Square D Digest 179

NEMA Style Contactors, 1500 V

Vacuum Contactors and Starters, Full Voltage

www.se.com/us

Class 8502 / Refer to Catalog 8502CT9701

General Information

Figure 16.3: Class 8502 Type VF

The Class 8502 Type V vacuum contactor is a 3-pole device rated 1500 V that meets UL508 (1.5 kV) and CSA standards. Vacuum technology offers long life and low maintenance in a compact, lightweight design. The contactor is suitable for contaminated atmospheres because the main contacts are sealed in vacuum bottles. In addition, since gravity is not used to assist contactor operation, the Class 8502 contactor can be mounted in any plane without special modifications. Type V vacuum contactors are designed for the control of inductive or non-inductive loads at voltages from 200–1500 Vac. For How to Order Information, see page 16-28. NOTE: In Table 16.113, replace the three bullets (●●●) in the catalog number with the coil voltage code. Refer to the standard coil voltage codes listed in Table 16.78 Coil Voltage Codes, page 16-28. Table 16.113: Class 8502—Full Voltage 3 Pole Vacuum Contactors NEMASize Enclosed Ampere Rating Locked Rotor Current (A) Motor Voltage Max. Hp OpenStyle Type

16 NEMA AND DEFINITE PURPOSE CONTACTORS AND STARTERS

200 230 460 575 800

50 60

125 150 200 250 400 100 125 250 300 400 800 150 200 400 400 —

VFO3●●●

4

160

1080

1000 1500 200 230 460 575 800 1000 1500 200 230 460 575 800 1000 1500

5

320

2160

VGO3●●●

6

540

4320

VHO3●●●

— —

1300

Table 16.114: Class 9998—Replacement Coils for Class 8502/8702 (contains rectifier)

Suffix (the complete coil number consists of the Class, Type, and suffix) 110/120V 220/240V 440/480V 550/600V

Classand Type 9998WF 9998WG 9998WH

Size Type Poles

4 5 6

VF

3

120 120 120

240 240 240

480 480 480

600 600 600

VG 3 VH 3

Table 16.115: Class 9999—Vacuum Starter Kits For Use With Kit Description Size VF, VG 4, 5 Auxiliary Contacts, Non-Convertible 1 N.O. & 1 N.C. Isolated Contacts Type

Class9999 Type

WX11

VH VF

6

4 Coil Circuit Auxiliary Contacts

1 N.O. & 1 N.C. Isolated Contacts, Delayed Break 1 N.C. Isolated Contact

VG, VH 5, 6

WLX01 LUW5

VG VH

5 Lug Kits, 6 lugs included

6

16-45