Square D Digest 179
I-Line™ Panelboards—600 Vac, 250 Vdc
Molded Case Circuit Breakers for I-Line Panelboards
www.se.com/us
Refer to I-Line Power Distribution Panelboards Table 9.136: M-Frame 800 A, Basic Electronic Trip System Type ET 1.0 [69] Factory-Sealed Trip Unit (PowerPacT M-frame circuit breakers utilize 9 in. of the available I-Line bussing.) Electronic Trip Unit Ampere Rating Adjustable Instantaneous Trip Range Interrupting Rating
Terminal Wire Range
Type
High
Function
Low
G
J
2P, 600 Vac 50/60 Hz [70]
(3) 3/0 through 500 kcmil Al orCu (3) 3/0 through 500 kcmil Al orCu (3) 3/0 through 500 kcmil Al orCu (3) 3/0 through 500 kcmil Al orCu
MGA26400()
MJA26400()
400A
800
4000
Fixed Long-time, Adjustable Instantaneous Trip
Basic
MGA26600()
MJA26600()
600A
1200
6000
3P, 600 Vac 50/60 Hz
400A
800
4000
MGA36400
MJA36400
Fixed Long-time, Adjustable Instantaneous Trip
Basic
600A
1200
6000
MGA36600
MJA36600
Table 9.137: M-Frame 800 A, Adjustable Amperage Electronic Trip Unit Electronic Trip Unit Adjustable Long Time Settings Adjustable Instantaneous
Interrupting Rating
Terminal Wire Range
Type
High
Function
Low
G
J
2P, 600 Vac 50/60 Hz [70] Basic 3P, 600 Vac 50/60 Hz Basic
Adjustable Long time, Adjustable Instantaneous Trip Adjustable Long time, Adjustable Instantaneous Trip
MGA26800()E10 MJA26800()E10 (3) 3/0 through 500 kcmil Al orCu
300–800
2x
10x
9 PANELBOARDS
300–800
2x
10x
MGA36800E10
MJA36800E10 (3) 3/0 through 500 kcmil Al orCu
L-frame accessories, see PowerPact Accessories in Section 7 of the Digest. L-frame dimensions, see Molded Case Circuit Breaker Dimensions in Section 7 of the Digest. L-frame optional lugs, see Mechanical Lugs in Section 7 of the Digest.
M-frame accessories, see PowerPact Accessories in Section 7 of the Digest. M-frame dimensions, see Molded Case Circuit Breaker Dimensions in Section 7 of the Digest. M-frame optional lugs, see Mechanical Lugs in Section 7 of the Digest.
Table 9.138: Automatic Molded Case Switches—600 Vac, 50/60 Hz Ampere Rating 2-pole 3-pole Catalog Number [70] Catalog Number 240Vac
Withstand Rating [71]
Trip Point Amperes
Terminal WireRange
480Vac
600Vac
AC
PJA26000S60( ) PJA26000S80( ) PJA26000S10( ) PJA26000S12( )
600A 800A
PJA36000S60 PJA36000S80 PJA36000S10 PJA36000S12
100 100 100 100
65 65 65 65
25 25 25 25
10000 10000 10000 10000
(3) 3/0 through 500 kcmil Al or Cu (4) 3/0 through 500 kcmil Al or Cu
1000A 1200A
Table 9.139: PowerPacT P- and R-frame Interrupt Ratings Codes Voltage P-frame Interrupt Rating
R-frame Interrupt Rating
G
J
K
L
G
J
K
L
240Vac 480Vac 600Vac
65 kA 100 kA 65 kA 125 kA 65 kA 100 kA 65 kA 125 kA
35kA 65kA 18kA 25kA
50 kA 100 kA 35 kA 65 kA 50 kA 25 kA 18 kA 25 kA
65kA 100kA 65kA 50kA
PG/PJ/PK/PL 2– and 3–pole
RG/RJ/RK/RL 2– and 3–pole
[69] The ET 1.0 trip unit cannot be field replaced. The Basic Electronic ET1.0 trip unit (offered in 400 A and 600 A only) does not allow adjustment of the long time trip point setting. It is considered an electronic equivalent of a thermal-magnet circuit breaker. [70] Fill in parentheses with the following phase connection options: (2) for AC or (5) for CA. [71] The withstand rating is the fault current, at rated voltage, that the molded case switch will withstand without damage when protected by a circuit breaker with an equal ampere rating.
9-57
© 2024 Schneider Electric All Rights Reserved
Made with FlippingBook Ebook Creator