Square D Digest 179
NQ Panelboards—240 Vac, 48 Vdc
NQ Merchandised Main Circuit Breaker Interiors
Online Refer to NQ Panelboards
www.se.com/us
NQ 14-inch-wide—240 Vac, 48 Vdc [58] Features
14-inch-wide NQ panelboards are available for those customers whose equipment space is limited. Developed with customer input, Square D™ brand NQ panelboards are built to last, featuring innovations for ease of installation and durability. • 240 Vac, 48 Vdc maximum • 225 A maximum main circuit breaker or main lugs • 100 A maximum branch circuit breakers • Interiors accept bolt-on and plug-on branch circuit breakers • Three-phase, four-wire, and single-phase, three-wire interiors available • Panelboards available with Mono-Flat™ front • May be suitable for use as service entrance equipment with neutral bonding kit and main circuit breaker barrier installed • Branch circuit filler plates provide fast and easy installation • Both fully and series-rated systems are available Table 9.5: Main Lug Interiors—Accepts Plug-On and Bolt-On Branch Breakers • Visi-Trip ™ indication on branch circuit breakers • 10,000–65,000 A Short Circuit Current Rating (SCCR) • Interiors supplied with silver flashed copper bus as standard
9 PANELBOARDS
Interior Only (Order Branch Circuit Breakers Seperately)
NEMA Type 1 Enclosure
Main Ratings
Max. Number of Breakers
Box 14 in. W x 5.75 in.Db
MonoFlat Front
14–inch wide NQ Panelboard Main Lug
Hinged Front
Cat. No. [59]
Cat. No.
Cat. No.
Cat.No.
14-inch-wide Cabinet—Single Phase 3-Wire 18 100A
NQC32 ( ) NQC32 ( ) NQC32 ( ) NQC38 ( ) NQC32 ( ) NQC32 ( ) NQC32 ( ) NQC38 ( )
NQ18L1C14 NQ30L1C14 NQ30L2C14 NQ42L2C14 NQ418L1C14 NQ430L1C14 NQ430L2C14 NQ442L2C14
NQB532 NQB532 NQB532 NQB538 NQB532 NQB532 NQB532 NQB538
N/A N/A N/A N/A N/A N/A N/A
30 30 42
225A
14-inch-wide Cabinet—Three Phase 4-Wire 18 100A
30 30 42
225A
N/A Table 9.6: Main Circuit Breaker Interiors—Accepts Plug-On and Bolt-On Branch Breakers
NEMA Type 1 Enclosure
Interior Only (Order Branch Circuit Breakers Seperately)
Main Circuit Breaker Panelboard
Max. Number of Break ers
Box14 in.Wx 5.75 in. Db Cat. No. [61]
Main Circuit Breaker Kit [60]
Main Rat ings
ULSE Barri erKit
MonoFlat Front
Hinged Front
Main Circuit Breaker Frame
Cat. No. [59]
Cat. No.
Cat. No.
14-inch-wide Cabinet—Single Phase 3-Wire 16 [62] 100 NQ18L1C14
NQB532 NQC32 ( ) NQB532 NQC32 ( ) NQB544 NQC44 ( )
N/A N/A N/A
— — Select QOB 2 pole or QOB-VH [60] — —
28 [62]
NQ30L1C14
HD, HG,HJ, HL, HR JD, JG, JJ, JL, QB , QD, QG,QJ
NQ30L2C14 NQMB2H J14 or NQMB2Q14 NQ42L2C14
30
HJQL LC
225
NQB550 NQC50 ( )
N/A
42
14-inch-wide Cabinet—Three Phase 4-Wire 15 [62] 100 NQ418L1 C14
Main Lug Panelboard
NQB532 NQC32 ( )
N/A
— — Select QOB 3 pole or QOB-VH [60] — —
NQ430L1 C14 NQ430L2 C14 NQ442L2 C14
27 [62]
NQB532 NQC32 ( )
N/A
HD, HG,HJ, HL, HR JD, JG, JJ, JL, QB , QD, QG,QJ
NQMB2H J14 or NQMB2Q14
NQB544 NQC44 ( )
30
N/A
HJQL LC
225
NQB550 NQC50 ( )
N/A
42
Table 9.7: NQ Accessories Available on NQ 14” Panelboards Description
Catalog No.
Equipment Ground Bars Aluminum (twenty seven terminations #14 to #4 AWG)
PK27GTA PK23GTAL PK27GTACU
PK23GTA+ #1 to #4/0 AWG Al or Cu lug
Copper (twenty seven terminations #14 to #4 AWG)
Ground Bar Insulator Kit
PKGTAB
Handle Attachments—Branch Circuit Breakers Handle lock-off
HLO1
Handle tie - (QO and QOB only) Handle padlock attachment—1-pole
QO1HT QO1PA QO1PL QO3HT
2- and 3-pole
Handle tie and lock-off for three 1-pole (QO, QOB)
Other Accessories Filler plates (15 per package)
NQFP15
[58] DC voltage applications require installation of DC rated QO(B) circuit breakers. [59] Add “F” for flush mount, “S” for surface mount. [60] Select a Q or H frame circuit breaker, HJQLLC barrier (and associated main circuit breaker kit) from the list for 225 interiors, for panels to be "Suitable for use as UL service equipment." [61] All 14 in. W boxes come with blank endwalls. [62] Pole spaces shown are available for branch circuits, with spaces deducted for the back-fed main circuit breaker.
9-10
© 2024 Schneider Electric All Rights Reserved
Made with FlippingBook Ebook Creator