Square D Digest 179
Manual Starters and Switches
Manual Starters, Type M and T—Integral Horsepower Class 2510, 2511, 2512 / Refer to Catalog 2510CT9701
www.se.com/us
Integral Horsepower
Types M and T integral horsepower manual starters provide convenient On-Off operation of small single phase, polyphase or DC motors. Typical applications include small machine tools, pumps, fans and conveyors. • Push button (M) or toggle (T) operators
• Reliable overload protection • Auxiliary contact available
16 NEMA AND DEFINITE PURPOSE CONTACTORS AND STARTERS
Table 16.16: Integral Horsepower Manual Starters (see Thermal Unit Selection, page 16-134) Non-Reversing, Class 2510, Max. Voltage: 600 Vac
NEMA1 Surface Mounting
NEMA4/4X Watertight, Dusttight and Corrosion Resistant Glass Polyester Enclosure
NEMA7&9 For Hazardous Locations Class I— GroupsC, D Class II— Groups E, F & G
Ratings
OpenType
NEMA12 Dusttight and Driptight Industrial Use Enclosure
NEMA4/4X Watertight and Dusttight Enclosure Brushed Stainless Steel
Square P.B. Operator
Square P.B. Operator
No. of Poles
NEMA Size
Toggle Operator
Toggle Operator
Max.Hp
Motor Voltage
Poly Phase
Single Phase
Type
Type
Type
Type [13]
Type
Type
115 230 115 230 115 230
— — — — — — — 3 5
1 2 2 3 3 5
MBW11 [14]
MBW1 [14]
— MBA1 [14]
M-0
—
TBG1
—
—
2 Pole
M-1
—
TCG1
MCW11
MCW1
—
MCA1
—
—
M-1P
MCG2
—
MCW12
MCW2
—
MCA2
MCO2
—
— — — — — —
200-230 380-575 200-230 380-575
MBW12 [14]
MBW2 [14]
MBR2 [14]
MBA2 [14]
M-0
MBG2
TBG2
MBO2
TBO2
3 Pole
— 7.5 10
MCG3
TCG3
MCW13
MCW3
MCR3
MCA3
MCO3
TCO3
M-1
1hpDC 1.5hpDC 1.5hpDC 2hpDC
115 230 115 230
M-0
—
TBG4
MBW14
MBW4
—
MBA4
—
TBO4
DC 2 Pole
M-1
—
TCG5
MCW15
MCW5
MCR5
MCA5
MCO5
—
Table 16.17: How to Order To Order Specify:
All Except NEMA 7 and 9 File E42243 CCNNLRV
All Except NEMA 7 and 9 File LR60905 Class 3211-05
Catalog Number
• Class Number • Type Number
Type
Class 2510
NEMA 7 and 9 Only File E58760 CCNNPXZ
NEMA 7 and 9 Only File LR26817 Class 3218-04
MCA1
[13] NEMA 7 & 9 enclosures are cast iron. NEMA 7 & 9 cast aluminum enclosures are also available; to order, replace the R in the catalog number with a T . For additional information, contact the Customer Care Center. [14] Approved for group motor installations per NEC 430-53(c).
16-8
© 2024 Schneider Electric All Rights Reserved
Made with FlippingBook Ebook Creator