Square D Digest 179
TeSys™ N Contactors and Starters
Non-Reversing Starters Refer to Catalog MKTED210011EN
www.se.com/us
TeSys N Non-Reversing Starters
TeSys N starters are used for full-voltage starting and stopping of AC squirrel-cage motors. Starters are available in NEMA Sizes 00–7 and come standard with Motor Logic Class 10/20 selectable solid-state overload relays. Starters with bimetal overload protection can be assembled from TeSys N contactors and TeSys Deca overload relays. Table 16.40: 3-Pole Polyphase, 600 Vac Max. (replace ●● with the coil voltage code) NEMASize Continuous Current Rating (A) Motor Voltage MaxHP Open Catalog No. [6]
16 NEMA AND DEFINITE PURPOSE CONTACTORS AND STARTERS
200 230 460 575 200 230 460 575 200 230 460 575 200 230 460 575 200 230 460 575 200 230 460 575 200 230 460 575 200 230 460 575 200 230 460 575
1.5 1.5
00
9
T36AN13●●
2 2 3 3 5 5
0
18
T36BN13●●
TeSys N Size 1 Contactor + TeSys LRD Bimetallic Overload Relay
TeSys N non-reversing starter, Size1
7.5 7.5 10 10 10 15 25 25 25 30 50 50 40 50 100 100 100 200 200 150 200 400 400 300 600 600 75 —
1 [7]
T36CN13●●
27
T36DN13●●
2
45
3
90
T36EN13●●
T36FN13●●
4
135
TeSys N non-reversing starter, Size3 TeSys N Size 1 Contactor + TeSys LR9D Electronic Overload Relay For more information on TeSys Deca relays, see Section 18.
5
270
T36GN13●●
T36HN13●●
6
540
Dimensions: page 16-23 TeSys N Accessories: pages page 16-18
7
810
T36JN13●●
Table 16.42: TeSys LR9D Electronic Overload Relays Current Setting Range (A) For Direct Mounting to TeSys N Contactors
Table 16.41: TeSys N Coil Voltage Codes Voltage
Class 5/10/20/30 Selectable
Voltage Code by NEMA Size Size 00 Size 0 Size 1 Size 2 Size 3 Size 4 Size 5 Size 6 Size 7
0.1–0.5 0.4–2.0 1.6–8.0 6.4–32
LR9D01 LR9D02 LR9D08 LR9D32
120Vac [8]
G7
G7
G7
G7
G7
G7
G7
F7
F7
Size00–1
Table 16.43: TeSys Deca Overload Relays—Ambient Compensated, Bimetallic, Direct Mounting Current Setting Range (A) For Direct Mounting to TeSys N Contactors Class 10 with Single-Phase Sensitivity Class 10 without Single-Phase Sensitivity
Class 20 with Single-Phase Sensitivity
Class 20 without Single-Phase Sensitivity
0.10–0.16 0.16–0.25 0.25–0.40 0.40–0.63
Size00–1 Size00–1 Size00–1 Size00–1 Size00–1 Size00–1 Size00–1 Size00–1 Size00–1 Size00–1 Size00–1 Size0–1 Size0–1 Size0–1 Size0–1
LRD01 LRD02 LRD03 LRD04 LRD05 LRD06 LRD07 LRD08 LRD10 LRD12 LRD14 LRD16 LRD21 LRD22 LRD32 LRD313 LRD318 LRD325 LRD332 LRD340 LRD350 —
LR3D01 LR3D02 LR3D03 LR3D04 LR3D05 LR3D06 LR3D07 LR3D08 LR3D10 LR3D12 LR3D14 LR3D16 LR3D21 LR3D22 LR3D32 LR3D313 LR3D318 LR3D325 LR3D332 LR3D340 LR3D350 —
— — — —
— — — — — —
0.63–1 1–1.6 1.6–2.5 2.5–4 5.5–8 7–10 9–13 12–18 16–24 17–24 23–32 9–13 12–18 16–25 23–32 30–40 37–50 4–6
LRD05L LRD06L LRD07L LRD08L LRD10L LRD12L LRD14L LRD16L LRD21L LRD22L LRD32L LRD313L LRD318L LRD325L LRD332L LRD340L LRD350L —
LR3D07L LR3D08L LR3D10L LR3D12L LR3D14L LR3D16L LR3D21L LR3D22L LR3D32L —
Size1 Size2 Size2 Size2 Size2 Size2 Size2
— — — — — —
[6] Replace the bullets (●●) in the catalog number with the coil voltage code. Refer to the coil voltage codes shown in Table 16.41. [7] Special size combinations of the contactor and Motor Logic overload relay are available. Add 0 to the catalog number before the coil voltage for a Size 0 overload relay (6–18 A); 9 for aSize 00C (3–9 A); and 8 for a Size 00B (1.5–4.5 A)—for example, T36CN13 0 G7. [8] The 24 and 120 Vac coils are available with optional separate control; add FormS to the catalog number (for example, T36AN13B7 S ).
16-16
© 2024 Schneider Electric All Rights Reserved
Made with FlippingBook Ebook Creator