Square D Digest 179
Miniature Circuit Breakers
Selection Information
Class 500, 600
www.se.com/us
Multi9, EDB Miniature Circuit Breakers Multi9™ Circuit Breakers and Supplementary Protectors
EDB Circuit Breakers
Plug-on Bolt-on
— —
— —
—
—
—
Circuit Breaker Type
EDB
EGB
EJB
UL1077 C60 SP [23]
UL489 C60 BP
C60H-DC
—
—
—
UnitMount
3,4
2, 3
2, 3
2, 3
Number of Poles Current Range (A) Interrupting Ratings
1
2
3
1
2
1
2
1
1
1
0.5–63 0.5–63 0.5–63 0.5–63 1–63 1–63 0.5–63
0.5–63 15–70 15–125 15–70 15–125 15–70 15–125
14 [24]
14 [24] 14 [24] 14 [24]
14 [24] 14 [24] 14 [24]
14 [25] 14 [25] 14 [25]
14 [25] 14 [25] 14 [25] 10 [27]
14 [25] 14 [25] 14 [25] 10 [27] 10 [27]
120Vac
— — — — —
— 25 — 18 — 18 — 18
25 25 25 18
65 35 35 35
65 65 65 35
100
100 100 100
UL/CSA Rating (kARMS) (50/60Hz)
120/240 Vac 14 [24]
65 65 65
240Vac [26]
14 [24]
— — — 10 [27]
277Vac
65
10 [29]
10 [29]
480Y/277 Vac 10 [28]
— 10 [27]
— — 18
— 35
— 65
48Vdc 60Vdc 65Vdc 125Vdc 250Vdc 500Vdc 240Vac 415Vac
— — — — 10
— 5
5 5 5 5 5
— — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — —
10
10
— 20
— — 5
— — — — — — 5
DCRatings
— 10
— — — — 5
— — — — — — 5 — — — — — — — 5 [30]
IEC 60947-2 (50/60Hz) Icu Special Ratings CCC Other Standard
10
20
20 10
10
20
20
— —
— 20 — 10
— 10
— 5
5
— — — — —
X
X
X
X
X
X
X
X
— — — — — —
IEC
HACR
Accessories and Modifications Shunt Trip
X [31]
X [31]
X [31]
X [31]
X [31]
X [31]
X X X X X X
X X X X X X
X X X X X X
X X X X X X
X X X X X X
X X X X X X
X X X X X X
X X X X X X
Undervoltage Trip Auxiliary Switches
— — — — — —
X [31] X [31]
X [31] X [31]
X [31] X [31]
X [31] X [31]
X [31] X [31]
X [31] X [31]
Alarm Switch
Handle Operators
— — — — — —
Handle Padlock Attachment
X
X
X
X
X
X
Trip System Type Thermal-magnetic Molded Case Switch
X
X
X
X
X
X
X
X
X
X
X
X
X
X
— — — — — — —
— — — — — — —
Dimensions (1P Unit Mount) Dimensions (1P Unit Mount) in. (mm)
Height Width Depth
4.05 (103) 0.71 (18) 2.76 (70)
3.19 (81) 0.71 (18) 2.76 (70)
3.19 (81)
5.66 (144) 0.98 (25) 4.05 (103)
0.71 (18)
1.42 (36)
2.56 (65)
Pages
page7-24
See Section 9
NOTE: All circuit breakers on this chart are UL Listed and CSA Certified unless otherwise noted.
[23] C60 are recognized components per UL 1077. [24] 14 kA up to 35 A, 10 kA from 40 to 63 A. [25] 14 kA up to 32 A, 10 kA from 40 to 63 A. [26] For information regarding 3Ø corner grounded systems see the Supplemental Digest, Section 3. [27] 10 kA up to 32 A, 5 kA from 40 to 63 A. [28] Up to35A. [29] 10 kA up to 35 A. [30] 2 poles must be wired in series for 500 Vdc. [31] Factory-installed option only.