Square D Digest 179
Gas-Insulated Ring Main Units for Secondary Distribution Systems Class 6047 / Refer to Brochure 6000BR1202
Medium Voltage Switchgear
www.se.com/us
Outgoing Line Module O DVCAS switchgear module O functions as an outgoing line to a downstream wind generator. There are two medium voltage cables per phase. Construction features include: • Metal base frame • Voltage presence indicator • MV cable compartment
– bushings for cable connection – clamps for MV cable connection
D + O Transformer protection + Outgoing line
DO
(I + D + O) Incoming line + Transformer protection + Outgoing line
I D
O
(I + I + D + O) Two Incoming lines + Transformer protection + Outgoing line
I I D O
Recommended Configurations
Incoming Line Module I DVCAS switchgear module I is a three-position switch-disconnector. It is recommended for the incoming line function from an upstream wind generator for the following reasons: • Reduces downtime caused by faults • Helps with fault detection • Reduces interruptions due to maintenance work • Improves energization works Module I is always connected to module D on the right with single-phase, coupling bushings. Construction features include: • Metal base frame • Operating mechanism compartment
Remote operation
Remote control
Motor power supply
– operating mechanism of the switch-disconnector – motor for the operating mechanism (optional) • MV cable compartment
RE - I
– bushings for cable connection • Stainless steel, gas-tight tank – busbar system – three position disconnector Table 11.56: Ratings Insulation level Powerfrequencywithstandvoltage(kV) Lightningimpulsewithstandvoltage,peak(kV) Rated current of the main busbar (A) Short time withstand current (kA/s) Short circuit breaking current capacity (kA) Short circuit making capacity, peak (kA) Internal arc withstand IAC AFL (kA/1s) Frequency (Hz) Rated voltage (kV)
11 SWITCHBOARDS AND SWITCHGEAR
M
Flair
Type
Rating
50/60
38
70
170 600
Module I
20/3 [24]
20 [24]
50
20 [24]
Degree of protection (NEMA/IP) HVcompartment
6/67
LVandoperatingmechanismcompartment
6P/3X
SF6 gas pressure at 20 ºC (PSI/bar)
4.35/0.3
[24] 25 kA for circuit breaker switchgear module D.
11-39
© 2024 Schneider Electric All Rights Reserved