Power-Zone™ Busway
Non-Segregated Bus
Class 6090 / Refer to Catalog 5600CT9101
www.se.com/us
Standard Construction Standard construction is as follows:
• Conductor (plating): Copper (silver) or Aluminum (tin) • Conductor Insulation (5 kV through 38 kV only): epoxy • Conductor Supports: Glass reinforced polyester blocks (5 kV and 15 kV); porcelain (38 kV) • Housing Material: Extruded Aluminum (1/8-inch Nominal) • Housing Construction: Totally Enclosed Non-ventilated • Joint Insulation: EPR and PVC tape • BIL Rating: 30 kV (600 V), 60 kV (5 kV) and 95 kV (15 kV) • Momentary (Short Circuit) Rating: 75 kA (600 V), 60 kA (5 kV, 15 kV), and 39 kA (38 kV) • Ground Conductor: Housing (100% rated) Table 12.44: Bus Enclosures Material and Finish Painted Aluminum (1/8” Nominal)
Painted 14 Gauge Steel Painted 11 Gauge Steel
Painted 14 Gauge 304 Stainless Steel Painted 14 Gauge 316 Stainless Steel Table 12.45: Momentary (Asymmetrical Short Circuit) Ratings Voltage Class
Ampere Options
75kA 100kA 125kA 150kA 60kA 80kA 100kA 150kA 39kA 49kA 62kA 100kA
600V
5kV 15kV
38kV
12 BUSWAY
12-20