Square D Digest 179
Mini Power-Zone Low Voltage Unit Substation
Mini Power-Zone Unit Substation
Class 7400 / Refer to Catalog 7440CT0901
www.se.com/us
Sealed, Mini Power-Zone™ Unit Substation The Square D™ brand Mini Power-Zone ™ unit substation from Schneider Electric provides the answer to requirements for a compact unit substation at low amperage ratings.. This complete package yields considerable savings on floor space, installation, and overall cost. NOTE: Mini Power-Zone unit substations are UL 1062 Listed File E92978 design in a Type 3R enclosure allowing for indoor or outdoor applications. Designed for wall mounting, the unit substation leverages Schneider Electric components integrated into one device. • Epoxy resin encapsulated low voltage transformer • H-frame main circuit breaker • Secondary main circuit breaker • Square D panel board or load center allowing for QO™ or QOB™ branch circuit breakers New MPU solution leverages the latest load center interiors, giving customers more flexibility for branch circuit requirements. Additionally design with a tiered dead front construction. The first dead front allows access to the secondary main circuit breaker, distribution panel board, and the second dead front. The second dead front allows access to the primary main circuit breaker and incoming voltage connection points.
Table 14.19: Distribution System Square D Load Centers (allowing plug-on QO circuit breakers only)
Primary Main Circuit Breaker Rating (A)
Secondary Main Circuit Breaker Rating (A)
Spaces for Branch Circuit Breakers
Full Capacity Taps[16]
Catalog No.
Weight (lbs)
Enclosure
kVA
Single Phase Unit Substation Input: 480 Vac, 18 kAIC; Output: 120 / 240 Vac 3 MPU3S40F 2–5%FCBN
MPU-A MPU-A MPU-A MPU-A MPU-B MPU-B MPU-C MPU-C MPU-C
85
15 15 20 30 60
15 30 40 60 80
10 10 10 10 22 22 27 27
5
MPU5S40F MPU7S40F MPU10S40F MPU15S40F MPU25S40F
2–5%FCBN 2–5%FCBN 2–5%FCBN 2–5%FCBN 2–5%FCBN
135 145 220 350 425 510 670 695
7.5 10 15 25
100
125
Three-Phase Unit Substation Input: 480 Vac 18 kAIC; Output: 208Y / 120 Vac 15 MPU15T2F 2–5%FCBN
40 60 90
60 80
22.5
MPU22T2F MPU30T2F
2–5%FCBN 2–5%FCBN
30
100 27 NOTE: Dimensions should not be used for construction. Contact you local Schneider Electric representative for certified prints. FCBN = Full Capacity Below Normal
Table 14.20: Bolt-On Circuit Breakers
Catalog No.
Primary Main Circuit Breaker Rating (A)
Secon daryMain Circuit Breaker Rating (A)
Spaces for Branch Circuit Breakers
Full Capacity Taps[16]
Weight (lbs)
Enclosure
kVA
18kAIC
25kAIC
65kAIC
Single-Phase Unit Substation Input: 480 Vac, 18 kAIC; Output: 120 / 240 Vac 3 MPUB3S40F MPUB3S40FSS
MPUB3S40FG MPUB3S40FJ MPUB5S40FG MPUB5S40FJ MPUB7S40FG MPUB7S40FJ MPUB10S40FG MPUB10S40FJ MPUB15S40FG MPUB15S40FJ MPUB25S40FG MPUB25S40FJ MPUB15T2FG MPUB15T2FJ MPUB22T2FG MPUB22T2FJ MPUB30T2FG MPUB30T2FJ
2–5% FCBN MPUB-AA 137 2–5% FCBN MPUB-AA 187 2–5% FCBN MPUB-AA 207 2–5% FCBN MPUB-AA 237 2–5% FCBN MPZUB-BB 367 2–5% FCBN MPZUB-BB 442 2–5% FCBN MPUB-CC 541 2–5% FCBN MPUB-CC 701 2–5% FCBN MPUB-CC 726
15 15 20 30 60
15 30 40 60 80
16 16 16 16 28 28 27 27 27
5
MPUB5S40F MPUB7S40F MPUB10S40F MPUB15S40F MPUB25S40F
MPUB5S40FSS MPUB7S40FSS MPUB10S40FSS MPUB15S40FSS MPUB25S40FSS
7.5 10 15 25
100
125
Three-Phase Unit Substation Input: 480 Vac, 18 kAIC; Output 208Y / 120 Vac 15 MPUB15T2F MPUB15T2FSS
40 60 90
60 80
22.5
MPUB22T2F MPUB30T2F
MPUB22T2FSS MPUB30T2FSS
30
100
Table 14.21: Enclosure Dimensions and Accessories Enclosure Number/ Style Height Width in. mm in. mm
Depth
Mounting
in.
mm 300 343 343
MPU-A MPU-B
32.90 43.20
836.0 1097.0 1148.0
14.00 21.00 27.40
356 533 696
11.80 13.50 13.50
Wall Wall Wall Wall Wall Wall
MPU-C 45.20 MPU-AA 43.20 MPU-BB 51.00 MPU-CC 51.20
— 16.00 — 27.40 — 27.40
— 11.75 — 13.50 — 13.50
— — —
14 TRANSFORMERS
14-13
© 2024 Schneider Electric All Rights Reserved
Made with FlippingBook Ebook Creator