Square D Digest 179
B-Frame Circuit Breakers
PowerPacT™ Molded Case Circuit Breakers
www.se.com/us
Class 0613 / Refer to catalog 0611CT1603
Table 7.48: B-Frame Termination Options Termination Letter and Description Example A I-Line (See Section 9, Panelboards) BD L 36100 For factory-installed
Table 7.49: B-Frame Lug Options Lug Option Suffix No Suffix = EverLink Lugs both ends
BD L 36100 LU For factory-installed lug option, place suffix after the amperage in the circuit breaker catalog number.
LU = EverLink Lug with Control Wire Terminal ON end; EverLink Lug OFF end LV = EverLink Lug ON end; EverLink Lug with Control Wire Terminal OFF end LW = EverLink Lug with Control Wire Terminal both ends LC = Copper Mechanical Lugs both ends LH = Aluminum Mechanical Lugs both ends Table 7.50: PowerPacT B-Frame 125 A Magnetic Trip Values Current Rating @ 40 o C
termination, place termination letter in the third block of the circuit breaker catalog number. In this example “L” indicates EverLink Lugs for both ON and OFFends.
No Lugs (includes terminal nut kit on both ends)
F
L ON end: EverLink Lugs OFF end: EverLink Lugs M ON end: EverLink Lugs OFF end: Terminal Nut Kit P ON end: Terminal Nut Kit OFF end: EverLink Lugs
Fixed AC Magnetic Trip
Trip
Hold 400A 400A 480A 480A 480A 480A 480A 480A 640A 800A 800A
15A 20A 25A 30A 35A 40A 45A 50A 60A 70A 80A 90A
600A 600A 720A 720A 720A 720A 720A 720A 960A
1200A 1200A 1500A 1500A 1500A 1500A
1000A 1000A 1000A 1000A
100A 110A 125A
Accessories see page 7-55 Optional Lugs see page 7-60 Dimensions see page 7-85
CIRCUIT BREAKERS
7 MINIATURE AND MOLDED CASE
7-33
© 2024 Schneider Electric All Rights Reserved
Made with FlippingBook Ebook Creator