Square D Digest 179
PowerLogic ™ P Series Protection Relays
PowerLogic P5 Applications
www.se.com/us
Table 5.1 Protection Functions (cont'd.) Protection Functions
ANSI code
P5F30
P5M30
P5T30
Overspeed [5] Anti-backspin [5] Line protection Fault locator Auto-Recloser
12
— —
2 1
— —
ABS
21FL
1 1 1 1
— —
— —
79
Transformer protection Magnetizing inrush detection Fifth harmonic detection 2-winding transformer differential
68H2 68H5
1 1
2
—
87T
— —
— — — —
1 2
Thermostat / Buchholz Capacitor protection Capacitor bank unbalance Capacitor overvoltage Other protection Arc-flash detection Programmable stages Programmable curves
26–63
51C 59C
2 1
— —
50ARC
8 8 3 1 1 1 1 4
8 8 3
8 8 3
99 —
Control, monitoring, supervision Synchronization check
25 86 60 60 —
—
—
Lockout relay CT supervision VT supervision Setting groups
1 1 1 4
1 2
—
4
Table 5.2: Control Functions Control Functions Control with Mobile application Switchgear control and monitoring
P5F30
P5M30
● 6 2 ● ● ● ● 7 ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
● 6 2 ● ● ● ● 7 ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
Switchgear monitoring only
Programmable switchgear interlocking Local control on single-line diagram
Local switchgear control with OPEN/CLOSE keys
Local/remote function
Function keys
Custom logic (equations)
Table 5.3: Measurement Functions Measurement functions
P5F30
P5M30
RMS current values RMS voltage values
RMS active, reactive and apparent power
Frequency
Fundamental frequency current values Fundamental frequency voltage values
Fundamental frequency active, reactive and apparent power values
Power factor
Motor speed detection [5]
Energy values: active and reactive Demand values: phase currents
Demand values: active, reactive, apparent power and power factor
Maximum demand values: phase currents
Minimum and maximum demand values: RMS phase currents
Minimum and maximum demand values: active, reactive, apparent power and power factor Maximum demand values over the last 31 days and 12 months: active, reactive, apparent power Minimum demand values over the last 31 days and 12 months: active, reactive power
5 PROTECTION, CONTROL, AND ENERGYAUTOMATION
Maximum and minimum values: currents Maximum and minimum values: voltages Maximum and minimum: frequency Table 5.4: Logs and Records Logs and records
P5F30
P5M30
Sequence of event record Disturbance record Tripping context record Relay maintenance data log
● ● ● ● ●
● ● ● ● ●
Security data log
Table 5.5: Monitoring Functions Monitoring functions
ANSI code
P5F30
P5M30
Trip circuit supervision Circuit breaker monitoring
74 — —
1 1 ●
1 1 ●
Relay monitoring
Function available if 12 DI / 4 DO board is present.
[5]
5-5
© 2024 Schneider Electric All Rights Reserved