NF Panelboard Accessories
NF Panelboards—600Y/347 Vac Max.
Accessories
www.se.com/us
Accessories
Table 9.74: NF Merchandised Neutrals Mains Ampacity
Copper 100% Neutral Kit
200% Neutral Kit
Catalog No.
Catalog No.
125 250 400 600
NFNL1 NFNL2
NFN1CU NFN2CU NFN6CU
NFNL4 [78]
Factory Assembled Only
NFN6CU [78]
Table 9.75: NF Merchandised Interior Modification Kits Mains Ampacity Sub-feed Lugs [79] Feed-through Lugs [79] Catalog No. Catalog No.
Sub-feed Circuit Breaker Kits [79] (circuit breaker not Included)
Mains Ampacity
Single Sub-feed Circuit Breaker
Twin Sub-feed Circuit Breakers
Catalog No.
Catalog No.
125 250 400 600 800
NF125SFL NF250SFL
NF125FTL NF250FTL NF400FTL
250 400 600 800
NF250SFBH/NF250SFBJ N600MPPL (400 A Max.) NF600SFBPPL (600A) [80]
—
NF600SFBH NF600SFBJ [80]
NF400SFL [81]
Factory Assembled Only
Factory Assembled Only
Factory Assembled Only NOTE: NF250SFBH and NF600SFBH are for use with HDL, HGL, HJL, HLL, and HRL circuit breakers. NF250SFBJ and NF600SFBJ are for use with JDL, JGL, JJL, JLL, and JRL circuit breakers.
9 PANELBOARDS
Table 9.76: Optional Main Lug Kits for Main Lug Panelboards Ampacity Al Compression Lug Kit
Cu Mechanical Lug Kit
Cu Compression Lug Kit [81]
Catalog No. NFALV1 [82]
Lug Wire Range
Catalog No.
Lug Wire Range
Catalog No. NFCUV1 [83] NFCUV2 [83]
Lug Wire Range one #6–1/0 AWG
125 250 400 600 800
one #4 AWG–300 kcmil
NFCUM1 NFCUM2 NFCUM4 NFCUM6
#6–2/0AWG
NFALV2 NFALV4 NFALV6
one 250–350 kcmil
#6 AWG–250 kcmil
one 2/0 AWG–300 kcmil
one 1/0 AWG–750 kcmil, or two 1/0 AWG–350 kcmil two 1/0 AWG–750 kcmil
two 2/0 AWG–500 kcmil two 2/0 AWG–500 kcmil
NFCUV4 NFCUV6
one 400–750 kcmil two 250–500 kcmil
Contact your local Schneider Electric representative or distributor.
[78] Not to be used with SFL, FTL, or SFB. These combinations are factory assembled only. [79] Available factory assembled only on non-linear panelboards. [80] Sub-feed circuit breakers may not be field installed onto NF Panelboards with PowerPacT L main circuit breakers. [81] Use copper wire only. [82] Use of this kit requires an additional 6 in. added to box height. [83] Use of this kit to terminate larger than standard wire size requires an additional 6 in. added to box height.
9-31