Enclosure Accessories and Dimensions

Circuit Breaker Enclosures

Class 610

www.se.com/us

Enclosure Accessories Table 7.169: Neutral Kit Terminal Data Neutral Kit Catalog Number

Terminal Lug Data -Total Available (Line plus Load) AWG/kcmil AL/CU

All Copper Neutral Terminal Lug Data -Total Available (Line plus Load) AWG/kcmil

(2) 14–1/0 Cu or (2) 12–1/0 Al plus (1) 14–4 Cu

100SNA

(4) 14–1/0 Cu or (4) 12–1/0 Al

SN100FA SN225KA 225SNA

— — — — — —

(2) 4–300 Al/Cu plus (2) 14–1/0 Al/Cu

(4) 6–350 Al/Cu

(2) 1–600 or (4) 1–250 Al/Cu, plus (2) 4–300 Al/Cu (2) 1–600 or (4) 1–250 Al/Cu, plus (2) 4–300 Al/Cu (6) 3/0–500 Al/Cu, plus (1) 1–4/0 Al/Cu

400SN

SN400LA SN1000MA SNC400LX SNC800LX AL800SN

(2) 2–-600 Cu, plus (2) 6–250 Cu (4) 2–600 Cu, plus (1) 2–4/0 Cu

— —

(6) 3/0–500 Al/Cu, plus (2) 6–250 Al/Cu (8) 3/0–750 Al/Cu, plus (2) 6–350 Al/Cu (8) 3/0–500 Al/Cu, plus (2) 4–300 Al/Cu

— — —

SN1200

S33576MK

Table 7.170: Service Ground Kit Terminal Data Service Ground Kit Catalog Number

Terminal Data AWG/kcmil 14–2Al/Cu 6–300 Al/Cu 6–250 Al/Cu 10–2/0 Cu or 6–2/0 Al

Lugs Per Kit

PKOGTA2 PKOGTH150 PKOGTJ250 PKOGTA4

2 2 2 4

Terminal Shields for Service Entrance Applications – Can be applied as line side barriers in service entrance applications – Will fit on top or bottom of the circuit breaker

Table 7.171: Terminal Shields Frame

2P

3P

PowerPacT Q

QSB2

QSB3

PowerPacT H (3 AWG Max. Wire Size) PowerPacT H (3/0 Max. Wire Size)

— — — — — —

S37446 S37447 S37448 MGJTC PA12TC LAHTC

PowerPacT J PowerPacT M PowerPacT P

LA/LH

J-Frame Short LugShield

See Supplemental Digest Section 3 for special options for enclosures: • Stainless steel fronts • Pilot lights, push buttons • Lock-on SPL0 • Key interlock systems • Legend plates

CIRCUIT BREAKERS

7 MINIATURE AND MOLDED CASE

7-89