Square D Digest 179

Motor Circuit Protectors

Motor Circuit Protectors and Motor Protector Circuit Breakers

www.se.com/us

Class 580, 585, 680, 685

PowerPacT Motor Protector Circuit Breakers—Two Device Solutions MicroLogic 2.2M and 2.3M trip units provide built-in thermal and magnetic protections. Use PowerPacT Motor Protect Circuit Breakers in two-device motor feeder solutions to provide protection against short-circuits, overloads, and phase unbalance. • Protection settings are made using a rotary switch.

Accessories see page 7-55 and Supplemental Digest Section 3 Optional Lugs see page 7-60 and Supplemental Digest Section 3

Dimensions see page 7-85 Enclosures see page 7-86

• Accept the same accessories and terminals as equivalent PowerPacT circuit breakers. • UL, CSA, NOM, IEC, CCC certified, and UKCA and CE marked for global acceptance. Table 7.92: H-Frame (150 A), J-Frame (250 A) and L-Frame (600 A) Electronic Motor Protector Circuit Breakers (UL Ratings)— Two Device Solutions [10] Electronic Trip Unit Type Frame Sensor Rating Trip Unit Isd (xFLA) Interrupting Rating

Full Load Amperes Range (FLA)

G

J

L

R

30 50

14–25 14–42 30–80 58–130 114–217 190–348 312–520

5-13 x FLA HGL36030M38X 5-13 x FLA HGL36050M38X 5-13 x FLA HGL36100M38X 5-13 x FLA HGL36150M38X 5-13 x FLA JGL36250M38X 5-13 x FLA LGL36400M38X 5-13 x FLA LGL36600M38X

HJL36030M38X HJL36050M38X HJL36100M38X HJL36150M38X JJL36250M38X LJL36400M38X LJL36600M38X

HLL36030M38X HLL36050M38X HLL36100M38X HLL36150M38X JLL36250M38X LLL36400M38X LLL36600M38X

HRL36030M38X HRL36050M38X HRL36100M38X HRL36150M38X JRL36250M38X LRL36400M38X

H-Frame

100 150 250 400 600

2.2M

Standard [11]

J-Frame L-Frame

2.3M

LRL36600M38X To select combination starters and motor controllers using MCP’s meeting NEC Article 430, refer to Section 16. PowerPacT H, J, and L-Frame Motor Protectors Table 7.93: Application of PowerPacT H- and L-Frame Motor Protector Circuit Breaker Hp Ratings of Induction Type Squirrel Cageand Wound Rotor Motors 3Ø60Hz Full Load Amperes [12] PowerPacT Family Motor Protector Circuit Breaker Cat.No. [13] Magnetic Trip Settings [14]

200 Vac 230 Vac 460 Vac 575 Vac

MIN

MAX

H( )L36030M38X H( )L36030M38X H( )L36030M38X H( )L36030M38X H( )L36030M38X H( )L36030M38X H( )L36030M38X H( )L36050M38X H( )L36050M38X H( )L36050M38X H( )L36050M38X H( )L36050M38X H( )L36050M38X H( )L36050M38X H( )L36050M38X H( )L36100M38X H( )L36100M38X H( )L36100M38X H( )L36100M38X H( )L36100M38X J( )L36250M38X L( )L36400M38X L( )L36400M38X L( )L36400M38X L( )L36400M38X L( )L36400M38X L( )L36400M38X L( )L36400M38X L( )L36400M38X L( )L36400M38X L( )L36600M38X L( )L36600M38X L( )L36600M38X L( )L36600M38X L( )L36600M38X L( )L36600M38X L( )L36600M38X L( )L36600M38X

10

14

5

15.2

500% 1300%

15

17

5

17.5

15

21 22

7-1/2

20

500% 1300%

7-1/2

25.3

20

25

27 28 32 34 40 41 42 52 54 62 65

10

30

500% 1300%

HJL36100M38X Motor Circuit Protector

10

32.2

25 30

40

500% 1300%

15

15

48.3

40

50

20

500% 1300%

20

60

MicroLogic 2.2M and 2.3M Trip Units

50

75

221 240 242 248 285 289 302 312 336 359 360 361 382 414 472 477 480

200

500% 1300%

250

100

100

300

500% 1300%

250

125

350

7 MINIATURE AND MOLDED CASE

125

500% 1300%

150

300

400

150

350

500% 1300%

500

400

CIRCUIT BREAKERS

200

[10] Two-device solutions (these electronic motor protector circuit breakers include short circuit and overload protection) • 1 electronic motor circuit protector with a MicroLogic 2.2 M plus • 1 contactor [11] The standard trip unit offers Class 5, 10 and 20 and phase unbalance or phase loss protection.

[12] Motor full-load currents are taken from NEC Table 430.250. Select wire and circuit breakers on basis of horsepower rather than nameplate full-load current per NEC 430.6 (A) for general motor applications. Do not use these values to select overload relay thermal units. See Digest Section 14 for selection of thermal units when actual full load current is not known. The voltages listed are rated motor voltages. Corresponding nominal system voltages are 200–208, 220–240, 440–480 and 550–600 V. [13] To complete catalog number, replace the blank with the appropriate rating (G, J, L or R). [14] Only MIN and MAX settings are shown, intermediate settings are available on all circuit breakers.

7-52

© 2024 Schneider Electric All Rights Reserved

Made with FlippingBook Ebook Creator