Square D Digest 179
NEMA 3R, 4, 4X, and 12
Separate Enclosures
Class 9991 / Refer to Catalog 9999CT9701
www.se.com/us
Separate Enclosures, Class 9991
Separate enclosures can be used with open style devices for field assembly of enclosed controls. These enclosures, plus the open style components, are equivalent to a factory assembled device. Separate enclosures are for use only with the following equipment: • NEMA 4 and 12 Class 9991 separate enclosures for Type S devices come standard with closing plates. See Table 16.294 for the specific number of closing plates. For applications requiring enclosures without closing plates, contact your nearest Schneider Electric sales office. • NEMA3R enclosures for field assembly of equipment for outdoor applications come with three closing plates, a reset mechanism, and a predrilled panel as standard. For a conduit connection to the top of these enclosures, select watertight hubs from the listing on Digest page 3-10 in accordance with applicable code requirements. Square D NEMA 12 enclosures can also be modified for outdoor use. For details, refer to the NEMA 12 enclosure modification information on page page 16-113. NOTE : Not for use in high-corrosive outdoor locations or sea coast environments. • NEMA4X enclosures for Type S devices, Sizes 0–2 and 30–60 A, come standard without closing plates. Cover mounted control units for NEMA 4X separate enclosures are available as a factory modification only. When closing plates are removed from NEMA 4, 12, and 3R enclosure covers, the openings can be used for easy installation of Class 9001 Type K or SK cover-mounted control units. Convenient Class 9999 modification kits containing Class 9001 Type K control kits can be found on page page 16-128. Table 16.293: How to Order To Order Specify: Catalog Number
NEMA 4X Enclosure
NEMA 12 Enclosure
16 NEMA AND DEFINITE PURPOSE CONTACTORS AND STARTERS
• Class Number • Type Number
Type
Class 9991
—
TypeSCH2 NEMA 3R Enclosure
NEMA 4 Enclosure
Table 16.294: Selection, Class 9991
Enclosure Classification
NEMA4X Watertight, Dusttight and Corrosion-Resistant Glass-Polyester
NEMA3R Rainproof, Sleet Resistant, Outdoor Use
NEMA4 [1] Watertight and Dusttight Stainless Steel
NEMA Size or Ampere Rating
For Use With
NEMA12/3R Dusttight and Driptight
Number of Closing Plates
Numberof Closing Plates
Types (All Pole Arrangements)
Type
Type
Type
Type
Class
Manual Starters 2510 [2]
MO M1 M1P
MBO,MCO
—
—
—
—
—
—
Magnetic Contactors
SAO, SBO, SCO
00, 0, 1
SCW20 SDW20
—
2 2 3 3 2 2 3 3 2 2 2 3
—
2 2 3 3 2 2 3 3 2 2 2 3
SCH2 SDH1 SEH1
SDA11 [4]
SDO SEO SFO
2 3 4
SDW11 SEW11 SFW11
8502 [3]
— —
— —
—
Magnetic Starters
SAO, SBO, SCO
00, 0, 1
— — — —
—
—
SCH2 SDH1 SEH1
SDA11 [4]
SDO SEO SFO
2 3 4
SDW11
8536
SEW11 [5] SFW11 [5]
— —
—
Lighting Contactors, Non-Combination, Electrically and Mechanically Held
SDA11 [4]
LO, LXO
20A 30A 60A
SDW20
SDW11
SDH1 SCH2 SDH1 SEH1
SCW20 [6] SCW20 [6]
SMO SPO SQO SVO
—
—
8903 [3]
SDA11 [4]
SDW11
SEW11 [5]
100A 200A
— —
— —
—
—
—
—
Reversing and Two-Speed, Horizontally Arranged Contactors and Starters 8702 [3] 8736 SBO, SCO SDO 0, 1 2 —
— SDA12 [4]
SCW12 SDW12 SCW13
— — —
3 3
3 3
0, 1
8810
SBO&SCO
—
—
The standard cabinet has a brushed finish.
[1] [2]
Type MBO, Size MO only.
[3] For contactors, replace the reset assembly with a proper closing plate: for NEMA 4, use Class 9001 Type K52; for NEMA 3R and 12, use Class 9001 Type K51. (Class 9991 Types SCW20 and SDW20 are designed for contactors only, so reset closing plates are not required.) [4] NEMA 12 enclosures can be field modified for outdoor non-corrosive and non–service entrance rated applications. See page 16-113 for more information. [5] This enclosure is suitable only for starters with a melting alloy , solid-state , or adapted bimetallic overload relay. [6] For electrically held devices only.
16-111
© 2024 Schneider Electric All Rights Reserved
Made with FlippingBook Ebook Creator