Square D Digest 179
QOB Circuit Breakers for NQ Panelboards
NQ Panelboards—240 Vac, 48 Vdc
Online Refer to NQ Panelboards
www.se.com/us
Table 9.11: QO/QOB Circuit Breaker Wire Sizes Breaker Type Ampere Rating
Wire Size (AWG or kcmil)
Al
Cu
10–30A 10–30A 35–70A 10–30A 10–30A 35–70A 80–125A 150–200A 10–30A 35–70A 80–125A 110–150A 15–30A
#14–8
#14–8
QOB 1-pole
—
two#14–10
#8–2 #14–8
#8–2 #14–8
—
two#14–10
QOB 2-pole
#8–2
#8–2
#4–2/0 #4–300 #14–8 #4–2/0 #4–300 #12–8 #12–4 #8–2
#4–2/0 #4–300 #14–8 #4–2/0 #4–300 #14–8 #8–2
QOB 3-pole
QOB-VH
QOB-GFI and QOB-EPD
40, 50, or 60 A #14–6 Table 9.12: QO ™ Arc-Fault and Dual Function Circuit Breakers [79][80][81]
1P120Vac 10kAIR 1Space Required
1P120Vac 22kAIR 1Space Required
2P240Vac 10kAIR 2Space Required
2P240Vac 22kAIR 2Space Required
Circuit Breaker Type Ampere Rating [81]
Catalog Number QOB115CAFI QOB120CAFI
Catalog Number Catalog Number Catalog Number
9 PANELBOARDS
Combination Arc-Fault Interupter Dual Function: Arc-Fault and Ground Fault
QOB115VHCAFI QOB120VHCAFI
QOB215CAFI QOB220CAFI
QOB215VHCAFI QOB220VHCAFI
15A 20A 15A 20A
QOB115DF QOB115VHDF Use plug-on QO 2–pole dual function MCBs QOB120DF QOB120VHDF NOTE: For accessories, see Accessories for QO/QOB Circuit Breakers, in Section7. Single Phase 400 or 600 A NQ Panelboards now accept 150, 175, and 200 A Two Pole QO Plug-on Branch Circuit Breakers. Each breaker takes four pole spaces. Installation into three phase interiors is not allowed as it may create a phase to phase short circuit. One NQ200AN neutral lug kit should be installed for each pair of 175 or 200 A QO breakers if a neutral termination is required. • One Q1150AN lug kit should be installed for each 110 to 150 A QO(B) circuit breaker, if a neutral termination is required. – Table 9.13: High Ampacity Plug-on Two Pole QO Branch Circuit Breakers Catalog Number Ampere Rating AICRating QO2150 150 10kA QO2150VH 150 22kA QO2175 175 10kA QO2200 200 QO2175VH 175 22kA QO2200VH 200 NOTE: May only be installed on Single Phase 400 or 600 A NQ Panelboards with three point latch trim fronts. A maximum of four 150, 175, or 200 A QO (VH) plug-on branch circuit breakers may be installed in NEMA 1 enclosures. These enclosures require NCxxV( )3P three point latch trim fronts, as listed in Main Lug Interiors, page 9-7 or Main Circuit Breaker Interiors, page 9-8. One 150, 175, or 200 A QO (VH) plug-on branch circuit breaker may be installed in 8.75 in. deep MHxxD9VWP NEMA 3R enclosures, as listed in Main Lug Interiors, page 9-7 or Main Circuit Breaker Interiors, page 9-8.
[79] UL Listed as HACR type for use with air conditioning, heating, and refrigeration equipment having motor group combinations and marked for use with HACR type circuit breakers. [80] QO arc-fault circuit breakers provide branch feeder protection (for example, QO115AFI) or combination protection (for example, QO115CAFI) as required by the NEC and local code adoption, and comply with UL 1699. [81] 10–30 A circuit breakers are suitable for use with 60°C or 75°C conductors. 35–60 A circuit breakers are suitable for use with 75°C conductors.
9-13
© 2024 Schneider Electric All Rights Reserved