Square D Digest 179

Air-Insulated Switchgear for Secondary Distribution Class 6045 / Refer to Catalog 6045CT9801

Medium Voltage Switchgear

www.se.com/us

Factory Modifications Table 11.33: Factory Modifications Catalog No.

Description

Auxiliary switch 2 N.O.–2 N.C. contact

HVLCC-X3

Distribution Class Surge Arresters (One Set of Three) Switch Load Side Connected or Incoming Line Bay) Table 11.34: Surge Arresters Catalog No. kVRating

Section Width Minimum Required in

mm 375 375 375 375 375 508 508

3 kV, 2.55 kV MCOV 6 kV, 5.10 kV MCOV 9 kV, 7.65 kV MCOV 10 kV, 8.40 kV MCOV 12 kV, 10.20 kV MCOV 15 kV, 12.70 kV MVOV 18 kV, 15.3 kV MCOV

HVLCCDSA3 HVLCCDSA6 HVLCCDSA9 HVLCCDSA10 HVLCCDSA12 HVLCCDSA15 HVLCCDSA18

14.75 14.75 14.75 14.75 14.75 20.00 20.00

600 A “Single” HVL/cc Switch with PROVISIONS ONLY for Square D™ brand Current-Limiting, Non-Disconnect Type Fuses for Cable Connection to Power Dry™, Power-Cast™, and Uni-Cast™ Transformers (FLC = 300 A MAXIMUM) RH—Transformer on right, LH—Transformer on Left

600 A, tin-plated, copper bus

Application A = Top Entry (Incoming Cables) Application B = Bottom Entry (Incoming Cables) Table 11.35: 600 A “Single” HVL/cc Switch Selection Catalog No. kV Rating Fuse Range Ap plica tion

Width

RH/ LH

in

mm 375 508 375 508 375 508 375 508 375 508 375 508 375 508 375 508

HVLCCA14405DGR HVLCCA20405DGR HVLCCA14405DGL HVLCCA20405DGL HVLCCA14415DGR HVLCCA20415DGR HVLCCA14415DGL HVLCCA20415DGL HVLCCB14405DGR HVLCCB20405DGR HVLCCB14405DGL HVLCCB20405DGL HVLCCB14415DGR HVLCCB20415DGR HVLCCB14415DGL HVLCCB20415DGL

4.76 4.76 4.76 4.76

10–450E 10–450E 10–450E 10–450E 10–200E 10–200E 10–200E 10–200E 10–450E 10–450E 10–450E 10–450E 10–200E 10–200E 10–200E 10–200E

A 14.75 A 20.00 A 14.75 A 20.00 A 14.75 A 20.00 A 14.75 A 20.00 B 14.75 B 20.00 B 14.75 B 20.00 B 14.75 B 20.00 B 14.75 B 20.00

RH RH LH LH RH RH LH LH RH RH LH LH RH RH LH LH

M

15 15 15 15

200E

90.00 2286

M

4.76 4.76 4.76 4.76

15 15 15 15

37.25 946

11 SWITCHBOARDS AND SWITCHGEAR

14.75 375

14.75 375

NOTE: Switches with transformer connections are painted ANSI 49. Standalone switches are painted ANSI 61. Transformer connections in HVL/cc switches are based on standard Square D™ brand transformer connections. If these switches are used to connect to other manufacturers' transformers, then connections must match standard Square D™ brand transformer connections. (Cable connections are furnished with the transformer.)

Listed Metal-Enclosed Interrupter Switchgear

11-27

© 2024 Schneider Electric All Rights Reserved

Made with FlippingBook Ebook Creator