or 2 1or 2
1
0
0
1
Table 19.138: 3 Position Selector Switch If you require contact sequence—
Use Contact BlockType
Mount on sideno. [42]
Use Cam Type
G
M KA2
1 2 1 2 2 1 2 1 2 1 2 1 2 1 2 2 1 2 1 1 1 2
L
KA2 KA3 KA3 KA2 KA2 KA3 KA3 KA2 KA3
C
E
1
0
0
B C
E F G J
KA5 [43]
B
G J
D E D E
J L
0
1
0
F
L
C
F
1or 2
B
D D
G L
KA3
0
0
1
KA5 [43]
B
M KA2
B
KA2
KA5 [43]
C
F
1or 2
1
1
0
M KA3
B
G J
KA2
KA5 [43] KA5 [43]
G
0
1
1
L
M KA3
J
KA3
KA5 [43] KA5 [43]
D E D E
J L
1
0
1
Table 19.139: 4 Position Selector Switch If you require contact sequence—
Use Contact BlockType
Mount on sideno. [42]
Use Cam Type
(A) KA3 (B) KA2 (C) KA2 (D) KA3
1 0 0 0 1 1 0 0 1 0 1 0 1 1
0 1 0 0 0 1 1 0 1 1 0 1 1 0
0 0 1 0 0 0 1 1 1 1 1 0 0 1
0 0 0 1 1 0 0 1 0 1 0 1 1 1
H H H H H H H H H H H H H H
2 1 2 1
A & D Wired in Parallel A & B Wired in Parallel B & C Wired in Parallel C & D Wired in Parallel A, B & C Wired in Parallel B, C & D Wired in Parallel A & C Wired in Parallel B & D Wired in Parallel
INTERFACE
KA5 [43] KA5 [43]
2 1
NOTE: For Outline Dimensions see Catalog 9001CT1103 NOTE: When ordering, add prefix 9001 to the catalog number. KA1 KA3 KA2 = + = + When ordering, please specify: • Quantity • Class Number • Type or Catalog Number For “H” Numbers, see Type K, SK, and KX Contact Block “H” Numbers, page 19-65
19 PUSH BUTTONS AND OPERATOR
[42] See Type K, SK, and KX Contact Block “H” Numbers, page 19-65 [43] Type KA5 must be the last block on either side. If more than one KA5 is required on either side—contact your local Square D sales office.
19-53
© 2024 Schneider Electric All Rights Reserved
Made with FlippingBook Ebook Creator